Manual de Instalação e Operação
Display will be showing: 12
7
Press
<
↑
>
until the value of the first place is equal to 0;
Display will be showing: 13
0
Press
<
←
>
to advance one place
Display will be showing: 1
3
0;
Press
<
↑
>
until the value of the second place be equal to 0;
Display will be showing: 2
0
0
Press
<
←
>
to advance one place
Display will be showing:
2
00;
Press
<
↑
>
until the value of the third place is equal to 8;
Display will be showing:
8
00
Press
<
←
>
to advance one place
Display will be showing:
_
800;
Press
<
↑
>
until the value of the forth place is equal to 3;
Display will be showing:
3
800;
Press
<
←
>
to advance one place
Display will be showing:
_
3800;
Press
<
↑
>
until the value of the fifth place is equal to 1;
Display will be showing:
1
3800;
Press
<F1>
to confirm the new value;
9. PROGRAMMING MENU
In this mode it is programmed the equipment operation parameters.
The programming form of all the items is as described in the item 8.3, except specified.
In this mode, if no key is pressed the equipment returns to the supervisor mode after 20
seconds.
The programming can be made directly pressing F0 and F1 and selecting the smaller
that you wish to change, or sequentially as follows.
The key "
F4
" returns to the supervisor mode.
9.1. PT/CT, CONNECTION TYPE AND Nº OF ELEMENTS
Press F0 and following F1:
Press
F1
again to come into the screen below, to setup the items described as follows.
TN
(Prog. PT/CT, Ligação = Connection , Confirmar = Confirm, Sair = Out)
These parameters show the voltage transformation relation. Value, max. 500kV and
min.50V.
TN
SMART CAP 485
47