SUGGESTED ENGINEERING SPECIFICATION

OVERVIEW

 

The boilers must be fully automatically controlled, wall 
mounted, fanned, super-efficient condensing appliances 
utilising an aluminium silicon alloy heat exchanger and be 
suitable for connection to fully pumped open vented or 
sealed water systems.      

CONTROLS

The condensing boilers must have connectivity for all 
common types of BMS integration including 0-10v, volt free 
and OpenTherm connections. Additional modules may 
be used for BACnet, LONWorks and MODBus gateways. 
Where no BMS is present a modulating sequencer must be 
available.
The boiler must be fully modulating with a 5:1 turndown ratio 
and include control features enabling set point adjustment, 
heating circuit control of one constant temperature and one 
DHW circuit or 2 constant temperature circuits, and safety 
lock out parameters including fault diagnosis for both boiler 
and external components such as sensors or pumps. 
Boiler capabilities must include, with the use of 
external components, frost protection, weather or room 
compensation and system pump control. 

FLUE 

The condensing boilers must be suitable for use with a room 
sealed flue or open flue applications including C13, C33 and 
B23 classifications. The combined flue outlet and air inlet 
must be situated on the top of the boiler. 

HYDRAULIC

The condensing boiler must be and be suitable for 
connection to fully pumped open vented or sealed water 
systems. All hydraulic connections including flow return and 
condensate drain must be located on the bottom of the 
boiler. Hydraulic connections must be uniform across the 
outputs available in the range to ensure ease of installation 
and maintenance in mixed output cascades. The boiler must 
have a maximum operating pressure of 6 bar and be suitable 
for heating and indirect hot water systems. 

DIMENSIONS

 

The condensing boiler range must have a universal compact 
width and height across the range to ensure mixed output 
cascades maintain the same universal configuration. 
Maximum permitted wall area of 0.43m

²

MOUNTING

The condensing boilers can be installed either on the wall or 
into a prefabricated floor mounted frame. Wall brackets must 
be located at the top of the boiler and visible from the front 
to aid installation.

EFFICIENCY

The condensing boilers are capable of high seasonal 
efficiencies with a minimum requirement of 96.2% and low 
NOx emissions no greater than 39.8mg/kWH for natural gas 
and 80mg/kWH for LPG. 
30, 40 and 60kW models must have a Seasonal Space 
Heating Energy Efficiency of A. 

APPROVALS

The boiler must be tested and certified to EN 483, EN 677, 
PREN 15420, BS EN 15502, BS EN 656, BS EN 55014-1 and BS 
EN 55014-2 for use with Natural Gas. Boilers are certified to 
meet the requirements of the EC Gas Appliance Directive, 
Boiler Efficiency Directive, EMC and Low Voltage Directive.
The manufacturer must be ISO 9001 accredited.

SPECIFICATION

• 

 The 30kW boiler will be capable of flow rates for common 
systems using either 11°C, 15°C, 20°C or 25°C temperature 
differentials.

• The 40, 60 and 80kW boiler will be capable of flow rates for  
   common systems using either 11°C, 15°C, 20°C, 25°C or 30°C  
   temperature differentials.
• The 100kW boiler will be capable of flow rates for common  
   systems using either 15°C, 20°C, 25°C or 30°C temperature  
   differentials.
• The 120 and 150kW boiler will be capable of flow rates  
   for common systems using either 20°C, 25°C or 30°C  
   temperature differentials.

SOURCING

The condensing boiler must be manufactured or finally 
assembled in the United Kingdom.

CASCADE

The boiler must be configurable up to 6 boilers (max 900kW) 
in cascade using a prefabricated frame and header kit. 

WARRANTY

The boiler must be available with a 5 year warranty. 

The Suggested Engineering Specification 
is wording designed for specifiers to copy 
and paste into their specifications to ensure 
inclusion of Ideal Heating commercial boilers.

SYSTEM TEMPERATURE DIFFERENTIALS

Flow rates for common systems using either 11

°

C, 15

°

C, 20

°

C, 25

°

C or 30

°

C temperature differentials 

are given in the table below.

FLOW RATE (L/MIN)

HYDRAULIC RESISTANCE (MBAR)

BOILER

11°C

15°C

20°C

25°C

30°C

11°C

15°C

20°C

25°C

30°C

Evomax 2 30 / 30P

39.1

28.7

21.5

17.9

N/A

425

225

127

89

N/A

Evomax 2 40 / 40P

52.1

38.2

28.7

23.9

19.1

875

405

225

163

100

Evomax 2 60 / 60P

78.2

57.3

43.0

35.9

28.7

435

180

83

57

30

Evomax 2 80 / 80P

104.2

76.4

57.3

47.8

38.2

750

420

180

125

70

Evomax 2 100 / 100P

N/A

95.6

71.7

59.8

47.8

N/A

315

134

97

60

Evomax 2 120 / 120P

N/A

N/A

86.0

71.7

57.3

N/A

N/A

218

149

80

Evomax 2 150 

N/A

N/A

107.5

89.6

71.7

N/A

N/A

230

158

85

   

• 30kW boilers must operate with temperature differentials from 11°C to 25°C.
• 40, 60 and 80kW boilers must operate with temperature differentials from 11°C to 30°C.
• 100kW boilers must operate with temperature differentials from 15°C to 30°C.
• 120 and 150kW boilers must operate with temperature differentials from 20°C to 30°C.

FLUE SYSTEMS 

A comprehensive range of flue kits are available from  
Ideal Heating including horizontal and vertical concentric and 
open flue options. 

For horizontal flues: this is the distance from the flue outlet 
centre line on the boiler to the outside wall.

For vertical flue: this is the distance from the top of the boiler 
case to the aperture in the weather collar. If elbows are to 
be used, then the equivalent length of that fitting must be 
subtracted from the maximum flue extensions allowed for that 
flue option.

Note: Horizontal terminal resistance includes 1 x 90° elbow.

When installing Evomax 2 boilers with concentric flue 
(horizontally or vertically) the Ideal commercial flue system 
must be used.

The resistance of flue components, together with the 
maximum flue resistance each boiler can work against, may 
be used to calculate the total flue resistance of the system, 
and to determine if they are acceptable to run on the boiler.
Multiple boilers may be installed with a common  
flue header.

The flue system should be designed and supplied by a 
specialist flue company. BS 6644 and IGEM UP10 provide 
guidance on design and the drainage of condensate from flue 
stack and headers. Condensate from a flue stack and header 
must be collected and drained before entering  
the boiler.

For Ventilation requirements, please refer to the 
Installation Manual.

CONTROL KITS

VARICAN MODULE MASTER & SLAVE KITS 

 

Enables cascade control from Evomax 2 boiler controls.

EXTENSION MODULE KIT 

 

 

Capable of managing 2 mixing circuits. Multiple 
modules can be used.

OPENTHERM ROOM CONTROL KIT 

Timed control of central heating via OPENTHERM.

ROOM SENSOR KIT 

Used with Extension Module Kit for CH control

TANK SENSOR KIT 

Provides DHW temperature control. Also for use with 
Extension Module Kit.

OUTSIDE SENSOR KIT 

Provides weather compensation directly or with 
Extension Module Kit.

HEADER FLOW TANK IMMERSION SENSOR KIT  

Ensures boiler provides correct temperature to water in 
header via immersed sensor

HEADER FLOW TANK STRAP ON SENSOR KIT   

Ensures boiler provides correct temperature to water in 
header via external sensor

SAFETY INTERLOCK KIT 

 

 

 

Provides boiler shut down via an external signal.

Содержание EVOMAX 2

Страница 1: ...EVOMAX 2 CONDENSING BOILER Terms and conditions text in 6pt white montserrat light Commercial Industrial Heating Product of the Year 2020 PRODUCT FLUE GUIDE ...

Страница 2: ...e Ideal Heating Eye app uses the latest Augmented Reality technology to project accurately scaled 3D renders into your surroundings The app is available for both Apple and Android devices just search Ideal Heating Eye Over the coming pages the icon below shows which boilers are featured in the app BRING BOILERS TO LIFE DOWNLOAD THE APP 2 Introduction 4 11 Evomax 2 30 150kW 12 31 Evomax 2 Cascade 3...

Страница 3: ... 5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 5 DOWNLOAD THE APP Commercial Industrial Heating Product of the Year 2020 ...

Страница 4: ... 5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com Wall Hung BIM NOx Class 6 Flueing options Cascade control 5 A A A A B C D A Applies to Evomax 2 30 40 and 60kW models only 1 3 4 5 7 6 8 9 10 2 BOILER ASSEMBLY KEY 1 Auto Air Vent 2 Burner Fixings 3 Fan 4 Gas ...

Страница 5: ... 7 Gas Rate Max rate m hr 1 26 1 69 2 53 3 41 4 35 5 23 Flue Gas Flow Rate Max Rate m hr 44 09 61 68 88 66 121 57 153 60 183 81 COЇ 0 5 Max Rate 10 9 11 2 11 4 11 4 10 8 11 2 Min Rate 10 3 9 7 10 2 10 8 10 1 10 1 NOx with OЇ 0 gross BS EN 15502 1 Weighted mg kWh 52 3 64 4 67 7 63 2 65 3 41 6 Efficiency Seasonal 97 2 96 7 96 9 97 7 96 7 96 6 SEDBUK 2009 90 6 90 3 90 5 n a n a n a Operating Temperatu...

Страница 6: ...ature differentials SOURCING The condensing boiler must be manufactured or finally assembled in the United Kingdom CASCADE The boiler must be configurable up to 6 boilers max 900kW in cascade using a prefabricated frame and header kit WARRANTY The boiler must be available with a 5 year warranty The Suggested Engineering Specification is wording designed for specifiers to copy and paste into their spec...

Страница 7: ... for up to 6 boilers A Low Height Inline cascade can be for up to 4 boilers 1 Standard Height Frame required for each boiler in the cascade 1 pump required for each boiler in the cascade The wide range of options available are detailed on the pages overleaf Alternatively use our online Evomax 2 Cascade Configurator tool to compile a complete list of accessories for your cascade idealcommercialboile...

Страница 8: ... DN50 209394 DN65 209395 DN80 219552 DN100 219553 DN150 219554 Magnetic Low Loss Mixing Header MLLH DN50 222191 DN65 222192 DN80 222193 DN100 222194 Plate Heat Exchanger Up to 60kW nominal output DN50 222219 Up to 60kW nominal output DN65 222993 Up to 60kW nominal output DN80 222220 Up to 150kW nominal output DN50 222221 Up to 150kW nominal output DN65 222994 Up to 150kW nominal output DN80 222222...

Страница 9: ...1480 25 530 850 560 456 212 200 380 2 63 HPDOH DV RQQHFWLRQ 1950 to top of Frame 1918 to top boiler 300 650 1650 25 25 2030 414 30 N N N 414 30 N N N STANDARD HEIGHT INLINE CASCADES 4 X EVOMAX 2 5 X EVOMAX 2 UIN DN FLANGE SIZE SUITABLE FOR 219549 DN100 4 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation 2 63 HPDOH DV RQQHFWLRQ 380 850 530 200 560 456 212 1950 to top of Frame 1918 to top bo...

Страница 10: ...ers 120 150kW with LLH separation 2 63 HPDOH DV RQQHFWLRQ 560 456 212 1950 to top of Frame 1918 to top boiler 414 30 N N N LOW HEIGHT INLINE CASCADES 1 X EVOMAX 2 2 X EVOMAX 2 UIN DN FLANGE SIZE SUITABLE FOR 221127 DN50 1 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221128 DN65 2 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation 685 30 80kW 360 ...

Страница 11: ...ER UP TO 60KW NOMINAL OUTPUT PLATE HEAT EXCHANGER Covering outputs of 60 150 300 450 600 750 and 900kW Brazed Plate Heat Exchangers ensure optimum heat transfer efficiency and low resistance within a compact footprint To be used with Ideal Heating Frame and Header kits Compact design No gaskets Low maintenance and self cleaning All units are pressure tested To be used with Ideal Heating Frame and H...

