WIRING SCHEMATIC
Refer to Page 30 for Schematic
INTELLYSIS CONTROLLER INACTIVATED
The photo on page 21 illustrates a condition that can render the Intellysis
controller inoperative; display error codes 01 through 06 or 8’s appearing on the
display.
SYMPTOMS:
1. The Intellysis controller does not power up, even though power is present
at the primary and secondary contacts of the transformer and interface
board or intermittent contact will give various error codes.
CAUSE:
The electrical signal in the pressure transducer can ground itself fully or
intermittently when the 4 prong adopter is installed in the cable housing.
The spade connection at the end of the wire may contact the inner metal
wire sheath of the cable connector. Note photo A on page 21.
There are four wires inside the cable (red, green, black, white). Therefore
several combinations of ground contact is possible. Note photo B on
page 21.