117/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
Registers
Description
Default
Min
Max.
R/W
7467
DIGITAL_OUTPUT1_FUNC
(see table pag.
36
)
0=Speed 1 of the ON/OFF fan
2=Speed 2 of the ON/OFF fan
2=Speed 3 of the ON/OFF fan
3=ON/OFF fan 1
4=ON/OFF fan 2
'HKXPLGL¿HU
6=ON/OFF thermal actuator output 1
7=ON/OFF thermal actuator output 2
8=ON/OFF thermal actuator output 3
9=ON/OFF thermal actuator output 4
10=ON/OFF valve
11=Local pump
12=Column pump
13=Dew point or condensation alarm
(Note3)
14=Control request
(Note3)
15=Season changeover
(Note3)
16=Not used
M15
16
0
16
R
7468
DIGITAL_OUTPUT2_FUNC
(see table pag.
36
)
0=Speed 1 of the ON/OFF fan
2=Speed 2 of the ON/OFF fan
2=Speed 3 of the ON/OFF fan
3=ON/OFF fan 1
4=ON/OFF fan 2
'HKXPLGL¿HU
6=ON/OFF thermal actuator output 1
7=ON/OFF thermal actuator output 2
8=ON/OFF thermal actuator output 3
9=ON/OFF thermal actuator output 4
10=ON/OFF valve
11=Local pump
12=Column pump
13=Dew point or condensation alarm
(Note3)
14=Control request
(Note3)
15=Season changeover
(Note3)
16=Not used
M16
16
0
16
R
7469
DIGITAL_OUTPUT3_FUNC
(see table pag.
36
)
0=Speed 1 of the ON/OFF fan
2=Speed 2 of the ON/OFF fan
2=Speed 3 of the ON/OFF fan
3=ON/OFF fan 1
4=ON/OFF fan 2
'HKXPLGL¿HU
6=ON/OFF thermal actuator output 1
7=ON/OFF thermal actuator output 2
8=ON/OFF thermal actuator output 3
9=ON/OFF thermal actuator output 4
10=ON/OFF valve
11=Local pump
12=Column pump
13=Dew point or condensation alarm
(Note3)
14=Control request
(Note3)
15=Season changeover
(Note3)
16=Not used
M17
16
0
16
R or
R/W
Note3)
7470
DIGITAL_OUTPUT4_FUNC
(see table pag.
36
) (not for models FH-2xxSH1)
0=Speed 1 of the ON/OFF fan
2=Speed 2 of the ON/OFF fan
2=Speed 3 of the ON/OFF fan
3=ON/OFF fan 1
4=ON/OFF fan 2
'HKXPLGL¿HU
6=ON/OFF thermal actuator output 1
7=ON/OFF thermal actuator output 2
8=ON/OFF thermal actuator output 3
9=ON/OFF thermal actuator output 4
10=ON/OFF valve
11=Local pump
12=Column pump
13=Dew point or condensation alarm
(Note3)
14=Control request
(Note3)
15=Season changeover
(Note3)
16=Not used
M18
16
0
16
R