2.4  USING THE BOILER.

Attention:

the Victrix Maior 35 X TT 1 ErP boiler was de-

signed to operate as an appliance for room central 

heating only or, coupled to a specific optional 

kit, for central heating and DHW production. 

For this reason the boiler control panel has a 

knob to adjust the temperature of DHW, but its 

operation is only activated by the optional kits 

that also enable the production of DHW. Without 

coupling to these specific kits, the functioning of 

this knob and all functions referring to DHW are 

inhibited, apart from the calibration phase and 

scrolling the P.C.B. programming menu.
Before ignition make sure the heating system 

is filled with water and that the manometer (7) 

indicates a pressure of 1 ÷ 1.2 bar.

- Open the gas cock upstream from the boiler.
- Press the button (6) until the display switches 

on. The boiler now returns to the state prior to 

switch-off.

-  If the boiler is in stand-by, press the button (6) 

again to activate it. If this is not the case, go to 

the next point.

- Then press the button (3) in sequence and set 

the boiler in the summer (

) or winter (

position.

• 

Summer 

(

)

:

 in this mode the boiler only 

works to produce DHW 

(when the boiler is 

connected to the external storage tank unit)

; the 

temperature is set via the selector (1) and the 

relative temperature is shown on the display 

via the indicator (14).

• Winter 

( )

:

 in this mode, the boiler works to 

produce DHW 

(when the boiler is connected to 

the external storage tank unit)

 as well as central 

heating. The temperature of the DHW is always 

regulated via the selector (1), the heating tem-

perature is regulated via selector (4) and the 

relative temperature is shown on the display 

via the indicator (14).

From this moment the boiler functions automati-

cally. With no demand for heat (central heating 

or domestic hot water production) the boiler 

goes to “standby” function, equivalent to the 

boiler being powered without presence of flame. 

Each time the burner ignites, the relative flame 

present symbol is displayed (10) with relative 

output scale.
• 

Operation with Comando Amico Remoto

V2

 

(CAR

V2

) (Optional)

. If the CAR

V2

 is connected, 

the (

) symbol will appear on the display. 

The boiler regulation parameters can be set via 

the CAR

V2

 control panel and the reset button 

(2) remains active on the boiler control panel, 

along with the switch-off button (6) (“off ” 

mode only) and the display where the function-

ing state is shown.

  

Caution:

 if the boiler is switched “off” the 

CAR

V2

 will display the connection error symbol 

“ERR>CM”, the CAR

V2

 is however powered 

constantly so as not to lose the stored programs.

• 

Operation with optional external probe 

(

)

.

 In the case of a system with optional 

external probe, the boiler flow temperature 

for room central heating is managed by the 

external probe depending on the external 

temperature measured (Par. 1.8). The flow 

temperature can be modified by selecting the 

functioning curve via the selector switch (4) 

(or on the CAR

V2

 control panel, if connected 

to the boiler) selecting a value from “0 to 9”.

  With external probe present, the relative 

symbol (18) will appear on the display. In the 

central heating phase, if the temperature of the 

water contained in the system is sufficient to 

heat the radiators, the boiler can only function 

with the activation of the pump.

• 

“Stand-by” mode.

 Press button (6) until the 

(

) symbol appears. The boiler remains 

active from this moment and the anti-freeze 

function, pump anti-block function and 3-way 

and signalling of any anomalies is guaranteed.

 

N.B.:

 in these conditions the boiler is still 

powered.

• 

“Off” mode.

 By holding the button (6) down 

for 8 seconds, only the central point remains lit 

on the display, and the boiler is off completely. 

The safety functions are not guaranteed in this 

mode.

 

IMPORTANT NOTE:

 in these conditions the 

boiler is considered still live even if there are 

no functions active.

• 

“Automatic vent” mode.

 When the function 

is enabled, every time the boiler is electrically 

powered, the system automatic vent function 

is activated (lasting 8 minutes). This function 

is displayed via a countdown signalled by the 

indicator (14). During this period the DHW 

and CH functions are not active.

  The “automatic vent” can be annulled by press-

ing the “reset” button (2).

• 

Display operation.

 The display lights up while 

the control panel is being used; after a set in-

activity period, the brightness drops until only 

the active symbols are displayed. The lighting 

mode can be varied via parameter t8 in the 

P.C.B. programming menu.

