CAN in the ecomatmobile controller
Physical connection of CAN
8.3.4
Wire cross-sections
For the layout of the CAN network the wire cross-section of the bus cable used must also be taken into
account. The following table describes the dependence of the wire cross-section referred to the cable
length and the number of the connected nodes.
Cable length
[m]
Wire cross-section at
32 nodes
[mm
2
]
Wire cross-section at
64 nodes
[mm
2
]
Wire cross-section at
100 nodes
[mm
2
]
< 100
0.25
0.25
0.25
< 250
0.34
0.50
0.50
< 500
0.75
0.75
1.00
Depending on the EMC requirements the bus cables can be laid out as follows:
•
in
parallel,
•
as twisted pair
•
and/or
shielded.