Immergas VICTRIX MAIOR 35 X TT 1 ERP Скачать руководство пользователя страница 29

29

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

3.7  CALIBRATION TYPE INVOLVING 

THE REPLACEMENT OF A 

COMPONENT.

When performing extraordinary maintenance 

on the boiler, involving the replacement of a 

component, such as the P.C.B. (if the removable 

memory is not put into the replacement board) 

or components in the air, gas and flame control 

circuits, the boiler will need to be calibrated.

Select the type of calibration to be carried out 

according to the table below.

Replaced 

component

Type of calibration 

required

Gas valve

Quick calibration

Fan

Quick calibration

Burner

Complete calibra-

tion with air-gas ratio 

check

Ignition/detection 

electrodes

Complete calibra-

tion with air-gas ratio 

check

P.C.B. 

(New virgin P.C.B. 

without removable 

memory recovery) 

Restore the param-

eters as described in 

the paragraph "P.C.B. 

programming"

Complete calibra-

tion with air-gas ratio 

check

P.C.B.

(Recovery of the 

removable memory 

with the boiler 

parameters set from 

the replaced board)

No calibration re-

quired.

3.8  COMPLETE CALIBRATION 

FUNCTION.

N.B.:

 before carrying out complete calibration, 

ensure that all the requirements indicated in 

paragraphs 1.23 and 1.24 have been fulfilled.

IMPORTANT NOTE:

 to access this function 

it is crucial that there are no active requests for 

central heating or DHW production.

In the event of anomaly “62” or “72” (see parag. 

2.5) the boiler cancels any requests by itself.

N.B.:

 during the various calibration stages, the 

air - gas ratio can be checked and possibly cor-

rected as described in par. 3.9.
The energy produced is dissipated via the heat-

ing circuit; alternatively, the energy can be 

released from the DHW circuit by opening any 

hot water tap.

Caution:

 in this case the only active temperature 

control is the flow probe that limits the maximum 

temperature exiting the boiler at 90°C, therefore 

be careful not to get burned.
- The calibration procedure involves various 

stages:

  - nominal heat output calibration;
  -  intermediate heat output ignition calibration;
  - minimum heat output calibration;
  - calibration self-check.
Each calibration procedure, if carried out without 

altering the parameters, lasts 5 minutes at the 

most, after which it switches automatically to 

the next parameter until the calibration process 

is complete.

In order to access the complete calibration 

stage, you must switch the boiler on, set the 

DHW selector in the “6 o' clock” position and 

the heating selector in the “9 o' clock” position, 

(Fig. 3-5) and press the “Reset” button for about 

8 seconds until the “chimney sweep” function 

is activated; then press the “summer / winter” 

button within 3 seconds.

• 

Nominal heat output:

 with the function active, 

the boiler carries out the procedures required 

to calibrate the appliance at the nominal heat 

output.

  At this stage the display features flashing 

icons: “summer”, “winter”, “stand-by” and the 

operating temperature alternated with the 

current operating heat output (99%); once the 

parameters are detected and stabilised, the 

frame of the flame presence symbol (ref. 10 fig. 

2-1) will start flashing (this procedure may last 

a few minutes), meaning that the nominal heat 

output parameters have been set.

  The air - gas ratio can only be corrected after 

the flame presence frame has flashed (see parag. 

3.9) or switch to the next heat output parameter 

by pressing the “info” button.

3-5

3-6

• 

Intermediate heat output ignition:

 once the 

nominal heat output calibration is confirmed, 

the boiler is calibrated with the intermediate 

heat output (or ignition heat output).

  At this stage the display features flashing 

icons: “summer”, “winter”, “stand-by” and the 

operating temperature alternated with the cur-

rent operating heat output (typically 41% but 

variable according to the boiler model); once 

the parameters are detected and stabilised, the 

frame of the flame presence symbol will start 

flashing, meaning that the intermediate heat 

output parameters have been set.

 

The air - gas ratio can only be corrected after 

the flame presence frame has flashed (see parag. 

3.9) or switch to the next heat output parameter 

by pressing the “info” button.

• 

Minimum heat output:

 after having calibrated 

the boiler with the intermediate heat output, it 

is calibrated with the minimum heat output.

  At this stage the display features flashing 

icons: “summer”, “winter”, “stand-by” and the 

operating temperature alternated with the 

current operating heat output (0%); once the 

parameters are detected and stabilised, the 

frame of the flame presence symbol will start 

flashing, meaning that the minimum heat 

output parameters have been set.

  The air - gas ratio can only be corrected after 

the flame presence frame has flashed (see parag. 

3.9) or exit the calibration mode by pressing the 

“summer / winter” button.

• 

Calibration self-check:

 once calibration opera-

tions are complete, the boiler runs a self-check 

for about one minute. During this check, the 

boiler can run at different powers and it is not 

possible to apply modifications to the operat-

ing parameters or to delete the operation in 

progress. Moreover, it is important not to cut 

the boiler's power.

3-7

3-8

STD.002549/004

Содержание VICTRIX MAIOR 35 X TT 1 ERP

Страница 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG STD 002549 004...

Страница 2: ...STD 002549 004...

Страница 3: ...ified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits establis...

Страница 4: ...ce 21 2 2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 Syst...

Страница 5: ...removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safet...

Страница 6: ...kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Attention the excessive use of glycol could jeopardise the proper functioni...

Страница 7: ...ipes radiators etc with special pickling or descaling products to remove any deposits that could compromise correct boiler operation A treatment of the heating and water system water is required in co...

Страница 8: ...stats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two r...

Страница 9: ...ystem flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperature The exte...

Страница 10: ...owed cor responds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting...

Страница 11: ...nd Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m 7 5 Pip...

Страница 12: ...the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws provided Insta...

Страница 13: ...cular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of...

Страница 14: ...up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas where ve...

Страница 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Страница 16: ...a The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a square s...

Страница 17: ...uildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with Type B open chamber boilers must not be installed in places where commerci...

Страница 18: ...ated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of use of w...

Страница 19: ...valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit i...

Страница 20: ...7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Return pr...

Страница 21: ...prohibited For safety purposes check that the concentric air intake flue exhaust terminal if fitted is not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heati...

Страница 22: ...external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the system is sufficient to heat the radiators the b...

Страница 23: ...er flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler restar...

Страница 24: ...e has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Combustio...

Страница 25: ...ntly filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing Never...

Страница 26: ...eck that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices checktheproductionofDHW whentheboiler is connected to an external storage tank unit check seali...

Страница 27: ...or X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory B1 Boil...

Страница 28: ...are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condensation mo...

Страница 29: ...position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the function...

Страница 30: ...is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermedia...

Страница 31: ...E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve control set...

Страница 32: ...neral alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boiler model...

Страница 33: ...On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too ofte...

Страница 34: ...heck power supply Incaseoffunctioningindomestichotwa Id Parameter Parameter Description Range Default Customised value F0 Equivalent length flue Defines the length of the flue see par 3 12 0 2 0 F1 No...

Страница 35: ...integrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct calibr...

Страница 36: ...a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen screws d 6...

Страница 37: ...USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of side faste...

Страница 38: ...URNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94 3 51 2 58 31 5 27090 91 3 40 2 50 30 5 26230 88 3 29 2 42 29 5 25370 85 3 19...

Страница 39: ...80 60 C 0 24 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating temperature C 90 Adjustable heating temperature max oper...

Страница 40: ...l Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn...

Страница 41: ...1 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 004 kW Emissions of nitrogen oxides NOX 24 mg kWh For mixed central heating appliances Stated...

Страница 42: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Страница 43: ...energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further facto...

Страница 44: ...ution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123...

Страница 45: ...nder colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G...

Страница 46: ...46 STD 002549 004...

Страница 47: ...47 STD 002549 004...

Страница 48: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 004 08 18 Inglese per IRLA...

Отзывы: