55
idealheating.com
54
welcome to our ideology
CONDENSATE PUMPS
The condensate pump is designed to collect and remove condensate and can be
used with high effi ciency condensing boilers.
TECHNICAL INFORMATION
Maximum fl ow rate
440 litres/hour
Electrical supply
230V AC / 50-60 Hz 0.8amps
Alarm contact
NC 4 Amps resistive
Overheat protection
130˚C
Tank Capacity
2.0 Litres
Maximum vertical head
4.5m
Maximum horizontal length
30m
IDEAL COMMERCIAL BOILERS - CONDENSATE PUMP COMPATIBILITY
BOILER
COMPATIBLE
EVOMAX 2 - 30 - 150kW
IMAX XTRA 2 - 80 - 280kW
IMAX XTRA EL - 320 - 1240kW
EVOMOD - 250 - 1000kW
EVOJET - 150 - 1450kW
TERMINATION TO DRAIN / GULLEY
SEE INSTALLATION MANUAL FOR FULL INSTRUCTIONS
AND SYSTEM OPTIONS
TYPICAL CONDENSATE SYSTEM
55
idealheating.com