IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
76
>
Command response
52138
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
Response data length (number of bytes m)
4
Output acyclic process data switch (OPDS)
5
Output Data (Byte 1)
...
...
5+(n-1)
Output Data (Byte n)
(5+n)...160
ignored
Legend:
[Response Data
Length]
Length of the return data incl. OPDS byte (number of
bytes n)
8 bits
0x03
3 bytes (n=2)
0x05
5 bytes (n=4)
0x09
9 bytes (n=8)
0x11
17 bytes (n=16)
0x21
33 bytes (n=32)
[OPDS]
Output acyclic data Switch: signals whether cyclic or
acyclic process data is transmitted
8 bits
0x00
cyclic process data
0x01
acyclic process data
[Output Data
(Byte m)]
IO-Link output data (m = 1...n)
n*8 bits
per byte: 0x00...0xFF
Diagnostic codes:
0x01
OK
0x04
Blocked Port - another acyclic access is still active
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x0A
Wrong Block ID