IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
81
>
13.3.10 0x08: Factory Defaults
52145
The command resets the configuration of the IO-Link ports of the IO-Link master to the factory
settings. The bytes 4...8 contain the "reset" string in hexadecimal representation.
>
Command request
52146
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
0x08
2
0x0A
3
0x05
4
0x72
5
0x65
6
0x73
7
0x65
8
0x74
9...160
ignored
>
Command response
52147
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
0x00
4...160
ignored
Diagnostic codes:
0x04
Blocked Port - another acyclic access is still active
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x09
Wrong parameter (value of a parameter not in proper range)
0x0A
Wrong Block ID