2.5 TROUBLESHOOTING.

In the event of an anomaly, it is signalled via 

the flashing indicator (14) on the boiler display 

according to the following table.

On the remote control, the error code will be 

displayed by means of the same numeric code 

represented according to the following example 

(e.g. CAR

V2

 = Exx).

Error 

Code

Anomaly signalled

Cause

Boiler status / Solution

01

No ignition block

If room central heating or domestic hot water production is requested, 

(when the boiler is connected to an external storage tank unit)

the boiler 

does not switch on within the preset time. Upon appliance commissioning 

or after extended downtime, it may be necessary to eliminate the block.

Press the Reset button (1).

02

Safety thermostat 

block (overheat-

ing), flame control 

anomaly

During normal operation, if a fault causes excessive overheating internally, 

the boiler goes into overheating block.

Press the Reset button after cooling (1).

03

Fan anomaly

This occurs if the fan is blocked or if the intake or drain pipes are ob-

structed.

If normal conditions are restored the boiler 

restarts without having to be reset (1).

04

Generic boiler 

P.C.B. anomaly

This occurs when a signal is recognised incorrectly by the boiler P.C.B. 

microprocessor.

Press the Reset button (1).

05

Flow probe 

anomaly

The board detects an anomaly on the flow probe.

The boiler does not start (1).

08

Maximum N° of 

reset

Number of allowed resets that have already performed.

Attention: 

the anomaly can be reset 5 times 

consecutively, after which the function in 

inhibited for at least one hour. One attempt 

is gained every hour for a maximum of 5 

attempts. By switching the appliance on and 

off the 5 attempts are re-acquired.

10

Insufficient system 

pressure

Water pressure inside the central heating circuit that is sufficient to guar-

antee the correct operation of the boiler is not detected.

Check on the boiler pressure gauge (1) that 

the system pressure is between 1÷1.2 bar 

and restore the correct pressure if necessary.

11

Flue pressure 

switch failure

This occurs in the event of an error on the P.C.B. that enables fan start-up 

incorrectly or in the event of a flue-gas pressure switch fault.

If normal conditions are restored the boiler 

restarts without having to be reset (1).

12

Storage tank probe 

anomaly

If the board detects an anomaly on the boiler probe, the boiler cannot 

produce domestic hot water 

(when the boiler is connected to an external 

storage tank unit)

.

(1).

15

Configuration error

If the board detects an anomaly or incongruity on the electric wiring, the 

boiler will not start.

If normal conditions are restored the boiler 

restarts without having to be reset (1).

20

Parasite flame

This occurs in the event of a leak on the detection circuit or anomaly in 

the flame control unit.

Press the Reset button (1).

24

Push button control 

panel anomaly

The board detects an anomaly on the pushbutton panel.

If normal conditions are restored the boiler 

restarts without having to be reset (1).

27

Insufficient circula-

tion

This occurs if there is overheating in the boiler due to insufficient water 

circulating in the primary circuit; the causes can be: 
-  low system circulation; check that no shut-off devices are closed on the 

heating circuit and that the system is free of air (deaerated);

- pump blocked; free the pump.

Press the Reset button (1).

31

Loss of remote 

control communi-

cation.

This occurs if an incompatible remote control is connected, or after 1 

minute if communication is lost between the boiler and CAR

V2

.

Power cycle the boiler. If the Remote Con-

trol is still not detected on re-starting the 

boiler will switch to local operating mode, 

i.e. using the controls on the control panel. 

In this case the “Central heating” mode (1) 

cannot be activated.

37

Low power supply 

voltage

This occurs when the power supply voltage is lower than the allowed limits 

for the correct boiler operation. 

If normal conditions are restored the boiler 

restarts without having to be reset (1).

38

Loss of flame signal

 This occurs when the boiler is ignited correctly and the burner flame 

switches off unexpectedly; a new attempt at ignition is performed and 

if normal conditions are restored, the boiler does not have to be reset.

If normal conditions are restored the boiler 

restarts without having to be reset (1).

(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical After-Sales Service).

Содержание 3.020928

Страница 1: ...MAIOR EOLO X 28 Instruction and recommendation booklet 1 038769ENG...

Страница 2: ......

Страница 3: ...specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits esta...

Страница 4: ...ce 19 2 2 General warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Troubleshooting 21 2 6 Boiler shutdown 22 2 7 Restoring central heating system pressure 22 2 8 System draining 22 2 9 Ant...

Страница 5: ...ances underneath the boiler as they could be damaged if the safety valve intervenes if the drain trap is blocked or if there are leaks from the hydraulic connec tions otherwise the manufacturer cannot...

Страница 6: ...ts the central heating circuit from freez ing by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must...

