3. Analogue input 3 (
AI3
):
Parameter
M12
=0
Remote control
sensor for zone 1
Sensor
AI3
is used as a control sensor for zone 1.
M12
=1
Remote control
sensor for zone 2
Sensor
AI3
is used as a control sensor for zone 2.
M12
=2
Remote control
sensor for zone 3
Sensor
AI3
is used as a control sensor for zone 3.
M12
=3
Remote control
sensor for zone 4
Sensor
AI3
is used as a control sensor for zone 4.
M12
=4
External sensor
Sensor
AI3
is used as an external sensor for control with compensation
M12
=5
Floor sensor for
zone 1
The
AI3
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M12
=6
Floor sensor for
zone 2
The
AI3
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M12
=7
Floor sensor for
zone 3
The
AI3
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M12
=8
Floor sensor for
zone 4
The
AI3
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M12
=9
Remote season
changeover contact
M13
=
0
1
Summer
Winter
M12
=10
Remote on/off
M13
=
0
1
On
Off
M12
=11
Non-occupied
holiday
M13
=
0
1
“Non-occupied holiday” mode
Occupied mode
M12
=12
Economy mode
M13
=
0
1
No economy mode
Economy mode
M12
=13
The
AI3
sensor is used for the dew point calculation (only for the
MASTER or SLAVE_Y controller)
M12
=14
The
AI3
sensor is used as limit sensor for the MASTER or SLAVE:Y
controller
M12
=15
Sensor not used
M12
=16
0..10 V input
)RUFRQ¿JXUDWLRQV
M12
=9, 10, 11, 12, the analogue input 3 is used as a digital input. The contact is considered closed
if there is a short-circuit on the analogue input. The contact is considered open if there is no connection.