IO-Link master
22
14 Connection options
14.1 ProfiNet and voltage supply connection
Port1
Port2
U IN
S
U IN
A
U OUT
S
U OUT
A
Port 1 (X21): Ethernet port 1
Port 2 (X22): Ethernet port 2
U
S
IN (X31): voltage supply IN (logic and sensors)
U
A
IN (X31): voltage supply IN (IO-Link actuators)
U
S
OUT (X32): voltage supply OUT for additional devices
U
A
OUT (X32): voltage supply OUT for additional devices
► Ground the device using the screws
14.2 ProfiNet pin connection
1
2
3
4
Ethernet port 1 X21
1: TX +
2: RX +
3: TX -
4: RX -
1
2
3
4
Ethernet port 2 X22
1: TX +
2: RX +
3: TX -
4: RX -
The shield is connected to FE in the device� The thread is used for additional shielding�
14.3 Pin connection voltage supply U
S
/U
A
3
1
4
2
IN X31
1: + 24 V DC (U
S
) brown
2: GND (U
A
) white
3: GND (U
S
) blue
4: + 24 V DC (U
A
) black
3
1
4
2
OUT X32
1: + 24 V DC (U
S
) brown
2: GND (U
A
) white
3: GND (U
S
) blue
4: + 24 V DC (U
A
) black
Pin connection voltage supply, T-coded