background image

10

IMAX XTRA EL

 - 

Installation & Servicing

GENERAL

4  SEALED SYSTEM REQUIREMENTS

Working pressure 6 bar maximum.

Particular reference should be made to BS. 6644 and Guidance 

note PM5 "Automatically controlled steam and hot water boilers" 

published by the Health and Safety Executive.
The information and guidance given below is not intended to 

override any requirements of either of the above publications 

or the requirements of the local authority, gas or water 

undertakings.
In general commercial closed pressurised systems are provided 

with either manual or automatic water make up.

In both instances it will be necessary to fit automatic controls 

intended to protect the boiler, circulating system and ancillary 

equipment by shutting down the boiler plant if a potentially 

hazardous situation should arise.
Examples of such situations are low water level and operating 

pressure or excessive pressure within the system.  Depending 

on circumstances, controls will need to be either manual or 

automatic reset.  In the event of a shutdown both visual and 

audible alarms may be necessary.

Expansion vessels used must comply with BS. 4814 and must 

be sized on the basis of the total system volume and initial 

charge pressure.
Initial minimum charge pressure should not be less than         

1.0 bar (15psi) and must take account of the static head and 

specification of the pressurising equipment.  The maximum 

water temperatures permissible at the point of minimum 

pressure in the system are specified in BSEN 61508.

When make up water is not provided automatically it will be 

necessary to fit controls which shut down the plant in the event 

of the maximum system pressure approaching to within 0.35bar 

(5psi) of the safety valve setting.
Other British Standards applicable to commercial sealed 

systems are:
BS. 6880: Part 2
BS. 1212
BS. 6281: Part 1
BS. 6282: Part 1
BS. 6283: Part 4

3  VENTILATION

The ventilation requirements of these boilers are dependant 

on the type of flue system used, and their heat input.  All vents 

must be permanent with no means of closing, and positioned to 

avoid accidental obstructions by blocking or flooding.

Detailed reference should be made to BS. 6644 for inputs 

between 70kW and 1.8MW (net).  In IE refer to the current edition 

of I.S.820.  The following notes are for general guidance only:

Dust contamination in the combustion air may cause 

blockage of the burner slots.  Unless the boiler room 

provides a dust free environment then direct connection 

of the air intake via ducting to clean outside air should be 

used.

The temperature within a boiler room shall not exceed 25

o

within 100 mm of the floor, 32

o

C at mid height and 40

o

C within 

100 mm of the ceiling.

IMPORTANT NOTE.

If combustion air is drawn from within the boiler room, 

ensure no dust or airborne debris can be ingested into the 

appliance.  Dusty concrete flooring should be sealed to 

reduce the presence of dust.  Ideally where possible duct 

the air supply into the boiler room from a clean source 

outside the boiler room/building.

Open Flued Installations

If ventilation is to be provided by means of permanent high and 

low vents communicating direct with outside air, then reference 

can be made to the sizes below.  For other ventilation options 

refer to BS. 6644.  In IE refer to the current edition of I.S.820.

Required area (cm

2

) per kW of total rated input (net)

   

Boiler Room 

Enclosure

  Low level (inlet) 

10

  High level (outlet) 

5

Note: Where a boiler installation is to operate in summer months 

(e.g. DHW) additional ventilation requirements are stated, if 

operating for more than 50% of time (refer to BS6644).

IMPORTANT

If a sealed system is required please ensure a 

maximum flow temperature of 90ºC is not exceeded.

Содержание IMAX XTRA EL

Страница 1: ...fety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and main...

Страница 2: ...n kW 58 9 72 6 85 2 100 7 114 9 Boiler output condensing Mean 40o C Max kW 323 1 399 5 475 8 552 7 628 9 Min kW 66 7 80 5 95 6 113 0 127 6 Boiler Input Max Rate Net kW 304 8 376 2 447 6 519 0 590 0 Gr...

Страница 3: ...he room containing the boiler The combustion air is drawn directly from the room The fan is up stream of the combustion chamber C53 A room sealed appliance which is connected via its separate ducts to...

