9.6. PROGRAMMING OF PARAMETER OF BANKS CONTROL
Go to the below screen using the key F1 and the arrows.
Press F1 to confirm.
TN
(Param Controle =
Control Parameter)
INPUT TIME OF CAPACITORS BANK
TN
Entrada = Input
The next screen setups input time of capacitors bank. This time is a delay in capacitors
bank activation when the value of the measured power factor is below the programmed
minimum value. It can be setup between 1 and 1200 seconds.
Press the arrows to adjust the input time value and press F1 to confirm the alteration.
OUTPUT TIME OF CAPACITORS BANK
TN
Saida = Out
Output time is a delay in capacitors bank disconnection when the measured value of the
power factor is above of programmed maximum value. It can be setup between 1 and 1200
seconds.
Press the arrows to adjust the input time value and press F1 to confirm the alteration.
The times of output and input of capacitors bank are useful parameters for the protection
and extending of the useful life of capacitors bank. These parameters affect only capacitors
banks activation when
Smart Cap 485
is working on Automatic Mode.
MINIMUM REACTIVE POWER (KVAR IMIN):
The minimum reactive power (kVAr Imin) is a setup parameter that specifies which is the
reactive power that is going to be activated when the net current is very low (below the setup
minimum current value).