Immergas 3.020928 Скачать руководство пользователя страница 17

17

1-29

A

B

C

D

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

H

ea

d (m H

2

O)

Flow rate (l/h)

H

ea

d (kP

a)

Head available to the system.

  A  =  Head available to the system at 

maximum speed with by-pass 

excluded

  B  =  Head available to the system at 

maximum speed with by-pass 

inserted

  C  =  Head available to the system 

at second speed with by-pass 

excluded

  D  =  Head available to the system 

at second speed with by-pass 

inserted

1.19 KITS AVAILABLE ON REQUEST.

•  System shut off valves kit. The boiler is designed 

for installation of system interception cocks 

to be placed on flow and return pipes of the 

connection assembly. This kit is particularly 

useful for maintenance as it allows the boiler to 

be drained separately without having to empty 

the entire system.

• System zone control unit Kit. If the heating 

system is to be divided into several zones 

(max. 

three),

 in order to interlock them with separate 

adjustments and to keep water flow rate high 

for each zone, Immergas supplies zone system 

kits by request.

• Polyphosphate dispenser kit. The polyphos-

phate dispenser reduces  the formation of lime-

scale and preserves the original heat exchange 

and domestic hot water production conditions. 

The boiler is prepared for application of the 

polyphosphate dispenser kit.

• Cover kit. If installed outdoors in a partially 

sheltered place with direct air intake, it is 

compulsory to mount the appropriate top pro-

tection cover for the correct functioning of the 

boiler and to protect it from adverse weather 

conditions (Fig. 1-6); or, if installed indoors in 

configuration type B, it is compulsory to mount 

the appropriate top protection cover along with 

the flue exhaust kit.

Anti freeze kit with resistance (on request). If the 

boiler is installed in a place where the tempera-

ture falls below -5°C and in the event there is 

no gas, the appliance can freeze. To prevent 

freezing of the domestic hot water system, an 

anti freeze kit with an electrical resistance can 

be fitted from the relative cable and from a 

control thermostat.

• External storage tank unit coupling kit. If the 

production of DHW is required as well as room 

central heating, on request Immergas supplies 

a kit made up from an external cylinder unit 

and everything necessary for adaptation of the 

boiler

The above-mentioned kits are supplied complete 

with instructions for assembly and use.

1.18 CIRCULATION PUMP.

The boilers are supplied with a built-in circula-

tion pump with 3-position electric speed control. 

The boiler does not operate correctly with the 

circulation pump on first speed. To ensure opti-

mal boiler operation, in the case of new systems 

(single pipe and module) it is recommended to 

use the pump at maximum speed. The circulation 

pump is already fitted with a capacitor.

Pump release.

 If, after a prolonged period of 

inactivity, the circulation pump is blocked, 

unscrew the front cap and turn the motor shaft 

using a screwdriver. Take great care during this 

operation to avoid damage to the motor.

By-pass Regulation (part. 25 Fig. 1-30).

 If nec-

essary, the by-pass can be adjusted according to 

system requirements from a minimum (by-pass 

excluded) to a maximum (by-pass inserted) 

represented by the graph (Fig. 1-29). Make the 

regulation using a flat head screwdriver, turn 

clockwise and insert the by-pass, anti-clockwise 

it is excluded.

Содержание 3.020928

Страница 1: ...MAIOR EOLO X 28 Instruction and recommendation booklet 1 038769ENG...

Страница 2: ......

Страница 3: ...specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits esta...

Страница 4: ...ce 19 2 2 General warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Troubleshooting 21 2 6 Boiler shutdown 22 2 7 Restoring central heating system pressure 22 2 8 System draining 22 2 9 Ant...

Страница 5: ...ances underneath the boiler as they could be damaged if the safety valve intervenes if the drain trap is blocked or if there are leaks from the hydraulic connec tions otherwise the manufacturer cannot...

Страница 6: ...ts the central heating circuit from freez ing by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must...

Страница 7: ...cal standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits Water connections must be made in a rational way using the couplings...

Страница 8: ...h its climate thermostat function disabled i e it must be set to On Off mode Comando Amico Remoto Remote Control V2 or On Off chrono thermostat electrical con nections Optional The operations describe...

Страница 9: ...haust in individual flue or to the outside The boiler with this type of configuration is classified as type B22 in accordance with the technical standards in force With this configuration air intake t...

