IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
88
>
Command response
52156
Byte
Bit
7
6
5
4
3
2
1
0
0
Block-ID
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
Parameter Data Length (n Bytes)
4
Parameter Data (Byte 1)
...
...
4+(n-1)
Parameter Data (Byte n)
(4+n)...160
ignored
Legend:
[Parameter Data Length]
Length of the return data (number of bytes n)
8 bits
0x00
...
0 bytes
...
0x9C
156 bytes
[Parameter Data (Byte m)]
Parameter-Daten (m = 1...n)
n*8 bits
per byte: 0x00...0xFF
Diagnostic codes:
0x01
OK
0x04
Blocked Port - another acyclic access is still active
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x0A
Wrong Block ID
0x0B
Error - for additional information see data field