19/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – [email protected] – www.industrietechnik.it
6.
&RQ¿JXUDWLRQRITXLFNDFFHVVSDUDPHWHUV
The controller provides the following functions with a simple press of a button:
•
Switch on and off
•
&RQ¿JXUDWLRQRIWKHVHWSRLQWRUVHWSRLQWRIIVHW
•
Fan operating mode
•
MODE
button functionality
The
MODE
button can be assigned one quick access function and other normal access functions, depending on parameter
I74
(see
³02'(EXWWRQIXQFWLRQ´SDJH
22
)
I74
=0: season change (if it is local, for 2-pipe systems)
I74
=1: zone 1 timer extension
I74
=2: zone 2 timer extension
I74
=3: zone 3 timer extension
I74
=4: zone 4 timer extension
I74
=5: operating mode (without clock, using time slots, holiday)
• Keypad lock
To lock the keypad, press buttons
ESC
M
O
D
E
at the same time; the display shows
LK
for one second.
When any button is pressed, it is no longer possible to access the parameters and the display shows
LK
.
To unlock the keypad, press the buttons
ESC
M
O
D
E
again; the display shows
NLK
for one second.
• Switch on and off
Distinction can be made between two types of switch on/off commands:
- global command
- local command for one zone
The global command switches off all equipment and may be performed in 3 ways:
- manually using the
button,
- from an external contact,
- from the Modbus (solely for the SLAVE controller with Modbus)
The local command switches off only one zone and may be performed in two ways:
- manually by accessing parameters
OC1
for zone 1,
OC2
for zone 2,
OC3
for zone 3,
OC4
for zone 4
- automatically from the clock, programming the time slots of the 4 zones (if
I78
=1)
Global commands:
Switching on/off from an external contact has maximum priority. If the external contact is in OFF position, the equip-
ment cannot be manually restarted or by Modbus or by time slots.
7RXVHWKHH[WHUQDOFRQWDFWDVDZD\RIVZLWFKLQJRQRURIIWKHDSSOLDQFHFRQ¿JXUHDGLJLWDOLQSXWDV³5HPRWH2Q2II´
(
M04
=1 or
M06
=1).
Example for digital input 1 (
M04
=1):
Unit
ON=
(
M05
=0)
Unit
OFF=
(
M05
=0)
Unit
ON=
(
M05
=1)
Unit
OFF=
(
M05
=1).
,IWKHH[WHUQDOFRQWDFWLVRQ21SRVLWLRQRULWLVQRWFRQ¿JXUHGZLWK³5HPRWH2Q2II´IXQFWLRQDOLW\DSSOLDQFHFDQEH
switched on or off by pressing button
(until
ON
or
OFF
is displayed) or through Modbus (through the
ON_OFF_VIA_
MODBUS
register (see
³0RG[0[6+PRGHOV´SDJH
103
).
The manual global switch on/off has the same priority as the one through Modbus. This means that if the appliance is
globally off in manual mode, it can be restarted through Modbus or viceversa.