Electronic pressure sensor
PI16xx PI18xx
33
12 Troubleshooting
12.1 Troubleshooting
The unit has many self-diagnostic options.
•
It monitors itself automatically during operation.
•
It indicates warnings and faults via IO-Link and via display (even if the display is deactivated).
•
If a fault is found, the outputs are set according to the setting of the parameters FOU1 and FOU2.
Display
Warning
Error
Status LED
Type of error or event
Corrective measures
Err
X
unit faulty
u
Replace the unit.
SIM + PW
(alternately)
X
Simulation function active
IO-L
X
Optical identification function
active
OFF
X
Supply voltage too low.
u
Check / correct the supply voltage.
u
In 2-wire operation: Check / correct
the connected load.
SC1
X
OUT1 flashes
Short circuit switching output
1.
u
Check switching output 1 for short
circuit, eliminate fault.
SC2
X
OUT2 flashes
Short circuit switching output
2.
u
Check switching output 2 for short
circuit, eliminate fault.
SC
X
OUT1
and OUT2
flash
Short circuit switching output
1 and switching output 2.
u
Check switching outputs 1 and 2 for
short circuits; Remove the fault.
PArA
X
Parameter setting outside
the permissible range.
u
Repeat parameter setting.
u
Change parameter setting
u
Carry out [APPL] or [btb] reset.
See:
OL
X
Above the measuring range:
measured value greater
+5% VMR
u
Check / reduce pressure.
UL
X
Below the measuring range
u
Check / increase pressure.
Loc
X
Setting keys on the unit
locked, parameter change
rejected.
u
Unlock.
C.Loc
X
Parameter setting via keys
locked, parameter setting is
active via IO-Link communi-
cation.
u
Finish the IO-Link communication
before parameters are set on the
sensor.
S.Loc
X
Setting keys locked via pa-
rameter setting software, pa-
rameter change rejected.
u
Unlock sensor via parameter setting
software.