Страница 4: ...ers have been tested and certified by BSI to EN 15502 for use with Natural Gas Detailed recommendations are contained in the following Standards and Codes of Practice BS 5854 Flue and flue Structures...

Страница 5: ...possible duct the air supply into the boiler room from a clean source outside the boiler room building If the air filter accessory is fitted the 100Pa 10Pa pressure requirement must be checked at max...

Страница 6: ...1 SENTINEL X100 or CALMAG CM100 inhibitors and associated water treatment products which must be used in accordance with the manufacturers instructions In hard water areas where mains water can exceed...

Страница 7: ...7 25 10 1 168 3 24 11 7 195 0 24 13 3 221 7 24 Nominal ow 13 8 230 0 100 17 283 3 98 20 2 336 7 96 23 5 391 7 95 26 7 445 0 94 Nominal ow x1 5 20 7 345 0 225 25 5 425 0 221 30 3 505 0 216 35 2 586 7 2...

Страница 8: ...8 IMAX XTRA EL Installation Servicing GENERAL 1 BOILER DIMENSIONS AND CLEARANCES FRONT VIEW REAR VIEW SIDE VIEW ELECTRICAL CABLE OUTLETS All dimensions in mm unless otherwise stated...

Страница 9: ...CLEARANCES CONT D D C E B A Dimension A B C D E TOP Minimum 700 150 700 150 700 Recommended 1000 400 1000 400 1000 This clearance dimension applies independently of the installed flue system TOP VIEW...

Страница 10: ...ards applicable to commercial sealed systems are BS 6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 3 VENTILATION The ventilation requirements of these boilers are dependant on the ty...

Страница 11: ...f circulation in the system Systems designed to rise above the boiler flow tappings will automatically require a minimum static head higher than that shown 5 The position of the open vent safety pipe...

Страница 12: ...et Strapping 301 PCB 309 Ignition Electrode 310 Ionisation Electrode 311 Air Pressure Switch 315 Air Pressure Switch Kroms 316 Buttons Potentiometer Knob 317 Pod CUI 318 PCB CUI 401 Heat Engine Gasket...

Страница 13: ...ia crane hoist forklift truck or pallet truck If using pallet truck refer to diagram below 2 To remove the appliance from the pallet packaging and panels MUST be removed and stored safely 3 Remove the...

Страница 14: ...to the instructions supplied with the kit If the kit is not being fitted the 2 BSP branch must be capped off as shown in image 3 6 The flange joint is DN80 PN6 A suitable mating flange with bolts and...

Страница 15: ...ours without frost damage However if parts of the pipework run outside the building or if the boiler will be left off for more than a day or so then a frost thermostat should be wired into the system...

Страница 16: ...Wiring Regulations For Ireland reference should be made to the current ETCI rules for electrical installations For wiring external controls to the boiler reference should be made to the systems wiring...

Страница 17: ...6 SEQUENCER CONTROL OF MULTIPLE BOILERS In installations where the heat load is greater than the boiler capacity an ideal solution is to use multiple boiler arrangements The ideal way to control a mul...

Страница 18: ...Volt Free Relay contacts will close when the Burner is on 4 Only Ideal Outside Sensor and DHW Tank Sensor kits should be connected to the boiler 5 The External Interlock connection is only used in con...

Страница 19: ...MAINS SUPPLY PE MAINS SUPPLY N MAINS SUPPLY L DIVERTER VALVE L CH GAS VALVE PE DIVERTER VALVE L DHW GAS VALVE N PUMP PE PUMP N GAS VALVE L GAS VALVE N DIVERTER VALVE PE DIVERTER VALVE N FAN L IONISAT...

Страница 20: ...on setup Line 5 indicates Switched Live or OpenTherm or 0 10V depending on which controls are connected to the boiler Hot Water DHW Switched Live On Burner On DHW Thermostat Flow Temp 80 C Domestic H...

Страница 21: ...Frame 25 for adjusting the system frost protection temperature setpoint Cylinder Frost Protect Burner Power 100 Outside Temp 10 C Frost Setpoint 5 C Hot Water Temp 4 C Cylinder Frost Protection Mode...

