After 24 hours from the last activation, independently from the functioning status of the 

boiler (Summer or Winter), the pump (M1) is started for a time of 30 seconds and the 

three-way valve (M30) is started for a period of 10 seconds.

Three-way valve/anti-

block pump

P.C.B. safety functions

If the contact of the water overheating thermostat is opened (temperature of the primary 

circuit exceeding 100 °C), boiler functioning is blocked.

The main selector switch (S2) must be turned to the Reset position in order to restore 

functioning of the appliance.

Thermostat safety

block

If a fan speed is detected that is out of safe limits (700-5700 rpm) the burner is switched 

off and it cannot be re-ignited for 7.5 minutes.

The main selector switch (S2) must be turned to the Reset position in order to restore 

functioning of the appliance.

Fan speed anomaly

In the case of dispersion of the detection circuit or anomaly in the flame control that ge-

nerates a correct ionisation current (without the gas valve being open) with the duration of 

at least 20 seconds, boiler functioning is blocked.

The main selector switch (S2) must be turned to the Reset position in order to restore 

functioning of the appliance.

Parasite flame block

If within 10 seconds from the start of the ignition cycle, the detection electrode (E2) has not 

detected flame presence on the burner, boiler functioning is blocked.

The integrated P.C.B. makes 2 ignition attempts with duration of 10 seconds, intervalled by 

a time of 30 seconds, after which it blocks.

The main selector switch (S2) must be turned to the Reset position in order to restore fun-

ctioning of the appliance.

N.B.:

 It is possible to reset the anomaly up to 5 consecutive times, after which the function is 

prevented for at least one hour and one attempt is gained after every hour. Five attempts can 

be gained by pressing the   Stand-by key or by removing the power supply to the circuit.

No ignition 

block

If the contact of the flue overheating thermostat is opened (temperature of the external part 

of the condensation module exceeding 110 °C) owing to the combustion impurities deposited 

on the heat exchanger (soot, oxidations, etc...), boiler functioning is blocked.

The main selector switch (S2) must be turned to the Reset position in order to restore 

functioning of the appliance.

Flue safety thermostat 

block

To prevent overheating of the water-gas heat exchanger, at the end of CH (room thermostat 

opening), anti-freeze or "chimney sweep" request, the boiler pump (M1) is kept working 

for a period of 60 seconds.

Boiler pump post-circu-

lation

The combustion chamber is washed after switch-off of the burner at the end of any request 

and the fan works for 55 seconds.

Sealed chamber post-

ventilation

To prevent overheating of the water-gas heat exchanger if the pump is blocked or due to 

little circulation in the primary circuit, when the CH NTC flow probe (B1) detects an 

increase in the temperature exceeding 5 °C per second (for more than 2 consecutive seconds), 

the burner is switched off.

Re-start takes place when the flow temperature falls below 43°C.

Insufficient circulation

If the NTC flow probe (B1) detects a temperature higher than 100 °C, (with boiler in stand-

by), the successive burner ignition request is delayed by 20 seconds and only the pump is 

activated. If the successive request takes place with the flow temperature below 70°C the 

burner ignition delay is annulled.

Dynamic hysteresis 

function

Содержание VICTRIX Zeus 26 1 I

Страница 1: ...VICTRIX Zeus 26 1 I Condensation type wall hung room sealed fan assisted boiler with stainless steel storage tank VICTRIX Zeus 26 1 I...

Страница 2: ......

Страница 3: ...he regulation and control are entrusted to a P C B with inte grated microprocessor with continuous flame modulation via 2 sensors DHW and CH which through a backlit display shows the functioning state...

Страница 4: ...al connection G Gas supply SC Condensate drain minimum internal diameter 13 mm R System return M System flow RC Domestic hot water pump optional AC Domestic hot water outlet AF Domestic hot water inle...

Страница 5: ...cal Documentation VICTRIX Zeus 1I control panel Key 1 Boiler status signal display 2 Stand by Domestic water Remote Control Domestic water and Heating Reset Selector 3 Domestic hot water temperature s...

Страница 6: ...2 Detection electrode 13 Condensation module 14 Flue safety thermostat 15 Air intake pipe 16 Sample points air A flue gas F 17 Negative signal pressure point 18 Burner 19 Positive signal pressure poin...

Страница 7: ...pe 13 Condensation module 14 Manual air vent valve 15 Flue hood 16 Air sample point 17 p gas pressure point 18 Flue sample point 19 Delivery probe 20 Safety thermostat 21 Burner 22 Ignition electrodes...

Страница 8: ...ition of the motorised 3 way valve A Head available to the plant at third speed with by pass excluded B Head available to the plant at third speed with by pass inserted C Head available to the plant a...

Страница 9: ...while the fourth is arranged in the condensation chamber which is separated from the combustion chamber by sheet steel see flue circuit PTo reduce head losses to a minimum and increase the flow rate a...

Страница 10: ...ion thanks to a motor 1 that causes movement according to necessity Operation When it is necessary to reach the CH or DHW position the motor 1 is activated by the P C B Functioning of the motor leads...

Страница 11: ...the flow manifold unit 1 and is coupled to a micro switch that prevents functioning of the burner when the pressure detected is below 0 3 bar Prevents overheating of the main heat exchanger Automatic...

Страница 12: ...Replacement of the automatic air vent valve To replace the air vent valve the relative locking clip must be removed and the valve extracted 9 paying attention not to damage the relative O ring N B wh...

Страница 13: ...at loss Operation Following a DHW request the P C B starts the boiler pump 7 and powers the electric 3 way valve motor 8 The consequent shifting of the valve into the DHW position see electric 3 way v...

Страница 14: ...tional Allows to connect the pipes of any DHW pump system It consists in a pipe that is inserted in the boiler after the anode and relative cap have been removed With the installation of the kit the a...

Страница 15: ...ent air The mixture obtained in this way is ignited on the surface of the cylindrical burner 8 by the discharge of the ignition electrodes 9 Gas valve The gas valve is equipped with two main coils con...

Страница 16: ...to mix it with the air The nozzle 2 has a different diameter depending on whether natural gas or LPG is used as working with both gases with more or less constant pressure its section establishes the...

Страница 17: ...w otherwise no discharge is obtained Detection electrode 9 It is controlled by the integrated P C B and detected burner ignition It also acts as a flue safety device when any air intake problems or pr...

Страница 18: ...the system flow and return pipes and of the condensate discharge pipe positioned in the lower part of the module Loosen the two screws 7 and 9 that fix the condensation module to the support back usin...

Страница 19: ...urner enter the calibration function by positioning the DHW regu lation selector switch on notch N 6 and the CH regulation selector switch on notch N 9 turn the main selector switch to the Reset posit...

Страница 20: ...ation max DHW min DHW CH and max CH always turn the main selector switch to the Reset position for at least 2 seconds The boiler will go into chimney sweep mode and at this point it is possible to ver...

Страница 21: ...present on the control panel to minimum and check the correspondence of the carbon dioxide CO2 value measured with that indicated in the table for the minimum output see table at the side if the value...

Страница 22: ...he sealed combustion chamber 6 which has a sheet steel section on its base 7 that divides it from the condensation chamber 2 and diverts the flow of flue gases to the outside of the module In this way...

Страница 23: ...ler The GREEN SERIES flue kit is made in plastic PPS self extinguishing polypropylene suitable for resisting the corrosive action of the acid condensate Configuration with sealed chamber and fan as si...

Страница 24: ...or 80 flexible For that regarding the head losses relative to each accessory for the various combinations that can be performed see the instructions relative to the intake and exhaust terminals see b...

Страница 25: ...chimneys technical slots to be used exclusively with a unique Immergas condensing appliance Fit a 90 bend 5 to the appliance exhaust pipe which using the necessary vertical extensions 2 must be conne...

Страница 26: ...the boiler flue evacuation pipe Using a divided kit 80 80 1 bend 1 m in intake and exhaust with intake grid the maximum length allowed is 30 straight vertical metres System for ducting 80 flexible It...

Страница 27: ...at E6 Flue safety thermostat F1 Phase fuse F2 Transformer fuse G2 Igniter M1 Boiler pump M20 Fan M30 Three way valve S2 Selector switch functioning S5 System pressure switch S7 Central heating timer s...

Страница 28: ...he speed With the consent of the safety thermostat E4 and the flue safety thermostat E6 and the fan M20 reaching the vali date ignition speed the integrated P C B allows to start the ignition cycle by...

Страница 29: ...only if the temperature drops to 75 C Central heating anti freeze request When the temperature detected by the CH flow probe B1 falls below 4 C the board gives consent for ignition and keeps the gener...

Страница 30: ...etection electrode E2 Inputs The board power supply is connected to the L and N clamps of the X1 connector 230 V AC 10 15 50 Hz 5 230 V 50 Hz Detects the ignition of the burner by which the flame is h...

Страница 31: ...probe B4 optional PTC probe 1 k 25 C When the pressure of the boiler circuit is below 0 3 bar it determines burner switch off System pressure switch S5 Open No pressure Closed Pressure OK It enables...

Страница 32: ...X40 jumper must be eli minated Comando Amico Remoto remote control CAR optional See Comando Amico Remoto remote control functioning CAR Allows the control of 1 additional zone valve by means of CAR wh...

Страница 33: ...et position in order to restore fun ctioning of the appliance N B It is possible to reset the anomaly up to 5 consecutive times after which the function is prevented for at least one hour and one atte...

Страница 34: ...elative anomaly and prevents functioning in DHW mode but functioning in CH mode is allowed Breakage of the NTC DHW probe B2 The breakage of the central heating flow probe B1 is signalled by the relati...

Страница 35: ...mbol Numerical characters to indicate temperatu re any error code or optional external probe temperature correlation factor Degrees symbol External probe connection symbol Connection to Comando Amico...

Страница 36: ...NTC flow probe anomaly 05 E05 Reset selector switch fault 08 E08 Calibration function active displayed only on CAR E09 No circulation 10 E10 Storage tank probe anomaly 12 E12 Configuration error 15 E1...

Страница 37: ...2580 Efficiency 80 60 Nom Min 96 9 93 2 Efficiency 50 30 Nom Min 105 3 106 8 Efficiency 40 30 Nom Min 107 5 108 8 Heat loss at casing with burner On Off 80 60 C 0 58 0 90 Heat loss at flue with burne...

Страница 38: ...16 0 13760 1 75 2 32 23 7 1 30 2 33 23 7 1 28 3 09 31 5 15 0 12900 1 64 2 07 21 1 1 22 2 07 21 1 1 20 2 75 28 1 14 0 12040 1 53 1 83 18 7 1 14 1 83 18 6 1 13 2 44 24 9 13 0 11180 1 43 1 61 16 4 1 06...

Страница 39: ...rmostat cod 3 014438 Radio timer thermostat wireless cod 3 014439 Zones control unit kit cod 3 011668 Relay interface kit for zone valve coupling cod 3 017331 GSM telephone control kit cod 3 017182 DH...

Страница 40: ...e boiler to start a new ignition cycle Ignition cycle CENTRAL HEATING MODE Main selector switch in winter position Turn the heating selector to a maximum and interrupt and DHW re quests The pump start...

Страница 41: ...ains the set tem perature No Check the maximum DHW heating ou tput and adjust it to maximum See section D Yes The domestic hot water request is satisfied Yes The burner stays on after the first 10 sec...

Страница 42: ...the valve make sure that there is enough gas inlet dynamic pressure and that the gas valve is correctly calibrated 01 c The electrode detects a direct current of 6 8 A during the burner ignition phase...

Страница 43: ...ream from the boiler Error 02 intervenes also if the board detects a loss of the flame signal 6 times in 8 5 minutes ERROR 05 NTC flow probe anomaly The wiring between the flow probe and the board con...

Страница 44: ...OK Check continuity of the cable on clamp 4 of connector X12 No Restore the electric connection replace the wiring Yes Replace the fan If the anomaly persists replace the P C B ERROR 20 Parasite flam...

Страница 45: ...ly connection wires and relative external fuses are integral No Restore the electric connection replace the cables external fuses Yes Replace the P C B ERROR 38 Loss of flame signal It is displayed ev...

Страница 46: ...ING MODE 230 VDC are present to the clamps 1 3 of connector X5 on the P C B DOMESTIC HOT WATER MODE 230 VDC are present to the clamps 1 2 of connector X5 on the P C B No Replace the P C B Yes The wiri...

Отзывы: