35
idealheating.com
34
welcome to our ideology
CONCENTRIC FLUE OPTIONS (C TYPE)
HORIZONTAL WALL FLUE KIT
VERTICAL ROOF FLUE KIT
EVOMAX 2 HORIZONTAL CONCENTRIC FLUE APPLICATION ~ MAXIMUM LENGTHS
AND PRESSURE DIFFERENTIALS
Model
30/30P
40/40P
60/60P
80/80P
100/100P
120/120P
150
Max flue length (m)
33
30
17.5
10
10
9
6
Flue Size
80/125
100/150
Wall flue kit No
220919
220921
EVOMAX 2 VERTICAL CONCENTRIC FLUE APPLICATION ~ MAXIMUM LENGTHS AND
PRESSURE DIFFERENTIALS
Model
30/30P
40/40P
60/60P
80/80P
100/100P
120/120P
150
Max flue length (m)
33
30
17.5
10
10
9
6
Flue Size
80/125
100/150
Wall flue kit No
220915
220918
EVOMAX 2 60 & 80 HORIZONTAL CONCENTRIC FLUES
OF LONGER LENGTHS
(LARGER FLUE DIAMETER)
Model
60/60P
80/80P
Max flue length (m)
28
18
Flue Size
100/150
Wall flue kit No
220920
CONTENTS
• 90° elbow
• Terminal
• Locking collars (x2)
• Wall plates (x2)
CONTENTS
• Increaser
• 90° elbow
• Terminal
• Locking collars (x2)
• Wall plates (x2)
CONTENTS
• Terminal
• Locking Collar
• Finishing plates (x2)
• Bracket
To comply with CE certification, Evomax boilers must be fitted with
Ideal concentric flues (when using concentric flue type).
OPEN FLUE OPTIONS (B TYPE)
EVOMAX 2 60 & 80 VERTICAL CONCENTRIC FLUES OF
LONGER LENGTH
Model
60/60P
80/80P
Max flue length (m)
28
18
Flue Size
100/150
Wall flue kit No
220916
CONTENTS
• Increaser
• Terminal
• Locking Collars (x2)
• Finishing plates (x2)
• Bracket
* The air inlet grille must be fitted to all installations.
** At least 1 off extension tube MUST be used in the installation. This may be suitably cut to length if required.
CONTENTS
221216 / 221218
• Air inlet grille*
158769 / 158770
• Terminal
158771 / 158772
• Extension tube (x2)**
EVOMAX 2 VERTICAL CONCENTRIC FLUE APPLICATION ~ MAXIMUM LENGTHS AND PRESSURE
DIFFERENTIALS
Model
30/30P
40/40P
60/60P
80/80P
100/100P
120/120P
150
Max flue
length (m)
65
70
25
15.3
20
49
32
Max flue
press diff
(Pa)
180
227
146
312
220
473
332
Flue Size
80/125
100/150
Wall flue
kit No
158769
158770