Hangzhou IECHO Science & Technology Co., Ltd.
22
18
Rated speed limit
activated
Parameter
"rated speed" or
analog value
input is too high
Check the parameter "rated
speed", limit the rated value
"minimum speed" and
"maximum speed", adjust
the fixed frequency 1 to 4
22
10 V output voltage
output range
10V output
voltage AIN is
not acceptable
range (±3%)
Check the wiring, there may
be a short circuit
23
24 V output short circuit 24 V short circuit Check wiring
24
Error during parameter
import or export
No/bad SD card
or the
parameter file
on the SD card is
incomplete or
does not exist
Use a complete parameter
file (parameter import) and
a complete SD card
27
Generator running
The motor runs
on the inverter
and stops
Wait until the motor is
stationary
28
Comparator's own error
test
Internal fault
If the fault still exists after
the power is turned off and
on, send the inverter for
repair.
45
Watchdog reset control
on the motor
Strong EMC
interference of
motor control
board
Restart the motor
54
Brake chopper failure, or
interruption during
brake resistor self-test
Performance
component
failed
Switch twice. If the fault still
exists, send the inverter for
repair. The motor can still be
operated