Parameter
Description
Default
Min
Max.
I76
Summertime change
Determines whether summertime is used automatically
0=No automatic update of summertime change
1=Automatic summertime change in Europe
2=Automatic summertime change in the USA
1
0
2
I77
Duration of extension timer (minutes).
With timer extension function activated
• If
I78
=0, the operating setpoint is the base setpoint, economy and holiday
PRGHVDUHH[FOXGHGIRUWKHGXUDWLRQGH¿QHGE\SDUDPHWHU
I77,
• If
I78
WKHDSSOLDQFHUHPDLQVVZLWFKHGRQIRUGXUDWLRQGH¿QHGE\SDUDPHWHU
I77
regardless of the timer slot.
60
1
480
I78
Timer slots function
0=Timer slots for normal/economy operation
1=Timer slots to switch on/off the appliance
0
0
1
I79
Modbus baud rate (1=2400, 2=4800, 3=9600, 4=19200, 5=38400 bit/s)
(for
FH-xMxSH1
models only)
4
1
5
I80
Modbus parity (0=none, 1=odd, 2=even)
(for
FH-xMxSH1
models only)
2
0
2
I81
Appliance address in Modbus (1...247)
(for
FH-xMxSH1
models only)
1
1
247
I82
Reset fan coil 1 and/or 2 working hours counter
(Note1)
The operating hours of the fans are stored.
When they exceed
I71
, the icon
is displayed.
To erase the fan 1 counter, put
I82
=1. The parameter
I82
automatically returns to 0
after reset.
To erase the fan 2 counter, put
I82
=2. The parameter
I82
automatically returns to 0
after reset.
To erase the fan 1 and 2 counters, put
I82
=3. The parameter
I82
automatically
returns to 0 after reset.
0
0
3
I83
COMFORT function
&XUUHQWVHWSRLQWPRGL¿DEOHYLDTXLFNDFFHVV
6HWSRLQWRIIVHWPRGL¿DEOHYLDTXLFNDFFHVV
See paragraph
³6HWSRLQWDQGVHWSRLQWRIIVHWFRQ¿JXUDWLRQ´SDJH
21
for further
information
0
0
1
I84
Setpoint offset range applied in the comfort function (K) (°C [°F]).
'H¿QHVKRZPXFKWKHVHWSRLQWFDQEHYDULHGLQWKHFRPIRUWIXQFWLRQ
3.0[5]
0[0]
10[18]
I85
Maximum number of SLAVE controllers with Modbus (parameter considered only by
the MASTER controller)
31
1
31
I86
Scale lower end for 0...10 V input
0
-50
I87
I87
Scale upper end for 0...10 V input
100
I86
9999
I88
Unit of measurement on display B for 0...10 V input
0=ppm
1=% R.H.
2=No unit
1
0
2
I89
AI3
0...10 V input correction
0
-98.0
98.0
I90
ON/OFF source sent by the MASTER controller (parameter considered only by the
MASTER controller).
Allows the MASTER controller to send the on/off source to be considered to the
SLAVE_X controllers.
0=No on/off sent
1=On/off from contact sent
2=Manual on/off sent
3=Manual on/off and from contact sent
4=On/off from timer slot sent
5=On/off from timer slot and on/off from contact sent
6=Manual on/off and from timer slot sent
7=Manual on/off, from timer slot and from contact sent
7
0
7
I91
Activation of the thermal actuator 1 operation
0=Actuator disabled
1=Actuator enabled only during summer season
2=Actuator enabled only during winter season
3=Actuator enabled in all seasons
3
0
3
I92
Activation of the thermal actuator 2 operation
0=Actuator disabled
1=Actuator enabled only during the summer season
2=Actuator enabled only during winter season
3=Actuator enabled in all seasons
3
0
3