PI16xx PI18xx
Electronic pressure sensor
20
9 Menu
9.1 Menu structure: Main menu
1
RUN
rP1
SP2
rP2
tcoF
....
tASP
....
tAEP
....
FH1
FL1
FH2
FL2
ASP2
AEP2
EF
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
SP1
1000
1000
900
900
1000
1000
900
900
1000
0
9.05
1
1: Change to menu level 2 (extended functions).
Menu items highlighted in grey are active depending on the configuration of the output.
9.2 Explanation of the main menu
SPx / rPx*
Hysteresis function: upper / lower limit value for system pressure at which OUTx switches.
Requirement: OUTx setting is [Hno] or [Hnc].
FHx / FLx*
Window function: upper / lower limit value for system pressure at which OUTx switches.
Requirement: OUTx setting is [Fno] or [Fnc].
ASP2
Analogue start point for system pressure: measured value at which 4 mA (20 mA) are provided. Require-
ment: OUT2 setting is [I] or ([InEG]).
AEP2
Analogue end point for system pressure: measured value at which 20 mA (4 mA) are provided. Require-
ment: OUT2 setting is [I] or ([InEG]).
tcoF
Teach zero-point calibration.
tASP
Teach analogue start point for system pressure: set measured value at which 4 mA is provided (20 mA if
[OU2] = [InEG]).
tAEP
Teach analogue end point for system pressure: set measured value at which 20 mA is provided (4 mA if
[OU2] = [InEG]).
EF
Extended functions / opening of menu level 2.
* menu items not active in 2-wire operation