Immergas VICTRIX MAIOR 35 X TT 1 ERP Скачать руководство пользователя страница 18

18

1-27

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

Combustion products exhaust of natural 

draught or fan assisted appliances in open-top 

closed environments.

 In spaces closed on all 

sides with open tops (ventilation pits, court-

yards etc.), direct combustion product exhaust 

is allowed for natural draught or fan assisted gas 

appliances with a heat input range from 4 to 35 

kW, provided the conditions as per the current 

technical standards are respected.

1.21  WATER TREATMENT SYSTEM 

FILLING.

As already mentioned in the previous para-

graphs, a treatment of the thermal and domestic 

system water is required, in compliance with the 

local standards in force.
The parameters that influence the duration and 

proper operation of the heat exchanger are the 

water's PH, hardness, conductivity, and oxygen, 

together with the system's processing residues 

(any welding residues), any oil present and cor-

rosion products that can, in turn, cause damage 

to the heat exchanger. 
In order to prevent this from happening, you are 

recommended to:

- Before installation on new systems as well as 

old ones, clean the system with clean water to 

eliminate solid residues contained therein.

- Clean the system with a chemical treatment:
  -  Clean the new system with a suitable cleaning 

device (for example Sentinel X300, Fernox 

Cleaner F3 or Jenaqua 300) combined with 

thorough washing.

  -  Clean the old system with a suitable cleaning 

device (for example Sentinel X400 or X800, 

Fernox Cleaner F3 or Jenaqua 400) combined 

with thorough washing.

- Check the maximum hardness and quantity 

of filling water referring to the graphics (Fig. 

1-27). If the contents and hardness of the water 

are below the indicated curve, no specific treat-

ment is required; otherwise, to limit the content 

of calcium carbonate, you must provide for 

water-filling treatment. 

- For filling, you are not allowed to use water 

softened with the use of ionic-exchange resins 

or distilled water.

- Should you be required to provide for water 

treatment, this should be carried out by 

completely desalinating the filling water. As 

opposed to the complete softening process, 

desalinating the water completely not only 

removes hardening agents (Ca, Mg), but also 

eliminates all other minerals to reduce water-

filling conductivity up to 10 microsiemens/

cm. Given its low conductivity, desalinated 

water does not only prevent the formation of 

lime scale, but also serves as protection against 

corrosion.

- Insert a suitable inhibitor / passivator (for 

example Sentinel X100, Fernot Protector F1, 

or Jenaqua 100); if required, also insert appro-

priate antifreeze (such as for example Sentinel 

X500, Fernox Alphi 11 or Jenaqua 500).

-  Check electrical conduction of the water, which 

should not be higher than 2000 µs/cm in the 

case of treated water and lower than 600 µs/cm 

in the case of non-treated water.

- To prevent corrosion, the water system's PH 

should be between 6.5 and 8.5.

- Check the maximum content of chlorides, 

which should be less than 250 mg/l.

N.B.:

 for quantities and methods of use of water-

treatment products, refer to the instructions 

provided by their manufacturer.

1.22 SYSTEM FILLING.

Once the boiler is connected, proceed with 

system filling via the filling cock (Fig. 1-29 and 

1-3). Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents.

The boiler has a built-in automatic venting valve 

on the circulator. 

Check if the cap is loose.

 Open 

the radiator vent valves.

Close radiator vent valves when only water 

escapes from them.

Close the filling cock when the boiler pressure 

gauge indicates approx. 1.2 bar. 

N.B.:

 during these operations, enable the au-

tomatic vent functions on the boiler (active on 

first ignition). 

1.23 CONDENSATE TRAP FILLING.

On first lighting of the boiler, flue gas may come 

out the condensate drain; after a few minutes’ 

operation check that this no longer occurs. This 

means that the drain trap is filled with conden-

sate to the correct level preventing the passage 

of flue gas.

1.24 GAS SYSTEM START-UP.

To start up the system, refer to the technical 

standard in force.

In particular, for new gas systems:

-  open windows and doors;
-  avoid presence of sparks or open flames;
-  bleed all air from the pipelines;
-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force.

1.25  BOILER START UP (IGNITION).

To commission the boiler (the operations listed 

below must only be performed by a qualified firm 

and without any unauthorised persons):

-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force;

-  ensure that the type of gas used corresponds to 

the boiler settings (the type of gas appears on 

the display on first electrical supply voltage, or 

by checking the relative parameter “G”);

-  check connection to a 230V-50Hz power 

mains, correct L-N polarity and earthing con-

nection;

-  check that there are external factors that may 

cause the formation of fuel pockets; 

-  switch the boiler on and check correct ignition;
- make sure that the gas flow rate and relevant 

pressure values comply with those given in the 

manual (Par. 3.22);

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 

intervention time;

- check the intervention of the main switch 

located upstream from the boiler and in the 

boiler;

-  check that the intake and/or exhaust terminals 

(if fitted) are not blocked.

- Carry out the flue test and set the relative 

parameter "F0".

The boiler must not be started up even if only 

one of the checks should be negative.

N.B.:

 the graph refers to the 

entire life cycle of the system. 

Therefore, also consider sched-

uled and unscheduled mainte-

nance, which involves emptying 

and filling the said system.

Water hardness °F

Sys

tem w

at

er l

itr

es

STD.002549/004

Содержание VICTRIX MAIOR 35 X TT 1 ERP

Страница 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG STD 002549 004...

Страница 2: ...STD 002549 004...

Страница 3: ...ified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits establis...

Страница 4: ...ce 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 Syst...

Страница 5: ...removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safet...

Страница 6: ...kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Attention the excessive use of glycol could jeopardise the proper functioni...

Страница 7: ...ipes radiators etc with special pickling or descaling products to remove any deposits that could compromise correct boiler operation A treatment of the heating and water system water is required in co...

Страница 8: ...stats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two r...

Страница 9: ...ystem flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperature The exte...

Страница 10: ...owed cor responds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting...

Страница 11: ...nd Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pip...

Страница 12: ...the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Insta...

Страница 13: ...cular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of...

Страница 14: ...up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where ve...

Страница 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Страница 16: ...a The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a square s...

Страница 17: ...uildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with Type B open chamber boilers must not be installed in places where commerci...

Страница 18: ...ated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of use of w...

Страница 19: ...valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit i...

Страница 20: ...7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Return pr...

Страница 21: ...prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heati...

Страница 22: ...external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the system is sufficient to heat the radiators the b...

Страница 23: ...er flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler restar...

Страница 24: ...e has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Combustio...

Страница 25: ...ntly filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing Never...

Страница 26: ...eck that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices checktheproductionofDHW whentheboiler is connected to an external storage tank unit check seali...

Страница 27: ...or X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory B1 Boil...

Страница 28: ...are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condensation mo...

Страница 29: ...position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the function...

Страница 30: ...is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermedia...

Страница 31: ...E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve control set...

Страница 32: ...neral alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boiler model...

Страница 33: ...On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too ofte...

Страница 34: ...heck power supply Incaseoffunctioningindomestichotwa Id Parameter Parameter Description Range Default Customised value F0 Equivalent length flue Defines the length of the flue see par 3 12 0 2 0 F1 No...

Страница 35: ...integrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct calibr...

Страница 36: ...a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen screws d 6...

Страница 37: ...USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of side faste...

Страница 38: ...URNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94 3 51 2 58 31 5 27090 91 3 40 2 50 30 5 26230 88 3 29 2 42 29 5 25370 85 3 19...

Страница 39: ...80 60 C 0 24 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable heating temperature max oper...

Страница 40: ...l Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn...

Страница 41: ...1 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 004 kW Emissions of nitrogen oxides NOX 24 mg kWh For mixed central heating appliances Stated...

Страница 42: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Страница 43: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 44: ...ution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123...

Страница 45: ...nder colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G...

Страница 46: ...46 STD 002549 004...

Страница 47: ...47 STD 002549 004...

Страница 48: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 004 08 18 Inglese per IRLA...

Отзывы: