41 INSPECTING & CLEANING THE SUMP
1. Refer to Frame 34 & 36.
2. Remove the inspection cover which is
secured with eight bolts.
3.
Remove any debris and flush with
water if necessary.
4.
To re-fit the sump inspection panel
inspect the o-ring seal for damage
and replace if necessary.
5. Align the sump inspection cover and
secure with the 8 bolts.
42 CLEANING CONDENSATE TRAP
1. Refer to Frame 34.
2.
Unscrew the top fitting of the condensate
trap.
3.
Unscrew the fitting at the flue outlet drain
point.
4.
Unscrew the condensate outlet fitting.
5. Unscrew bracket and remove trap
6. Unscrew the base of the trap and drain into
a bucket.
7.
Remove all debris, flushing with water if
necessary.
8.
Re-fit the base of the trap.
9.
Re-fit in reverse order.
10.
Pour water into the flue sample point to
ensure the condense trap is re-filled before
the unit is operated after servicing.