IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
27
>
9.3.1
Example: Setting the gateway profile
51981
Task:
Each of the first two words of the input and output data of the IO-Link at the ports X01...X03 are to be
transmitted.
Solution:
•
Required ID1 code: 0x7
•
Mapping of the process data (details:
→
ID1 = 0x7
(
→
Add. Slave (n+4)
Add. Slave (n+3)
Add. Slave (n+2)
Add. Slave (n+1)
Basic Slave (n)
S-7.4.E
C
ha
nne
l 3
C
ha
nne
l 2
C
ha
nne
l 1
C
ha
nne
l 0
C
ha
nne
l 3
C
ha
nne
l 2
C
ha
nne
l 1
C
ha
nne
l 0
C
ha
nne
l 3
C
ha
nne
l 2
C
ha
nne
l 1
C
ha
nne
l 0
C
ha
nne
l 3
C
ha
nne
l 2
C
ha
nne
l 1
C
ha
nne
l 0
Port X01
1
0
1
0
→
Status-Informatio
nen
Port X02
1
0
1
0
Port X03
1
0
1
0
Port X04
1
0
1
0
green = input data
rot = output data
•
The following process data will be cyclically transmitted between IO-Link master and AS-i master:
Word 0 and 1 of the input and output data at port X01
Word 0 and 1 of the input and output data at port X02
Word 0 and 1 of the input and output data at Port X03
Word 0 and 1 of the input and output data at port X04 (remain unused)
•
Number of Additional AS-i slaves: 4
•
Valid address range for Basic AS-i slave: 1...27 (1 Basic AS-i slave + 4 Additional AS-i slaves = 5
consecutive AS-i addresses)