43
idealheating.com
42
welcome to our ideology
UIN
DESCRIPTION
220925
Multiline Starter Kit 80/125
220926
Multiline Extension Kit 80/125
220927
Multiline Starter Kit 100/150
220928
Multiline Extension 100/150
EVOMAX 2 MODEL
OUTPUT
CASCADE SYSTEM LIMITS
COMBUSTION PRODUCTS DATA
Model
Maximum
System
Capacity
Maximum
Permissible Head-
er
Pressure ‘A’
(Static)
Max rate
CO
Ї
Min rate
CO
Ї
Temperature
Max
Max
Min
Hmax
Pmax
±0.5
±0.5
kW
kW
kW
Pa
%
%
C
30
7.5
400
40
9.7
9.0
72
40
10
60
15
80
20
100
25
600
80
120
30
150
37.5
30P
7.5
400
40
11.4
10.6
40P
10
60P
15
80P
20
100P
25
600
80
120P
30
At the maximum system capacity the
static pressure generated against the flue
resistance at position [A] must not exceed the
value Pmax quoted in the table below.
*
Multiline flue supplied to point A. Customers are to
fabricate / supply B type flue system to termination
point within flue resistance parameters.
Flue height = 570mm from the top of the first boiler in the system.
Increase the height 29mm for each adjacent boiler.
Customer specified
components*
Must be CE approved
A*
A*
3.0ºC
Condensate Drain
(Siphon)
Header
UIN
DESCRIPTION
DRAWING
IDENTIFIER
COMPATIBLE
WITH EVOMAX 2
30, 30P, 40, 40P, 60,
60P, 80, 80P
COMPATIBLE WITH
EVOMAX 2 100, 100P, 120,
120P, 150
213274
Plume kit 1m extension 80/125
A
5
213272
Plume kit 90 deg elbow 80/125
B
5
213273
Plume kit 45 deg elbows (pair) 80/125
C
5
213277
Plume kit 1m extension 100/150
A
*
5
213275
Plume kit 90 deg elbow 100/150
B
*
5
213276
Plume kit 45 deg elbows (pair) 100/150
C
*
5
EVOMAX 2 PLUME KIT - PACKAGED OPTIONS
EVOMAX 2 PLUME KIT
The Evomax 2 Plume Kit is one of the latest additions to the flue accessory range from Ideal, designed specifically
for the Evomax 2 range. Available for Evomax 2 boilers up to 150kW the Plume Kit can be used to relocate the flue
terminal up to 10m.
• Suitable for all Evomax 2 up to 150kW
• Available for both 80/125 & 100/150
flue applications
• Plume kit offers terminal relocation up to 10m
• Includes standard appliance connector, horizontal
flue kit, special rain collar, external plume kit 1m
and terminal
• Offers neat solutions for awkward flue installations
where the terminal requires relocation
PRODUCTS
A
Turret elbow
B
Flue terminal with rain cowl & air terminal assembly
C
1 Meter extension tube
D
90 degree elbow
E
Flue terminal end
F
External wall plate
G
Internal wall plate
H
Wall bracket
*Note: The 100/150mm Plume Kit system
can also be used on Evomax 2 80, 80P,
60 & 60P model variants if internal
concentric wall horizontal flue adaptor
is used (Part No. 158660). See Evomax 2
installation manual for details.
OPERATION