PI16xx PI18xx
Electronic pressure sensor
26
Exit parameter without applying the settings:
u
Press [▲] + [▼] simultaneously.
w
Return to the menu level.
To exit the menu level:
u
Press [▲] + [▼] simultaneously.
w
Menu level 2 changes to level 1
or
level 1 changes to the display.
In 2-wire mode, those menu items that refer to switching functions are not active (
Ò
Menu
structure); in addition, for some menu items, those parameter values that refer to switching
functions cannot be selected.
10.2 Configure display (optional)
If the unit of measurement [uni.P] has to be changed, this needs to be done before setting other
parameters to avoid internal rounding deviations due to unit conversion.
u
Select [uni.P] and set the unit of measurement:
• [bAr], [mbAr], [MPA], [kPA].
• [psi] (depends on the device).
• [InHO] (depends on the device).
• [mWS] (depends on the device).
• [mmWS] (depends on the device).
[uni.P]
Selectable units of measurement → data sheet.
Uni.P only affects the sensor display. The IO-Link process value remains unaffected.