(C) IDM ENERGIESYSTEME GMBH
9. Allgemeine Informationen
Installation instructions TERRA SWM
38
60 mm
1 1/4”
Connection pipe to the
heatpump on site
connection set
PE plastic pipe Ø 25 mm
manifold length L
Mud tap
Stopcock
Supply
Return
Fill- and flushing device
Heat source
K
a
pit
e
l 09
Installation plan
Notes
-
Only antifreeze approved by iDM Energiesysteme
GmbH are permitted for use.
-
Brine circuit lines must be
fi
tted with steam
diffusion-proofed insulation to protect against
condensation and ice formation (e.g. Arma
fl
ex).
-
Brine circuit pump and the brine expansion tank are
integrated in the TERRA SWM.
- When
fi
lling the brine circuit with antifreeze mixture,
the expansion vessel must be
fi
lled (due do the
volume reduction when cooling in service).
Design of the depth sensor
If the use of geothermal heat is in the closer selection, then obtain information about the soil conditions by a
geological report. You
fi
nd out more details on requirements related, the expected soil layers, as well as notes
about the maximum abstraction capacity.
The dimensioning of the depth sensors to achieve the necessary abstraction capacity must be occu-
red by the drilling company or a geologist. Drilling may be performed only by a licensed company!