Страница 12: ...1 DN50 222994 DN65 222222 DN80 UIN DN FLANGE SIZE 222223 DN50 222225 DN80 222995 DN100 222221 DN50 222223 DN65 222225 DN80 222995 DN100 222994 DN65 222222 DN80 UIN DN FLANGE SIZE 222226 DN80 222996 DN100 UP TO 450KW NOMINAL OUTPUT PLATE HEAT EXCHANGER UP TO 600KW NOMINAL OUTPUT PLATE HEAT EXCHANGER UIN DN FLANGE SIZE 222227 DN100 222226 DN80 222996 DN100 222227 DN100 ...

Страница 13: ...lcome to our ideology 25 idealheating com UP TO 750KW NOMINAL OUTPUT PLATE HEAT EXCHANGER UP TO 900KW NOMINAL OUTPUT PLATE HEAT EXCHANGER UIN DN FLANGE SIZE 222229 DN100 UIN DN FLANGE SIZE 222228 DN100 222228 DN100 222229 DN100 ...

Страница 14: ...LH Pump Kit PHEX 222660 Grundfos UPMXXL PHEX Pump Kit PUMPS To ensure your Evomax 2 Cascade works correctly it is vital to fit the correct pumps One pump is required per boiler in the Cascade INSULATION Header kits and Low Loss Headers can be insulated using our robust expanded polypropylene modular insulation range Insulation is also available for 222659 Grundfos UPML M LLH Pump Kit The number of ...

Страница 15: ...LER CASCADE 2 BOILER CASCADE 3 BOILER CASCADE 4 BOILER CASCADE 223032 Standard Height Insulation Starter Kit DN50 1 223035 Standard Height Insulation Starter Kit DN65 1 223038 Standard Height Insulation Starter Kit DN80 DN100 1 1 223036 Standard Height Insulation Continuation Kit DN65 1 223039 Standard Height Insulation Continuation Kit DN80 DN100 2 2 223040 Standard Height Insulation Joined Heade...

Страница 16: ...this schematic is an illustration of a hydraulic arrangement for discussion and reference use only The schematic may not accurately describe the actual arrangement required in order for the system to operate correctly and additional components may be required Under no circumstances should this be used as basis for procurement production or installation ...

Страница 17: ...33 idealheating com 32 welcome to our ideology EVOMAX 2 FLUE OPTIONS ...

Страница 18: ...90 elbow Terminal Locking collars x2 Wall plates x2 CONTENTS Terminal Locking Collar Finishing plates x2 Bracket To comply with CE certification Evomax boilers must be fitted with Ideal concentric flues when using concentric flue type OPEN FLUE OPTIONS B TYPE EVOMAX 2 60 80 VERTICAL CONCENTRIC FLUES OF LONGER LENGTH Model 60 60P 80 80P Max flue length m 28 18 Flue Size 100 150 Wall flue kit No 220916 CO...

Страница 19: ...xtended 222004 90 Elbow 100 150 Extended 222005 45 Elbow 80 125 single 213260 45 Elbow 100 150 single 213258 Wall Bracket 125mm 202242 Wall Bracket 150mm 202243 Expander 80 125 100 150 222133 FLUE KITS OPEN FLUE UIN Open Flue Kit 80 221216 Open Flue Kit 100 221218 Vertical Flue Terminal 80 158769 Vertical Flue Terminal 100 158770 Extension Pipes 80 pair 158771 Extension Pipes 100 pair 158772 90 El...

Страница 20: ...0P 17 5 28 25 80 80P 10 18 15 3 100 10 20 120 9 49 150 6 32 EQUIVALENT LENGTH OF ELBOWS METRES CONCENTRIC OPEN FLUE Size 80 125 100 150 80 100 45 0 85 1 25 0 45 0 60 90 1 6 1 9 1 0 1 0 EXAMPLES OF FLUE LENGTH CALCULATION MODEL FLUE TYPE MAX PERMISSIBLE EQUIVALENT LENGTH TABLE 1 ELBOWS MAX PERMISSIBLE STRAIGHT LENGTH TYPE EQUIVALENT LENGTH TABLE 2 NO TOTAL EQUIVALENT LENGTH 60 80 125 17 5 90 1 6 2 ...

Страница 21: ...ded to prevent movement of the tube connections due to expansion and contraction These must be fitted to the ductwork to ensure safe operation of the system Simple system ordering with a starter kit and extension kits Starter kit includes appliance connection non return flue damper condensate tee and trap and all clips to secure the flue Extension pack includes appliance connection non return flue dam...

Страница 22: ...P COMPATIBLE WITH EVOMAX 2 100 100P 120 120P 150 213274 Plume kit 1m extension 80 125 A 5 213272 Plume kit 90 deg elbow 80 125 B 5 213273 Plume kit 45 deg elbows pair 80 125 C 5 213277 Plume kit 1m extension 100 150 A 5 213275 Plume kit 90 deg elbow 100 150 B 5 213276 Plume kit 45 deg elbows pair 100 150 C 5 EVOMAX 2 PLUME KIT PACKAGED OPTIONS EVOMAX 2 PLUME KIT The Evomax 2 Plume Kit is one of th...

Страница 23: ...ernal concentric lengths Y FLUE TYPES Before ventilation can be sized we need to identify the type of flue system Type B Open flue takes air from the plant room adequate ventilation must be available Type C Room sealed takes air from outside We also need to know the classification of the room type Boiler house a dedicated building for the installation of boilers and ancillary plant Boiler room a dedi...

Страница 24: ...any different regulations relating to flues and ventilation This document will not cover all of them but assist in obtaining information and guidance and provide useful and practical information This guide looks at common standards used to determine the requirements for flue and ventilation installation requirements and should not be used as a sole reference for flue regulations Please also remember ...

Страница 25: ...ll installations are subject to the clean air act requirements Installations below 333kW net heat input can terminate horizontally at low level subject to a risk assessment and complying with all other clearance distances as defined in IGEM UP10 Appliance inputs greater than 333kW net need prior approval from the Local Authority with position of flue termination agreed by them No terminal fitted to n...

Страница 26: ...ion openings are located at floor level Ventilation to an internal space is not generally recommended unless a Risk Assessment has been completed The air supplied for boiler room ventilation shall be such that the maximum temperature within the boiler house is 25 C at floor level or 100mm above floor level 32 C at mid level 1 5 m above floor level 40 C at ceiling level or 100mm below ceiling level MEC...

Страница 27: ...should not be nearer than 150mm fanned draught to an opening into the building fabric formed for the purpose of accommodating a built in element such as a window frame If the terminal is fitted less than 500 mm below plastic gutters painted eaves or any other painted surface then an aluminium shield at least 1m long should be fitted to protect the surface For positioning of open flue terminals refere...

Страница 28: ...0 60 Hz 0 8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDENSATE PUMP COMPATIBILITY BOILER COMPATIBLE EVOMAX 2 30 150kW IMAX XTRA 2 80 280kW IMAX XTRA EL 320 1240kW EVOMOD 250 1000kW EVOJET 150 1450kW TERMINATION TO DRAIN GULLEY SEE INSTALLATION MANUAL FOR FULL INSTRUCTI...

Страница 29: ...onal service team delivering help and advice to you and your customers throughout the year BOILER TRAINING Our comprehensive one day courses can be mixed and matched for individual installation and servicing companies Each course uses a simple step bystep approach with hands on training to ensure all aspects of commissioning servicing and fault finding can be dealt with quickly and efficiently Book ...

Страница 30: ...59 idealheating com 58 welcome to our ideology NOTES NOTES ...

Страница 31: ...ce Statutory rights of the consumer are not affected PLEASE NOTE The information in this brochure was correct at the time of going to print Ideal Heating reserve the right to make any modifications to product specifications or any other details without prior notification For further clarification please enquire in writing to the head office address address above Sales 0844 543 6060 Technical Help 01482...

Отзывы: