Registers
Description
Min
Max.
R/W
8031
DAY_NAME
o
name of current day
0=Sunday
1=Monday
2=Tuesday
3=Wednesday
4=Thursday
5=Friday
6=Saturday
0
6
R
8032
HOUR
o
current hour
0
23
R
8033
MIN
o
current time
0
59
R
8034
SEC
o
current time
0
59
R
8035
TOTAL_HOUR_OF_FAN_1
o
total hours of fan 1 operation
0
9999
R
8036
TOTAL_HOUR_OF_FAN_2
o
total hours of fan 2 operation
0
9999
R
8037
FLAG_GLOBAL_ON_OFF
o
general ON/OFF status
0=Appliance off from external contact
1=Appliance off manually
2=Appliance off from Modbus
3=Appliance on from external contact
4=Appliance on manually
5=Appliance on from Modbus
0
5
R
8038
FLAG_LOCAL_ZONE1_ON_OFF
o
zone 1 local ON/OFF status
0=zone 1 off
1=zone 1 on
0
1
R
8039
FLAG_LOCAL_ZONE2_ON_OFF
o
zone 2 local ON/OFF status
0=zone 2 off
1=zone 2 on
0
1
R
8040
FLAG_LOCAL_ZONE3_ON_OFF
o
zone 3 local ON/OFF status
0=zone 3 off
1=zone 3 on
0
1
R
8041
FLAG_LOCAL_ZONE4_ON_OFF
o
zone 4 local ON/OFF status
0=zone 4 off
1=zone 4 on
0
1
R
8042
FLAG_CURRENT_MODE_REG_Z1
o
zone 1 control status
0=Control without taking into account the time slots
1=Normal control (within time slots if
I78
=0)
2=Normal control forced manually (“Oc” for the
I77
timer duration)
3=Economy control
4=Non-occupied holiday mode control
0
4
R
8043
FLAG_CURRENT_MODE_REG_Z2
o
zone 2 control status
0=Control without taking into account the time slots
1=Normal control (within a time slots interval if
I78
=0)
2=Normal control forced manually (“Oc” for the
I77
timer duration)
3=Economy control
4=Non-occupied holiday mode control
0
4
R
8044
FLAG_CURRENT_MODE_REG_Z3
o
zone 3 control status
0=Control without taking into account the time slots
1=Normal control (within a time slots interval if
I78
=0)
2=Normal control forced manually (“Oc” for the
I77
timer duration)
3=Economy control
4=Non-occupied holiday mode control
0
4
R
8045
FLAG_CURRENT_MODE_REG_Z4
o
zone 4 control status
0=Control without taking into account the time slots
1=Normal control (within a time slots interval if
I78
=0)
2=Normal control forced manually (“Oc” for the
I77
timer duration)
3=Economy control
4=Non-occupied holiday mode control
0
4
R
8046
FLAG_STA_WORKING
o
operating season status
0=Heating
1=Cooling
0
1
R
8047
FLAG_CURRENT_SPEED
o
3-speed on/off fan or EC status
0=Fan coil off
1=Fan coil at speed 1 for ON/OFF 3-speed fan coil
2=Fan coil at speed 2 for ON/OFF 3-speed fan coil
3=Fan coil at speed 3 for ON/OFF 3-speed fan coil
xx=PWM value applied to the EC fan coil
0
3
R
8048
FLAG_FAN_ON_OFF_1
o
single-speed on/off fan 1 status
0=Fan coil 1 off
1=Fan coil 1 on
0
1
R
8049
FLAG_FAN_ON_OFF_2
o
single-speed on/off fan 2 status
0=Fan coil 2 off
1=Fan coil 2 on
0
1
R