Страница 22: ...ti clockwise until Normal Operation is highlighted again and press SELECT to return to normal operation Ideal imax XL 320 kW Normal Operation Set Flow Temp Set DHW Temp Press SELECT and a screen simil...

Страница 23: ...vary as the boiler operates Press SELECT to exit this option Rotate the KNOB anti clockwise until Normal Operation is highlighted again and press SELECT to return to normal operation VIEWING THE FAUL...

Страница 24: ...to 0 10V Input 0 10V Off 0 10V Capacity 0 10V Temperature Press and to change to the required setting and then press ENTER to store Rotate the KNOB anti clockwise until Normal Operation is highlighted...

Страница 25: ...et Night Setback DHW Pump Valve Set Booster Press SELECT and the following screen will be displayed Set Night Setback On Off Press and to change to required setting and then press ENTER to store Rotat...

Страница 26: ...ion Function is only operational if an Outside Sensor has been connected The CH pump is switched on if the Outside Temp is less than the System Frost Protection Temp The CH pump is switched off if the...

Страница 27: ...o the DHW Thermistor input Rotate the KNOB clockwise until the following screen is displayed Rotate the KNOB clockwise until the following screen is displayed Installer Mode O S Room Temp DHW Sensor F...

Страница 28: ...the following screen is displayed Installer Mode DHW Sensor Factory Settings Anti Legion Temp Anti Legion Enable Press SELECT and the following screen will be displayed Factory Settings Reset Press E...

Страница 29: ...with the external relay then powering the pump 0 10 0 10 DHW DHW OWC OWC OT OT PWM GND INT INT LOCKOUT LOCKOUT BURNER ON BURNER ON N L NO L NC N L L N LIVE OUT CH CALL LIVE OUT DHW CH2 CALL HEAT DEMAN...

Страница 30: ...ng instructions 7 The boiler will commence the ignition sequence If after 5 attempts the boiler has failed to light then it will lock out Press the reset button to restart the ignition sequence 8 Fit...

Страница 31: ...me detected Demand On Temp Set point Anti cycle done Fan On 10s Fan Pre purge Pump On Fan on Spark Generator On Gas Valve On 5s Ignition Period Burner Output controlled relative to Heat Demand by vary...

Страница 32: ...the case may be responds 2 Water circulation system a With the system HOT examine all water connections for soundness b With the system still HOT turn off the gas water and electricity supplies to th...

Страница 33: ...Light the boiler and carry out function checks noting any operational faults 2 Run the boiler for 10 minutes and then check the gas consumption rate Refer to procedure opposite on how to force the bur...

Страница 34: ...o front side panels have noise dampening insulation fitted SERVICING 37 REMOVAL OF BURNER MANIFOLD 1 Refer to Frames 34 36 2 Remove the four nuts securing the burner hood elbow to the heat exchanger 3...

Страница 35: ...howing signs of damage it must be replaced 5 Re assemble in reverse order replacing any seals gaskets which show signs of wear When refitting ensure the burner is correctly engaged so the burner flang...

Страница 36: ...ly insert the probe assembly engaging the securing stud 5 Replace the two nuts and tighten Re connect the earth lead and the spark generator lead IONISATION PROBE 6 Disconnect the wire from the ionisa...

Страница 37: ...secure with the 8 bolts 42 CLEANING CONDENSATE TRAP 1 Refer to Frame 34 2 Unscrew the top fitting of the condensate trap 3 Unscrew the fitting at the flue outlet drain point 4 Unscrew the condensate o...

Страница 38: ...e assembly forward on the interface plate 7 Remove the three nuts retaining the gas valve assembly to the fan scroll and remove the gas valve assembly taking care due to the weight of the gas valve 8...

Страница 39: ...HERMISTOR X3 REPLACEMENT 1 Refer to Frames 34 36 2 Disconnect the 2 wires from each thermistor 3 Using a suitable sized spanner on the hexagon undo the thermistor and remove 4 Refit in reverse order u...

Страница 40: ...t of the control pod 4 Refit in reverse order 47 BOILER CONTROL PCB REPLACEMENT 1 Refer to Frames 34 36 2 Remove all PCB electrical connections 3 Remove the PCB carefully by pulling gently towards you...

Страница 41: ...Position the flexible duct over the air inlet and secure with the hose clip 7 Postion the flexible duct over the fan inlet and secure with the hose clip 3 2 Air inlet 1 Refer to Frame 34 2 Unscrew the...

Страница 42: ...route back to the control box 5 Remove the connectors from the PCB 6 Remove the three bottom connectors on LHS of control box 7 Remove the earth post nut and release the earth connections 8 Feed the...

Страница 43: ...S connectors 9 Feed the harness back to the components listed above using the retaining clips and connect 2 3 4 GAS VALVE Whirl Wind Mixer FAN Heat Exchanger Sump Air Pressure Switches APS 1 Refer to...

Страница 44: ...ersed Cylinder Thermistor Fault Check Cylinder Thermistor Wiring Check Cylinder Thmr 10K 25 C 2K at 66 C Go to Frame 64 CylinderThermistor Fault Ext Interlock Off External Interlock Operated Reset Int...

Страница 45: ...continuity visual condition and position refer to Frame 42 Check if the condensate pipe is blocked yes no Is the dynamic gas pressure available at the boiler 15mbar Check gas supply and rectify fault...

Страница 46: ...ure wiring has continuity and is securely connected no Does the black wire from the Water Pressure Switch to the PCB have continuity and is it securely connected Check syphon and condensate drain Pipe...

Страница 47: ...therwise replace the main PCB no yes Check Spark Generator and associated Harness for continuity visual condition and position refer to Frame 46 Are these functioning correctly Replace Spark Generator...

Страница 48: ...ce main PCB no yes Is there continuity between the PCB and the thermistor 62 OUTSIDE SENSOR FAULT Fit a new Outside Sensor no Disconnect the wires to the Outside Sensor Check the resistance using a su...

Страница 49: ...linder thermistor wiring between the boiler terminal strip and the PCB have continuity and is it securely connected Replace main PCB Change menu setting for DHW Sensor to Switched Live See Frame 26 no...

Страница 50: ...30Vac at A There is no voltage from the external controls This is not a boiler fault Ensure voltage is supplied to the boiler by correcting external wiring no yes Is there 230Vac at B Check wiring fro...

Страница 51: ...l wiring Rectify wiring from boiler to OpenTherm device no yes Does the system have a DHW Pump or Power Open Diverter Valve Is the system correctly set for a Power Closed Diverter Valve no no Set boil...

Страница 52: ...PCB to user interface PCB no Does the cable from the main PCB to the user interface PCB have continuity and is it un damaged yes yes Replace main PCB yes Replace the user interface PCB still no displ...

Страница 53: ...es Ensure between 2V and 10V is correctly connected to these terminals from the external device no Is a voltage of between 2V and 10V being supplied to F with positive and negative connected correctly...

Страница 54: ...thorised by Ideal Failure to do so could affect safety or performance of this appliance Comprehensive spares parts information and details of approved Ideal Parts Distributors are available on www ide...

Страница 55: ...iler firing mbar Gas manifold pressure dynamic all boiler firing mbar Burner pressure if required mbar Gas rate kW hr Detection Electrode A Flue gas temperature gross C Ambient temperature C O 2 CO 2...

Страница 56: ...Inlet Pressure dynamic 1 Boiler mbar Gas Inlet Pressure dynamic all Boilers mbar CO2 CO CO2 Ratio Control Stat Setting C Temp Diff C Burner Pressure if applicable mbar Flue Gas Temp C Ambient Temp C...

Страница 57: ...Inlet Pressure dynamic 1 Boiler mbar Gas Inlet Pressure dynamic all Boilers mbar CO2 CO CO2 Ratio Control Stat Setting C Temp Diff C Burner Pressure if applicable mbar Flue Gas Temp C Ambient Temp C...

Страница 58: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...

Отзывы: