9. Allgemeine Informationen
Installation instructions TERRA SWM
36
Heat source
K
a
pit
e
l 09
Connection plan
Technical data fl at collector
Type BSC
Unit
4
5
6
Number of pipe circuits
4
5
6
Total length of pipe
lfm
400
500
600
Surface area supplied
m²
320
400
480
Diameter of connection line
mm
40
40
40
Length of Distributor
mm
240
300
360
Brine mixture*
lt.
140
175
210
* Brine mixture (30% antifreeze concentration, excluding the content of the distributing main
Laying distance: app. 80 cm
Laying depth: 110-120 cm
Note:
- The pipes should be laid several months before
the heating period. The relevant preparation times
must be taken into account in the overall planning
work.
- Vegetation with deep roots must be avoided at all
costs.
- Rainwater should not be drained off via drainage as
it is required to regenerate the ground.
60mm
1 1/4”
Connection pipe to the
heat pump on site
PE-plastic pipe Ø 25mm
manifold length L
Fill- and flushing device
Supply
Mud trap
Stopcock
Return
- When back-
fi
lling, a signal band of approx. 0.5 m
should be laid above the pipeline to avoid subse-
quent damage. When the
fl
at collectors, the surface
area above must not be sealed off (e.g. asphalt).