2.5 TROUBLESHOOTING.

The Victrix Maior 35 X TT 1 ErP boiler reports 

any anomalies using a code shown on the boiler 

display (14) according to the table below:

Error 

Code

Anomaly signalled

Cause

Boiler status / Solution

01

No ignition block

If room central heating or domestic hot water production is 

requested, 

(when the boiler is connected to an external storage tank 

unit)

the boiler does not switch on within the preset time. Upon 

appliance commissioning or after extended downtime, it may be 

necessary to eliminate the block.

Press the Reset button (1)

02

Safety thermostat 

block (over-temper-

ature)

During normal operation, if a fault causes excessive overheating 

internally, the boiler goes into overheating block.

Press the Reset button (1)

03

Flue safety thermostat 

block

During normal operation, if a fault causes excessive flue gas overheat-

ing, the boiler blocks.

Press the Reset button (1)

04

Contacts resistance 

block

The P.C.B. detects a fault on the gas valve supply. Check the connection. 

(the anomaly is detected and displayed only in the event of a request). Press the Reset button (1)

05

Flow probe anomaly

The board detects an anomaly on the flow NTC probe.

The boiler does not start (1)

08

Maximum N° of reset

Number of allowed resets that have already performed.

Attention: 

the anomaly can be reset 5 times 

consecutively, after which the function in 

inhibited for at least one hour. One attempt 

is gained every hour for a maximum of 5 

attempts. By switching the appliance on and 

off again, the 5 attempts are re-acquired.

(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical After-Sales Service).

(2) The anomaly can only be verified in the list of errors in the “Information” menu

STD.002549/004

Содержание VICTRIX MAIOR 35 X TT 1 ERP

Страница 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG STD 002549 004...

Страница 2: ...STD 002549 004...

Страница 3: ...ified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits establis...

Страница 4: ...ce 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 Syst...

Страница 5: ...removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safet...

Страница 6: ...kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Attention the excessive use of glycol could jeopardise the proper functioni...

Страница 7: ...ipes radiators etc with special pickling or descaling products to remove any deposits that could compromise correct boiler operation A treatment of the heating and water system water is required in co...

Страница 8: ...stats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two r...

Страница 9: ...ystem flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperature The exte...

Страница 10: ...owed cor responds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting...

Страница 11: ...nd Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pip...

Страница 12: ...the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Insta...

Страница 13: ...cular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of...

Страница 14: ...up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where ve...

Страница 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Страница 16: ...a The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a square s...

Страница 17: ...uildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with Type B open chamber boilers must not be installed in places where commerci...

Страница 18: ...ated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of use of w...

Страница 19: ...valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit i...

Страница 20: ...7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Return pr...

Страница 21: ...prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heati...

Страница 22: ...external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the system is sufficient to heat the radiators the b...

Страница 23: ...er flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler restar...

Страница 24: ...e has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Combustio...

Страница 25: ...ntly filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing Never...

Страница 26: ...eck that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices checktheproductionofDHW whentheboiler is connected to an external storage tank unit check seali...

Страница 27: ...or X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory B1 Boil...

Страница 28: ...are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condensation mo...

Страница 29: ...position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the function...

Страница 30: ...is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermedia...

Страница 31: ...E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve control set...

Страница 32: ...neral alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boiler model...

Страница 33: ...On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too ofte...

Страница 34: ...heck power supply Incaseoffunctioningindomestichotwa Id Parameter Parameter Description Range Default Customised value F0 Equivalent length flue Defines the length of the flue see par 3 12 0 2 0 F1 No...

Страница 35: ...integrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct calibr...

Страница 36: ...a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen screws d 6...

Страница 37: ...USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of side faste...

Страница 38: ...URNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94 3 51 2 58 31 5 27090 91 3 40 2 50 30 5 26230 88 3 29 2 42 29 5 25370 85 3 19...

Страница 39: ...80 60 C 0 24 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable heating temperature max oper...

Страница 40: ...l Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn...

Страница 41: ...1 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 004 kW Emissions of nitrogen oxides NOX 24 mg kWh For mixed central heating appliances Stated...

Страница 42: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Страница 43: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 44: ...ution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123...

Страница 45: ...nder colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G...

Страница 46: ...46 STD 002549 004...

Страница 47: ...47 STD 002549 004...

Страница 48: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 004 08 18 Inglese per IRLA...

Отзывы: