  B1  - Flow probe

  B2  - Domestic hot water probe (optional)

  B4  - External probe (optional)

 CAR

V2

  - Comando Amico Remoto remote control 

V2

 

(optional)

  DS1  - Display

  E3  - Ignition and detection electrode

  E4  - Safety thermostat

  F1  - Phase fuse

  M1  - Boiler circulator pump

  M20  - Fan

  M30  - Three-way valve (optional)

  R5  - Domestic hot water temperature trim-

mer

  R6  - Central heating temperature trimmer

  R8  - Storage tank function unabling resist-

ance

  S2  - Operation selector

  S3  - Block reset button

  S5  - System pressure switch

  S6  - Flue pressure switch

  S20  - Room thermostat (optional)

  S29  - D.H.W. priority unabling button

  S31  - On/Stand-by/Off Button

  T1  - Ignition transformer

  T2  - Boiler board transformer

  X40  - Room thermostat jumper

  Y1  - Gas valve

  Y2  - Gas valve modulator

  R8  - Storage tank function unabling 

resistance

  U1  - Rectifier inside the gas valve con-

nector (only available on Honeywell 

gas valves)

 

1  - N.B.: the user interface is on the 

welding side of the boiler board

 

2  - Zones control unit (optional)

 

3  - 230 Vac 50 Hz power supply

 

4  - Anti-freeze kit (optional)

 

5  - Storage tank unit (optional)

 

6  - Blue

 

7  - Brown

 

8  - Black

 

9  - Yellow/green

  10  - Orange

  11  - Red

  12  - White

  13  - Grey

  14  - Green

  15  - Domestic hot water

  16  - Central heating

3.2  WIRING DIAGRAM.

Remote control: the boiler is set-up for the ap-

plication of the Comando Amico Remoto remote 

control

V2

 (CAR

V2

) which must be connected to 

clamps 41 and 44 of connector X15 on the P.C.B., 

observing polarity and eliminating jumper X40.
Room thermostat: the boiler is designed for the 

application of the Room Thermostat (S20). Con-

nect it to clamps 40 – 41 eliminating jumper X40.
Storage tank unit: the boiler is set-up for the 

application of a storage tank unit, which must 

be connected to clamps 36-37 of the bipolar 

terminal board located under the sealed chamber 

and eliminating resistance R8.
The connector X5 is used for the connection to 

the relay board.
The connector X6 is for connection to a personal 

computer.
The connector X8 is used for software updating 

operations.

3.3 TROUBLESHOOTING.
N.B.: 

maintenance operations must be carried 

out by an authorised company (e.g. Authorised 

After-Sales Technical Assistance Service).
-  Smell of gas. Caused by leakage from gas circuit 

pipelines. Check sealing efficiency of gas intake 

circuit.

- The fan works but ignition discharge does not 

take place on the burner ramp. The fan may 

start but the safety air pressure switch does not 

switch the contact over. Make sure:

1)  that the intake-exhaust duct is not too long 

(over allowed length).

2)  that the intake-exhaust duct is not partially 

blocked (on the exhaust or intake side).

3)  the diaphragm of the flue exhaust is adequate 

for the length of the intake-exhaust duct.

4)  that the sealed chamber is sealed perfectly.
5)  the fan power supply voltage is not less than 

196 V.

- Irregular combustion (red or yellow flame). 

Can be caused by: dirty burner, clogged lamel-

lar pack, intake - exhaust terminal not installed 

properly. Clean the above components and 

ensure correct installation of the terminal.

- Frequent interventions of the over heating 

safety thermostat. It can depend on reduced 

water pressure in the boiler, little circulation 

in the heating system, the blocked pump or an 

anomaly of the boiler P.C.B. Check on the pres-

sure gauge that the system pressure is within 

established limits. Check that radiator valves 

are not all closed.

- The boiler produces condensate. It can be de-

termined by functioning at boiler temperatures 

that are excessively low. In this case, make the 

boiler run at higher temperatures.

-  Presence of air in the system. Check opening of 

the special air vent valve cap (Fig. 1-30). Make 

sure the system pressure and expansion vessel  

factory-set pressure values are within the set 

limits; the factory-set value for the expansion 

vessel must be 1.0 bar, and system pressure 

between 1 and 1.2 bar.

- Ignition block see par. 2.5 and 1.6 (electric 

connection).

Содержание 3.020928

Страница 1: ...MAIOR EOLO X 28 Instruction and recommendation booklet 1 038769ENG...

Страница 2: ......

Страница 3: ...specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits esta...

Страница 4: ...ce 19 2 2 General warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Troubleshooting 21 2 6 Boiler shutdown 22 2 7 Restoring central heating system pressure 22 2 8 System draining 22 2 9 Ant...

Страница 5: ...ances underneath the boiler as they could be damaged if the safety valve intervenes if the drain trap is blocked or if there are leaks from the hydraulic connec tions otherwise the manufacturer cannot...

Страница 6: ...ts the central heating circuit from freez ing by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must...

Страница 7: ...cal standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits Water connections must be made in a rational way using the couplings...

Страница 8: ...h its climate thermostat function disabled i e it must be set to On Off mode Comando Amico Remoto Remote Control V2 or On Off chrono thermostat electrical con nections Optional The operations describe...

Страница 9: ...haust in individual flue or to the outside The boiler with this type of configuration is classified as type B22 in accordance with the technical standards in force With this configuration air intake t...

Страница 10: ...with the boiler as standard DIAPHRAGM Shutter regulation table Flue gas shutter notch Type of installation duct length in metres 2 4 7 10 60 100 horizontal concentric kit From 0 to 0 5 From 0 5 to 1...

Страница 11: ...6 Exhaust m 2 0 Terminal complete with concentric vertical intake exhaust 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Concentric vertical intake exhaust termi nal 80 125 Inta...

Страница 12: ...it 80 125 Kit assembly Fig 1 18 install the bend with flange 2 onto the central hole of the boiler inserting the gasket 1 and tighten using the screws in cluded in the kit Fit the male end smooth of t...

Страница 13: ...in the figure Combustion products are expelled from pipe S Air is taken in through pipe A for combustion The intake pipe A can be installed either on the right or left hand side of the central exhaust...

Страница 14: ...screws included in the kit Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioning the gasket 2 already pre...

Страница 15: ...gas exhaust outlets to the same height Temperature loss in insulated flue ducting To prevent problems of flue gas condensate in the insulated exhaust pipe 80 due to flue gas cooling through the wall t...

Страница 16: ...edatlowspeedtoensurerelease of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the circulator Check if the cap is loose Open the r...

Страница 17: ...n type B it is compulsory to mount the appropriate top protection cover along with the flue exhaust kit Anti freeze kit with resistance on request If the boiler is installed in a place where the tempe...

Страница 18: ...itive signal pressure point 8 Negative signal pressure point 9 Flue pressure switch 10 Flow probe 11 Fumes hood 12 Safety thermostat 13 Primary heat exchanger 14 Ignition and detection electrodes 15 S...

Страница 19: ...cal power requires some funda mental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the appli ance...

Страница 20: ...to the boiler being powered without presence of flame Each time the burner ignites the relative flame present symbol is displayed 11 with relative output scale Operation with Comando Amico RemotoV2 C...

Страница 21: ...nables fan start up incorrectly or in the event of a flue gas pressure switch fault If normal conditions are restored the boiler restarts without having to be reset 1 12 Storage tank probe anomaly If...

Страница 22: ...y of the appliance and the domestic hot water heating system in areas where the temperature falls below zero we recommend protecting the central heating system with anti freeze liquid and installing t...

Страница 23: ...and that the manometer indicates a pressure of 1 1 2 bar make sure the air valve cap is open and that the system is well deaerated switch the boiler on and check correct ignition make sure the gas ma...

Страница 24: ...minating resistance R8 The connector X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operation...

Страница 25: ...he type of gas being used S3 Boiler type Establishes the boiler type and its functioning mode 0 combi 1 24 kW storage tank 2 28 kW storage tank 3 32kW storage tank 0 3 2 S4 Power block Establishes the...

Страница 26: ...0 P5 Relay 3 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas val...

Страница 27: ...be adjusted must not be lower than that stated in the tables par 3 18 Adjustment any of the boiler maximum heat output in central heating phase To adjust the maximum heat output during the heating ph...

Страница 28: ...tion of approx 10 seconds N B during self check the boiler remains off including signalling 3 15 SOLAR PANELS COUPLING FUNCTION In the event of integration of DHW heating with solar panel systems for...

Страница 29: ...the guard a 3 Unhook the decorative frame c from the relative lower retainers 4 Remove the decorative frame c from the cas ing e 5 Loosen the 2 front screws d that fasten the casing 6 Loosen the 2 lo...

Страница 30: ...30 3 5 6 6 7 8 8 f f e INSTALLER USER MAINTENANCE TECHNICIAN...

Страница 31: ...7 22 0 18920 2 49 7 43 75 8 1 86 18 61 189 8 1 83 22 76 232 1 21 0 18060 2 38 6 82 69 6 1 78 17 24 175 8 1 75 20 92 213 4 20 0 17200 2 27 6 24 63 7 1 70 15 91 162 3 1 67 19 18 195 6 19 0 16340 2 17 5...

Страница 32: ...eat output useful kW kcal h 11 2 9632 Efficiency at nominal heat output 94 3 Efficiency at 30 nominal heat output load 91 5 Heat loss at case with burner On Off 0 0 0 53 Heat loss at flue with burner...

Страница 33: ...odel code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH m...

Страница 34: ......

Страница 35: ......

Страница 36: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Отзывы: