![IFM PI16 Series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/ifm/pi16-series/pi16-series_operating-instructions-manual_4118550030.webp)
PI16xx PI18xx
Electronic pressure sensor
30
After the reset, the sensor suspends communication and measurement operation until the
voltage is interrupted. The IO-Link data storage is not triggered.
10.6 Simulation function
10.6.1 Open menu level 3 (simulation)
u
Select the parameter [SIM] in menu level 2 (extended functions) with [▲] or [▼].
u
Press [Enter] (= open menu level 3).
w
Simulation parameters are selectable.
[SIM]
10.7 Simulation
10.7.1 Set simulation value
u
Select [S.PRS].
u
Set the process value to be simulated.
[Numerical value] = pressure (depending on basic setting).
[OL] = Above the measuring range.
[UL] = Below the measuring range.
[Err] = Electronic error detected.
u
Press [Enter].
[S.PRS]
10.7.2 Set simulation value
u
Select [S.Tim].
u
Set time span for simulation.
u
Press [Enter].
Setting range: 1, 2, 3, 4, 5, 10, 15, 20, 30, 45, 60 min.
Factory setting: 3 min.
[S.Tim]
10.7.3 Switch simulation on / off
u
Select [S.On] and set:
[OFF] = simulation off
[On] = simulation on
u
Press [Enter] to start the simulation
[S.On]
Simulation active until [Enter] is pressed again or the time set via [STim] elapses. During the
simulation [SIM] is displayed every 3 s.
After the simulation the unit returns to the parameter [S.On] and internally the unit returns to the
operating mode (and the process value transmission). After another 30 s the display returns to
the process value display.
If the simulation is started via IO-Link, it can also only be finished via IO-Link. During the
attempt to finish the simulation via the buttons, C.Loc is displayed.