Страница 7: ...cal standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits Water connections must be made in a rational way using the couplings...

Страница 8: ...h its climate thermostat function disabled i e it must be set to On Off mode Comando Amico Remoto Remote Control V2 or On Off chrono thermostat electrical con nections Optional The operations describe...

Страница 9: ...haust in individual flue or to the outside The boiler with this type of configuration is classified as type B22 in accordance with the technical standards in force With this configuration air intake t...

Страница 10: ...with the boiler as standard DIAPHRAGM Shutter regulation table Flue gas shutter notch Type of installation duct length in metres 2 4 7 10 60 100 horizontal concentric kit From 0 to 0 5 From 0 5 to 1...

Страница 11: ...6 Exhaust m 2 0 Terminal complete with concentric vertical intake exhaust 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Concentric vertical intake exhaust termi nal 80 125 Inta...

Страница 12: ...it 80 125 Kit assembly Fig 1 18 install the bend with flange 2 onto the central hole of the boiler inserting the gasket 1 and tighten using the screws in cluded in the kit Fit the male end smooth of t...

Страница 13: ...in the figure Combustion products are expelled from pipe S Air is taken in through pipe A for combustion The intake pipe A can be installed either on the right or left hand side of the central exhaust...

Страница 14: ...screws included in the kit Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioning the gasket 2 already pre...

Страница 15: ...gas exhaust outlets to the same height Temperature loss in insulated flue ducting To prevent problems of flue gas condensate in the insulated exhaust pipe 80 due to flue gas cooling through the wall t...

Страница 16: ...edatlowspeedtoensurerelease of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the circulator Check if the cap is loose Open the r...

Страница 17: ...n type B it is compulsory to mount the appropriate top protection cover along with the flue exhaust kit Anti freeze kit with resistance on request If the boiler is installed in a place where the tempe...

Страница 18: ...itive signal pressure point 8 Negative signal pressure point 9 Flue pressure switch 10 Flow probe 11 Fumes hood 12 Safety thermostat 13 Primary heat exchanger 14 Ignition and detection electrodes 15 S...

Страница 19: ...cal power requires some funda mental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the appli ance...

Страница 20: ...to the boiler being powered without presence of flame Each time the burner ignites the relative flame present symbol is displayed 11 with relative output scale Operation with Comando Amico RemotoV2 C...

Страница 21: ...nables fan start up incorrectly or in the event of a flue gas pressure switch fault If normal conditions are restored the boiler restarts without having to be reset 1 12 Storage tank probe anomaly If...

Страница 22: ...y of the appliance and the domestic hot water heating system in areas where the temperature falls below zero we recommend protecting the central heating system with anti freeze liquid and installing t...

Страница 23: ...and that the manometer indicates a pressure of 1 1 2 bar make sure the air valve cap is open and that the system is well deaerated switch the boiler on and check correct ignition make sure the gas ma...

Страница 24: ...minating resistance R8 The connector X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operation...

Страница 25: ...he type of gas being used S3 Boiler type Establishes the boiler type and its functioning mode 0 combi 1 24 kW storage tank 2 28 kW storage tank 3 32kW storage tank 0 3 2 S4 Power block Establishes the...

Страница 26: ...0 P5 Relay 3 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas val...

Страница 27: ...be adjusted must not be lower than that stated in the tables par 3 18 Adjustment any of the boiler maximum heat output in central heating phase To adjust the maximum heat output during the heating ph...

Страница 28: ...tion of approx 10 seconds N B during self check the boiler remains off including signalling 3 15 SOLAR PANELS COUPLING FUNCTION In the event of integration of DHW heating with solar panel systems for...

Страница 29: ...the guard a 3 Unhook the decorative frame c from the relative lower retainers 4 Remove the decorative frame c from the cas ing e 5 Loosen the 2 front screws d that fasten the casing 6 Loosen the 2 lo...

Страница 30: ...30 3 5 6 6 7 8 8 f f e INSTALLER USER MAINTENANCE TECHNICIAN...

Страница 31: ...7 22 0 18920 2 49 7 43 75 8 1 86 18 61 189 8 1 83 22 76 232 1 21 0 18060 2 38 6 82 69 6 1 78 17 24 175 8 1 75 20 92 213 4 20 0 17200 2 27 6 24 63 7 1 70 15 91 162 3 1 67 19 18 195 6 19 0 16340 2 17 5...

Страница 32: ...eat output useful kW kcal h 11 2 9632 Efficiency at nominal heat output 94 3 Efficiency at 30 nominal heat output load 91 5 Heat loss at case with burner On Off 0 0 0 53 Heat loss at flue with burner...

Страница 33: ...odel code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH m...

Страница 34: ......

Страница 35: ......

Страница 36: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Отзывы: