IDEAL IMAX XTRA EL Скачать руководство пользователя страница 5

5

IMAX XTRA EL

 - 

Installation & Servicing

GENERAL

FLUE INSTALLATION

IMPORTANT.

  It is the responsibility of the installer to ensure, 

in practice, that products of combustion discharging from the 

terminal cannot re-enter the building or any other adjacent 

building through ventilators, windows, doors, other sources of 

natural air infiltration, or forced ventilation / air conditioning.

If this should occur the appliance MUST be isolated from the gas 

supply and labelled as 'unsafe' until corrective action can be taken.

Terminal Position

Due to the high efficiency of the boilers pluming will occur.  

Vertical termination is recommended and terminal positions which 

could cause problems should be avoided.  Particular care should 

be taken in the case of large output boiler installations, and 

complying with the requirements of the Clean Air Act.

The flue must be installed in accordance with the appropriate 

Building Regulations and standards listed on page 4 and in 

compliance with BS6644.  In IE refer to I.S.820:2000.

FLUE SYSTEM DESIGN

Due to the high efficiency of these boilers, the flue gas 

temperatures are low and the buoyancy in the stack will be 

relatively small.  The boiler is supplied with an integral fan which 

is fully matched to the boiler in each case to provide correct 

combustion air flow and overcome the flue resistance.

The power of this fan is such that there is a large reserve of 

pressure available to overcome a significant length of flue without 

affecting the combustion performance of the boiler.  The maximum 

& minumum pressure available measured at the base of the flue 

to overcome combined flue and air resistance is 100Pa (max) and 

-10Pa (min)  for all model sizes.  The pressure should be checked 

at maximum heat input to ensure this maximum pressure is not 

exceeded.  Care should be taken with tall flue systems to ensure 

excess buoyancy is not created.  A negative pressure must not be 

created at the boiler flue outlet.

/

Boiler Size

320

395

470

545

620

Flue Pressure (max)     Pa

100

Flue Pressure (min)      Pa

-10

The addition of elbows and their positions in the flue and the 

terminal will have a significant effect on the maximum flue length.  

Consult with your flue supplier for detailed design work.

IMPORTANT NOTE.  

 

If combustion air is drawn from within the boiler room, ensure 

no dust or airborne debris can be ingested into the appliance.  

Dusty concrete flooring should be sealed to reduce the 

presence of dust.  Ideally where possible duct the air supply 

into the boiler room from a clean source outside the boiler 

room/building.

If the air filter accessory is fitted the 100Pa / -10Pa pressure requirement 

must be checked at maximum heat input with the filter fitted.

Material

With no requirement for buoyancy to discharge flue products 

and with low flue gas temperatures, single wall flues are suitable 

for most installations.  Care should still be taken to maintain 

compliance with building regulations and relevant standards.

Care should also be taken in the selection of flue terminals as 

these tend to accentuate the formation of a plume and could freeze 

in cold weather conditions.

Care should be taken to ensure the specification of the chimney 

is suitable for the application by reference to the manufacturer's 

literature.  

WATER CIRCULATION SYSTEM

The boiler is suitable for connection to a sealed heating system or an 

open vented system.
A circulation pump MUST be connected to the boiler, see below.
The boiler must NOT be used for direct hot water supply.  The hot 

water storage cylinder MUST be of the indirect type.
Single feed, indirect cylinders are not recommended and MUST 

NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor are 

they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of 

the useful heating surface, should be lagged to prevent heat loss 

and any possible freezing - particularly where pipes run through 

roof spaces and ventilated underfloor spaces.

The boiler must be vented.  There must be no low points between 

the boiler flow connection and a system vent point, which should be 

positioned as close as practically possible to the boiler flow connection.

Draining taps MUST be located in accessible positions, which 

permit the draining of the whole system - including the boiler 

and hot water storage vessel.  They should be at least 1/2" BSP 

nominal size and be in accordance with BS. 2879.  Do not use the 

boiler drain tap to drain the system as this can induce sludge into 

the heat exchanger.
The central heating system should be in accordance with the 

relevant standards listed on page 4.
Once the burner has extinguished the boiler requires a 2 minute 

pump overrun to dissipate the residual heat.  In order to allow this 

a 2 minute pump overrun is incorporated into the boiler control.
An external pump must be connected or controlled by the boiler, 

however if it is directly connected it must not exceed 1.3A inductive 

load, if it does then a relay or contactor must be used.

Flue Products/Flue Pressure

Sampling

Point

Содержание IMAX XTRA EL

Страница 1: ...fety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and main...

Страница 2: ...n kW 58 9 72 6 85 2 100 7 114 9 Boiler output condensing Mean 40o C Max kW 323 1 399 5 475 8 552 7 628 9 Min kW 66 7 80 5 95 6 113 0 127 6 Boiler Input Max Rate Net kW 304 8 376 2 447 6 519 0 590 0 Gr...

Страница 3: ...he room containing the boiler The combustion air is drawn directly from the room The fan is up stream of the combustion chamber C53 A room sealed appliance which is connected via its separate ducts to...

Страница 4: ...ers have been tested and certified by BSI to EN 15502 for use with Natural Gas Detailed recommendations are contained in the following Standards and Codes of Practice BS 5854 Flue and flue Structures...

Страница 5: ...possible duct the air supply into the boiler room from a clean source outside the boiler room building If the air filter accessory is fitted the 100Pa 10Pa pressure requirement must be checked at max...

Страница 6: ...1 SENTINEL X100 or CALMAG CM100 inhibitors and associated water treatment products which must be used in accordance with the manufacturers instructions In hard water areas where mains water can exceed...

Страница 7: ...7 25 10 1 168 3 24 11 7 195 0 24 13 3 221 7 24 Nominal ow 13 8 230 0 100 17 283 3 98 20 2 336 7 96 23 5 391 7 95 26 7 445 0 94 Nominal ow x1 5 20 7 345 0 225 25 5 425 0 221 30 3 505 0 216 35 2 586 7 2...

Страница 8: ...8 IMAX XTRA EL Installation Servicing GENERAL 1 BOILER DIMENSIONS AND CLEARANCES FRONT VIEW REAR VIEW SIDE VIEW ELECTRICAL CABLE OUTLETS All dimensions in mm unless otherwise stated...

Страница 9: ...CLEARANCES CONT D D C E B A Dimension A B C D E TOP Minimum 700 150 700 150 700 Recommended 1000 400 1000 400 1000 This clearance dimension applies independently of the installed flue system TOP VIEW...

Страница 10: ...ards applicable to commercial sealed systems are BS 6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 3 VENTILATION The ventilation requirements of these boilers are dependant on the ty...

Страница 11: ...f circulation in the system Systems designed to rise above the boiler flow tappings will automatically require a minimum static head higher than that shown 5 The position of the open vent safety pipe...

Страница 12: ...et Strapping 301 PCB 309 Ignition Electrode 310 Ionisation Electrode 311 Air Pressure Switch 315 Air Pressure Switch Kroms 316 Buttons Potentiometer Knob 317 Pod CUI 318 PCB CUI 401 Heat Engine Gasket...

Страница 13: ...ia crane hoist forklift truck or pallet truck If using pallet truck refer to diagram below 2 To remove the appliance from the pallet packaging and panels MUST be removed and stored safely 3 Remove the...

Страница 14: ...to the instructions supplied with the kit If the kit is not being fitted the 2 BSP branch must be capped off as shown in image 3 6 The flange joint is DN80 PN6 A suitable mating flange with bolts and...

Страница 15: ...ours without frost damage However if parts of the pipework run outside the building or if the boiler will be left off for more than a day or so then a frost thermostat should be wired into the system...

Страница 16: ...Wiring Regulations For Ireland reference should be made to the current ETCI rules for electrical installations For wiring external controls to the boiler reference should be made to the systems wiring...

Страница 17: ...6 SEQUENCER CONTROL OF MULTIPLE BOILERS In installations where the heat load is greater than the boiler capacity an ideal solution is to use multiple boiler arrangements The ideal way to control a mul...

Страница 18: ...Volt Free Relay contacts will close when the Burner is on 4 Only Ideal Outside Sensor and DHW Tank Sensor kits should be connected to the boiler 5 The External Interlock connection is only used in con...

Страница 19: ...MAINS SUPPLY PE MAINS SUPPLY N MAINS SUPPLY L DIVERTER VALVE L CH GAS VALVE PE DIVERTER VALVE L DHW GAS VALVE N PUMP PE PUMP N GAS VALVE L GAS VALVE N DIVERTER VALVE PE DIVERTER VALVE N FAN L IONISAT...

Страница 20: ...on setup Line 5 indicates Switched Live or OpenTherm or 0 10V depending on which controls are connected to the boiler Hot Water DHW Switched Live On Burner On DHW Thermostat Flow Temp 80 C Domestic H...

Страница 21: ...Frame 25 for adjusting the system frost protection temperature setpoint Cylinder Frost Protect Burner Power 100 Outside Temp 10 C Frost Setpoint 5 C Hot Water Temp 4 C Cylinder Frost Protection Mode...

Страница 22: ...ti clockwise until Normal Operation is highlighted again and press SELECT to return to normal operation Ideal imax XL 320 kW Normal Operation Set Flow Temp Set DHW Temp Press SELECT and a screen simil...

Страница 23: ...vary as the boiler operates Press SELECT to exit this option Rotate the KNOB anti clockwise until Normal Operation is highlighted again and press SELECT to return to normal operation VIEWING THE FAUL...

Страница 24: ...to 0 10V Input 0 10V Off 0 10V Capacity 0 10V Temperature Press and to change to the required setting and then press ENTER to store Rotate the KNOB anti clockwise until Normal Operation is highlighted...

Страница 25: ...et Night Setback DHW Pump Valve Set Booster Press SELECT and the following screen will be displayed Set Night Setback On Off Press and to change to required setting and then press ENTER to store Rotat...

Страница 26: ...ion Function is only operational if an Outside Sensor has been connected The CH pump is switched on if the Outside Temp is less than the System Frost Protection Temp The CH pump is switched off if the...

Страница 27: ...o the DHW Thermistor input Rotate the KNOB clockwise until the following screen is displayed Rotate the KNOB clockwise until the following screen is displayed Installer Mode O S Room Temp DHW Sensor F...

Страница 28: ...the following screen is displayed Installer Mode DHW Sensor Factory Settings Anti Legion Temp Anti Legion Enable Press SELECT and the following screen will be displayed Factory Settings Reset Press E...

Страница 29: ...with the external relay then powering the pump 0 10 0 10 DHW DHW OWC OWC OT OT PWM GND INT INT LOCKOUT LOCKOUT BURNER ON BURNER ON N L NO L NC N L L N LIVE OUT CH CALL LIVE OUT DHW CH2 CALL HEAT DEMAN...

Страница 30: ...ng instructions 7 The boiler will commence the ignition sequence If after 5 attempts the boiler has failed to light then it will lock out Press the reset button to restart the ignition sequence 8 Fit...

Страница 31: ...me detected Demand On Temp Set point Anti cycle done Fan On 10s Fan Pre purge Pump On Fan on Spark Generator On Gas Valve On 5s Ignition Period Burner Output controlled relative to Heat Demand by vary...

Страница 32: ...the case may be responds 2 Water circulation system a With the system HOT examine all water connections for soundness b With the system still HOT turn off the gas water and electricity supplies to th...

Страница 33: ...Light the boiler and carry out function checks noting any operational faults 2 Run the boiler for 10 minutes and then check the gas consumption rate Refer to procedure opposite on how to force the bur...

Страница 34: ...o front side panels have noise dampening insulation fitted SERVICING 37 REMOVAL OF BURNER MANIFOLD 1 Refer to Frames 34 36 2 Remove the four nuts securing the burner hood elbow to the heat exchanger 3...

Страница 35: ...howing signs of damage it must be replaced 5 Re assemble in reverse order replacing any seals gaskets which show signs of wear When refitting ensure the burner is correctly engaged so the burner flang...

Страница 36: ...ly insert the probe assembly engaging the securing stud 5 Replace the two nuts and tighten Re connect the earth lead and the spark generator lead IONISATION PROBE 6 Disconnect the wire from the ionisa...

Страница 37: ...secure with the 8 bolts 42 CLEANING CONDENSATE TRAP 1 Refer to Frame 34 2 Unscrew the top fitting of the condensate trap 3 Unscrew the fitting at the flue outlet drain point 4 Unscrew the condensate o...

Страница 38: ...e assembly forward on the interface plate 7 Remove the three nuts retaining the gas valve assembly to the fan scroll and remove the gas valve assembly taking care due to the weight of the gas valve 8...

Страница 39: ...HERMISTOR X3 REPLACEMENT 1 Refer to Frames 34 36 2 Disconnect the 2 wires from each thermistor 3 Using a suitable sized spanner on the hexagon undo the thermistor and remove 4 Refit in reverse order u...

Страница 40: ...t of the control pod 4 Refit in reverse order 47 BOILER CONTROL PCB REPLACEMENT 1 Refer to Frames 34 36 2 Remove all PCB electrical connections 3 Remove the PCB carefully by pulling gently towards you...

Страница 41: ...Position the flexible duct over the air inlet and secure with the hose clip 7 Postion the flexible duct over the fan inlet and secure with the hose clip 3 2 Air inlet 1 Refer to Frame 34 2 Unscrew the...

Страница 42: ...route back to the control box 5 Remove the connectors from the PCB 6 Remove the three bottom connectors on LHS of control box 7 Remove the earth post nut and release the earth connections 8 Feed the...

Страница 43: ...S connectors 9 Feed the harness back to the components listed above using the retaining clips and connect 2 3 4 GAS VALVE Whirl Wind Mixer FAN Heat Exchanger Sump Air Pressure Switches APS 1 Refer to...

Страница 44: ...ersed Cylinder Thermistor Fault Check Cylinder Thermistor Wiring Check Cylinder Thmr 10K 25 C 2K at 66 C Go to Frame 64 CylinderThermistor Fault Ext Interlock Off External Interlock Operated Reset Int...

Страница 45: ...continuity visual condition and position refer to Frame 42 Check if the condensate pipe is blocked yes no Is the dynamic gas pressure available at the boiler 15mbar Check gas supply and rectify fault...

Страница 46: ...ure wiring has continuity and is securely connected no Does the black wire from the Water Pressure Switch to the PCB have continuity and is it securely connected Check syphon and condensate drain Pipe...

Страница 47: ...therwise replace the main PCB no yes Check Spark Generator and associated Harness for continuity visual condition and position refer to Frame 46 Are these functioning correctly Replace Spark Generator...

Страница 48: ...ce main PCB no yes Is there continuity between the PCB and the thermistor 62 OUTSIDE SENSOR FAULT Fit a new Outside Sensor no Disconnect the wires to the Outside Sensor Check the resistance using a su...

Страница 49: ...linder thermistor wiring between the boiler terminal strip and the PCB have continuity and is it securely connected Replace main PCB Change menu setting for DHW Sensor to Switched Live See Frame 26 no...

Страница 50: ...30Vac at A There is no voltage from the external controls This is not a boiler fault Ensure voltage is supplied to the boiler by correcting external wiring no yes Is there 230Vac at B Check wiring fro...

Страница 51: ...l wiring Rectify wiring from boiler to OpenTherm device no yes Does the system have a DHW Pump or Power Open Diverter Valve Is the system correctly set for a Power Closed Diverter Valve no no Set boil...

Страница 52: ...PCB to user interface PCB no Does the cable from the main PCB to the user interface PCB have continuity and is it un damaged yes yes Replace main PCB yes Replace the user interface PCB still no displ...

Страница 53: ...es Ensure between 2V and 10V is correctly connected to these terminals from the external device no Is a voltage of between 2V and 10V being supplied to F with positive and negative connected correctly...

Страница 54: ...thorised by Ideal Failure to do so could affect safety or performance of this appliance Comprehensive spares parts information and details of approved Ideal Parts Distributors are available on www ide...

Страница 55: ...iler firing mbar Gas manifold pressure dynamic all boiler firing mbar Burner pressure if required mbar Gas rate kW hr Detection Electrode A Flue gas temperature gross C Ambient temperature C O 2 CO 2...

Страница 56: ...Inlet Pressure dynamic 1 Boiler mbar Gas Inlet Pressure dynamic all Boilers mbar CO2 CO CO2 Ratio Control Stat Setting C Temp Diff C Burner Pressure if applicable mbar Flue Gas Temp C Ambient Temp C...

Страница 57: ...Inlet Pressure dynamic 1 Boiler mbar Gas Inlet Pressure dynamic all Boilers mbar CO2 CO CO2 Ratio Control Stat Setting C Temp Diff C Burner Pressure if applicable mbar Flue Gas Temp C Ambient Temp C...

Страница 58: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...

Отзывы: