Registers
Description
Default
Min
Max.
R/W
7460
ANALOG_INPUT1_FUNC
(see table pag.
36
)
0=Remote control sensor for zone 1
1=Remote control sensor for zone 2
2=Remote control sensor for zone 3
3=Remote control sensor for zone 4
4=External sensor
5=Floor sensor for zone 1
6=Floor sensor for zone 2
7=Floor sensor for zone 3
8=Floor sensor for zone 4
9=Season changeover remote contact (INPUT ON=Winter, INPUT
OFF=Summer)
10=On/Off remote contact (INPUT ON=OFF, INPUT OFF=ON)
11=Non-occupied holiday remote contact (INPUT ON=Occupied)
12=Economy remote contact (INPUT ON=Economy on)
13=Sensor for dew point calculation (only for MASTER or SLAVE_Y controller)
14=Limit sensor (used by the MASTER or SLAVE_Y controller)
15=Not used
M08
15
0
15
R/W
7461
ANALOG_INPUT1_LOG
(see table pag.
36
):
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
M09
0
0
1
R/W
7462
ANALOG_INPUT2_FUNC
(see table pag.
36
)
0=Remote control sensor for zone 1
1=Remote control sensor for zone 2
2=Remote control sensor for zone 3
3=Remote control sensor for zone 4
4=External sensor
5=Floor sensor for zone 1
6=Floor sensor for zone 2
7=Floor sensor for zone 3
8=Floor sensor for zone 4
9=Season changeover remote contact (INPUT ON=Winter, INPUT
OFF=Summer)
10=On/Off remote contact (INPUT ON=OFF, INPUT OFF=ON)
11=Non-occupied holiday remote contact (INPUT ON=Occupied)
12=Economy remote contact (INPUT ON=Economy on)
13=Sensor for dew point calculation (only for MASTER or SLAVE_Y controller)
14=Limit sensor (used by the MASTER or SLAVE_Y controller)
15=Not used
M10
15
0
15
R/W
7463
ANALOG_INPUT2_LOG
(see table pag.
36
) :
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
M11
0
0
1
R/W
7464
ANALOG_INPUT3_FUNC
(see table pag.
36
)
0=Remote control sensor for zone 1
1=Remote control sensor for zone 2
2=Remote control sensor for zone 3
3=Remote control sensor for zone 4
4=External sensor
5=Floor sensor for zone 1
6=Floor sensor for zone 2
7=Floor sensor for zone 3
8=Floor sensor for zone 4
9=Season changeover remote contact (INPUT ON=Winter, INPUT
OFF=Summer)
10=On/Off remote contact (INPUT ON=OFF, INPUT OFF=ON)
11=Non-occupied holiday remote contact (INPUT ON=Occupied)
12=Economy remote contact (INPUT ON=Economy on)
13=Sensor for dew point calculation (only for MASTER or SLAVE_Y controller)
14=Limit sensor (used by the MASTER or SLAVE_Y controller)
15=Not used
16 = 0....10 V input for humidity sensor
M12
15
0
16
R/W
7465
ANALOG_INPUT3_LOG
(see table pag.
36
)
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
M13
0
0
1
R/W
7466
CONF_OUTPUTS
(see table pag.
36
)
1RFRQ¿JXUDWLRQ
WR &RQ¿JXUDWLRQIRU0$67(5FRQWUROOHURU6/$9(B<FRQWUROOHU
WR &RQ¿JXUDWLRQIRU6/$9(B;FRQWUROOHU
M14
0
0
23
R/W