elevator motors or other large-current drawing machines) will have no effect on
the communication network if this configuration is used.
However, the power supplies must be truly floating, with no hidden paths back
to the high-voltage side of the transformers, or to earth ground. Since this
is difficult to achieve (there is always some parasitic capacitance between
the primary and secondary in any transformer), this method may be more
susceptible to high-frequency transients in the high-voltage side of the power
lines than the earth-grounded method.
The master unit’s ground establishes the ground for the entire system. The
main board ground points are connected to the shield ground at each unit,
but are not connected to earth ground. The ground point on the master can
be the data converter power supply negative terminal, or the GND pin on the
RS-232 cable. If the master is an HGU, its main board ground can be used.
This configuration should only be used if the power supplies to the units are
truly floating, otherwise ground loops will be created, and differences in local
grounds may cause large currents to flow through the cable shield.
Содержание SCHLAGE HP-3000
Страница 1: ...Terminal User s Guide HP 3000 4000...
Страница 12: ...Introduction 10 This page is intentionally blank...
Страница 24: ...Planning An Installation 22 This page is intentionally blank...
Страница 32: ...Networking and Communications 30 This page is intentionally blank...
Страница 44: ...Wiring Connections 42 This page is intentionally blank...
Страница 46: ...Planning an Installation 44 This page intentionally blank...
Страница 48: ...Planning an Installation 46 This page intentionally blank...
Страница 52: ...Enter a Command Menu 50 This page is intentionally blank...