Страница 10: ...with the boiler as standard DIAPHRAGM Shutter regulation table Flue gas shutter notch Type of installation duct length in metres 2 4 7 10 60 100 horizontal concentric kit From 0 to 0 5 From 0 5 to 1...

Страница 11: ...6 Exhaust m 2 0 Terminal complete with concentric vertical intake exhaust 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Concentric vertical intake exhaust termi nal 80 125 Inta...

Страница 12: ...it 80 125 Kit assembly Fig 1 18 install the bend with flange 2 onto the central hole of the boiler inserting the gasket 1 and tighten using the screws in cluded in the kit Fit the male end smooth of t...

Страница 13: ...in the figure Combustion products are expelled from pipe S Air is taken in through pipe A for combustion The intake pipe A can be installed either on the right or left hand side of the central exhaust...

Страница 14: ...screws included in the kit Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioning the gasket 2 already pre...

Страница 15: ...gas exhaust outlets to the same height Temperature loss in insulated flue ducting To prevent problems of flue gas condensate in the insulated exhaust pipe 80 due to flue gas cooling through the wall t...

Страница 16: ...edatlowspeedtoensurerelease of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the circulator Check if the cap is loose Open the r...

Страница 17: ...n type B it is compulsory to mount the appropriate top protection cover along with the flue exhaust kit Anti freeze kit with resistance on request If the boiler is installed in a place where the tempe...

Страница 18: ...itive signal pressure point 8 Negative signal pressure point 9 Flue pressure switch 10 Flow probe 11 Fumes hood 12 Safety thermostat 13 Primary heat exchanger 14 Ignition and detection electrodes 15 S...

Страница 19: ...cal power requires some funda mental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the appli ance...

Страница 20: ...to the boiler being powered without presence of flame Each time the burner ignites the relative flame present symbol is displayed 11 with relative output scale Operation with Comando Amico RemotoV2 C...

Страница 21: ...nables fan start up incorrectly or in the event of a flue gas pressure switch fault If normal conditions are restored the boiler restarts without having to be reset 1 12 Storage tank probe anomaly If...

Страница 22: ...y of the appliance and the domestic hot water heating system in areas where the temperature falls below zero we recommend protecting the central heating system with anti freeze liquid and installing t...

Страница 23: ...and that the manometer indicates a pressure of 1 1 2 bar make sure the air valve cap is open and that the system is well deaerated switch the boiler on and check correct ignition make sure the gas ma...

Страница 24: ...minating resistance R8 The connector X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operation...

Страница 25: ...he type of gas being used S3 Boiler type Establishes the boiler type and its functioning mode 0 combi 1 24 kW storage tank 2 28 kW storage tank 3 32kW storage tank 0 3 2 S4 Power block Establishes the...

Страница 26: ...0 P5 Relay 3 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas val...

Страница 27: ...be adjusted must not be lower than that stated in the tables par 3 18 Adjustment any of the boiler maximum heat output in central heating phase To adjust the maximum heat output during the heating ph...

Страница 28: ...tion of approx 10 seconds N B during self check the boiler remains off including signalling 3 15 SOLAR PANELS COUPLING FUNCTION In the event of integration of DHW heating with solar panel systems for...

Страница 29: ...the guard a 3 Unhook the decorative frame c from the relative lower retainers 4 Remove the decorative frame c from the cas ing e 5 Loosen the 2 front screws d that fasten the casing 6 Loosen the 2 lo...

Страница 30: ...30 3 5 6 6 7 8 8 f f e INSTALLER USER MAINTENANCE TECHNICIAN...

Страница 31: ...7 22 0 18920 2 49 7 43 75 8 1 86 18 61 189 8 1 83 22 76 232 1 21 0 18060 2 38 6 82 69 6 1 78 17 24 175 8 1 75 20 92 213 4 20 0 17200 2 27 6 24 63 7 1 70 15 91 162 3 1 67 19 18 195 6 19 0 16340 2 17 5...

Страница 32: ...eat output useful kW kcal h 11 2 9632 Efficiency at nominal heat output 94 3 Efficiency at 30 nominal heat output load 91 5 Heat loss at case with burner On Off 0 0 0 53 Heat loss at flue with burner...

Страница 33: ...odel code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH m...

Страница 34: ......

Страница 35: ......

Страница 36: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Отзывы: