3.13 SOLAR PANELS COUPLING 

FUNCTION.

In the event of integration of DHW heating with 

solar panel systems, the boiler is set by default 

for management of the storage tank unit via 

parameter “t2” set on “2 or 3”.

3.14 ''CHIMNEY SWEEP'' FUNCTION.

When activated, this function forces the boiler 

to variable output for 15 minutes.

In this state all adjustments are excluded and 

only the safety thermostat and the limit ther-

mostat remain active. To activate the chimney 

sweep function, press the “Reset” button (2) 

until activation of the function in the absence 

of DHW requests.
Its activation on the boiler display is confirmed 

by the indicators flashing at the same time (11 

and 12 Fig. 2-1), while on the CAR

V2

 (optional) 

it is indicated as “ERR>07”.
This function allows the technician to check the 

combustion parameters. 

Once the function is activated, it is possible to 

select whether to make the check in CH status 

or DHW status 

(when the boiler is connected to 

an external storage tank unit)

 by opening any hot 

water cock and regulating the power by turning 

the "CH regulation" selector (6).

The central heating or DHW operating mode is 
displayed by the relative symbols 

 or 

.

After the checks, deactivate the function switch-

ing the boiler off and then on again.

Attention:

 the boiler needs a certain amount of 

time to stabilise itself before carrying out a com-

bustion parameters check. It is thus necessary to 

wait for the boiler to carry out a self-diagnosis 

test, which is signalled by the (

)  flashing 

symbol. Once the symbol stops flashing, it is 

possible to check the combustion parameters.

3.15 PUMP ANTI-BLOCK FUNCTION.

The boiler has a function that starts the pump at 

least once every 24 hours for the duration of 30 

seconds in order to reduce the risk of the pump 

becoming blocked due to prolonged inactivity.

3.16 THREE-WAY ANTI-BLOCK 

FUNCTION.

Both in “domestic hot water” and in “domestic 

hot water-central heating” phase the boiler is 

equipped with a function that starts the three-

way motorised group 24 hours after it was last 

in operation, running it for a full cycle so as to 

reduce the risk of the three-way group becoming 

blocked due to prolonged inactivity.

3.17  RADIATORS ANTI-FREEZE 

FUNCTION.

If the system return water is below 4°C, the boiler 

starts up until reaching 42°C.

3.18 P.C.B. PERIODIC SELF-CHECK.

During functioning in central heating mode or 

with boiler in standby, the function activates 

every 18 hours after the last boiler check/power 

supply. In case of functioning in domestic hot wa-

Id 

Parameter

Parameter

Description

Range

Default

Customised 

value

F0

Equivalent length 

flue

Defines the length of the flue (see par. 3.12)

0 - 2

0

F1

-

Not used on this boiler model

-

-

In the event of an alteration, anomaly “E72” appears and fast calibration is required.

ter mode the self-check starts within 10 minutes 

after the end of the withdrawing in progress, for 

duration of approx. 10 seconds.

N.B.:

 during self-check, the boiler remains off.

3.19 AUTOMATIC VENT FUNCTION.

In the case of new central heating systems and 

in particular mode for floor systems, it is very 

important that dearation is performed correctly. 

The function consists of the cyclic activation of 

the pump (100 s ON, 20 s OFF) and the 3-way 

valve (120 s D.H.W., 120 s C.H.). 

The function is activated in two different ways:
- at each new boiler power supply, based on the 

setting of parameter “A7”;

- by pressing the buttons at the same time (3 

and 5 Fig. 2-1) for 5 seconds with the boiler in 

stand-by.

  

IMPORTANT NOTE:

 if the boiler is con-

nected to the CAR

V2

 the “stand-by” function 

can only be activated via the remote control 

panel.

In the first case, the function has duration of 8 

minutes and it can be interrupted by pressing 

the “reset” button (2). In the second case it has 

duration of 18 hours and it can be interrupted by 

simply switching the boiler on.
Activation of the function is signalled by the 

countdown shown on the indicator (14).

Id 

Parameter

Parameter

Description

Range

Default

Customised 

value

A0

Hydraulic model Defines the type of hydraulics in the boiler

Set

2

2

A1

-

Not used on this boiler model

-

-

A2

Model 

Pump

Defines the type of circulator in the boiler

Set

3

3

A3

Maximum pump 

speed

Sets the maximum pump operating speed

1 ÷ 9

9

A4

Minimum pump 

speed

Sets the minimum pump operating speed

1 ÷ A3

5

A5

Pump operating 

mode

Sets the pump operating mode

- DELTA T = 0:proportional head (see par. 1.26)
- DELTA T = 5 

÷

 25 K: constant ∆T (see par. 1.26) 

0 ÷ 25

15

A7

Ignition phase 

automatic vent

Sets the activation mode of the automatic vent at each new electric powering 

phase of the boiler.

This function lasts 8 minutes, and is displayed via a countdown signalled by the 

special indicator (Ref. 14 Fig. 2-1). During this period the DHW and CH func-

tions are not active. The “automatic vent” function can be annulled by pressing 

the “reset” button.

1:  the automatic vent is enabled at each new electric power supply.
0:  the automatic vent is enabled only at the first electric power supply after 

having set the parameter to “0”; once the function has ended, or is inter-

rupted by pressing the “reset” button, it will not be enabled again unless 

the parameter is set to “1”.

0 - 1

1

STD.002549/004

Содержание VICTRIX MAIOR 35 X TT 1 ERP

Страница 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG STD 002549 004...

Страница 2: ...STD 002549 004...

Страница 3: ...ified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits establis...

Страница 4: ...ce 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 Syst...

Страница 5: ...removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safet...

Страница 6: ...kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Attention the excessive use of glycol could jeopardise the proper functioni...

Страница 7: ...ipes radiators etc with special pickling or descaling products to remove any deposits that could compromise correct boiler operation A treatment of the heating and water system water is required in co...

Страница 8: ...stats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two r...

Страница 9: ...ystem flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperature The exte...

Страница 10: ...owed cor responds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting...

Страница 11: ...nd Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pip...

Страница 12: ...the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Insta...

Страница 13: ...cular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of...

Страница 14: ...up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where ve...

Страница 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Страница 16: ...a The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a square s...

Страница 17: ...uildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with Type B open chamber boilers must not be installed in places where commerci...

Страница 18: ...ated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of use of w...

Страница 19: ...valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit i...

Страница 20: ...7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Return pr...

Страница 21: ...prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heati...

Страница 22: ...external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the system is sufficient to heat the radiators the b...

Страница 23: ...er flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler restar...

Страница 24: ...e has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Combustio...

Страница 25: ...ntly filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing Never...

Страница 26: ...eck that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices checktheproductionofDHW whentheboiler is connected to an external storage tank unit check seali...

Страница 27: ...or X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory B1 Boil...

Страница 28: ...are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condensation mo...

Страница 29: ...position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the function...

Страница 30: ...is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermedia...

Страница 31: ...E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve control set...

Страница 32: ...neral alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boiler model...

Страница 33: ...On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too ofte...

Страница 34: ...heck power supply Incaseoffunctioningindomestichotwa Id Parameter Parameter Description Range Default Customised value F0 Equivalent length flue Defines the length of the flue see par 3 12 0 2 0 F1 No...

Страница 35: ...integrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct calibr...

Страница 36: ...a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen screws d 6...

Страница 37: ...USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of side faste...

Страница 38: ...URNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94 3 51 2 58 31 5 27090 91 3 40 2 50 30 5 26230 88 3 29 2 42 29 5 25370 85 3 19...

Страница 39: ...80 60 C 0 24 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable heating temperature max oper...

Страница 40: ...l Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn...

Страница 41: ...1 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 004 kW Emissions of nitrogen oxides NOX 24 mg kWh For mixed central heating appliances Stated...

Страница 42: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Страница 43: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 44: ...ution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123...

Страница 45: ...nder colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G...

Страница 46: ...46 STD 002549 004...

Страница 47: ...47 STD 002549 004...

Страница 48: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 004 08 18 Inglese per IRLA...

Отзывы: