Summary of Contents for armoMAG 4/1 G Series

Page 1: ...n and maintenance instructions atmoMAG MAG 4 1 G AT BE de CH de DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de www...

Page 2: ...setting the water flow rate 13 6 3 Gas conversion 13 6 4 Checking that the flue gas sensor works correctly 13 6 5 Checking the gas flow pressure 14 6 6 Checking leak tightness 15 6 7 Handing the prod...

Page 3: ...other system compon ents installing and fitting the product in accord ance with the product and system approval compliance with all inspection and main tenance conditions listed in the instruc tions...

Page 4: ...combustion and room air Sprays solvents chlorinated cleaning agents paint adhesives ammonia com pounds dust or similar substances may lead to corrosion on the product and in the flue system Ensure tha...

Page 5: ...ing regulations and or OIB Austrian Institute of Construc tion Engineering directives Applicability Switzerland The gas fired instantaneous water heater must only be installed by a competent per son w...

Page 6: ...e data plate The data plate is mounted at the front of the down draught diverter under the product casing at the factory Applicability Germany OR Austria OR Belgium OR Switzerland Information on the d...

Page 7: ...applicable directives as stated on the identification plate The declaration of conformity can be viewed at the manufac turer s site 4 Set up 4 1 Checking the scope of delivery 1 Remove the product fr...

Page 8: ...0 mm B 180 mm optimum approx 250 mm C 20 mm optimum approx 50 mm D 500 mm in front of the heat generator to enable easy access for maintenance work may be provided by an opening door It is not necessa...

Page 9: ...270 172 5 50 26 259 115 113 61 4 min 20 120 min 20 110 224 617 48 A 557 579 680 616 Height dimension A Germany Austria Belgium Switzerland MAG 114 1 G E BE FR 658 mm MAG 114 1 G H DACH 658 mm 658 mm...

Page 10: ...270 172 5 50 26 259 124 141 61 4 min 20 120 min 20 133 5 224 617 48 A 493 679 680 616 Height dimension A Germany Austria Belgium Switzerland MAG 114 1 G E BE FR 658 mm MAG 114 1 G H DACH 658 mm 658 m...

Page 11: ...ring capacity of the wall 2 Note the total weight of the product 3 Only use fixing material that is permitted for the wall 4 If required ensure that mounting apparatus on site has sufficient load bear...

Page 12: ...e liquid gas tank has been purged properly before installing the product If required contact the filler or the liquid gas supplier 5 3 Using the correct gas type Using the incorrect gas type may cause...

Page 13: ...e with the value specified in the technical data At initial start up After replacing the micro switch 1 2 If the measured value exceeds the value specified in the technical data set the flow rate at t...

Page 14: ...by opening the hot wa ter tap again and switch the product on and off again by pressing the main switch 1 a second time If resetting does not work or the product is repeatedly blocked by a safety devi...

Page 15: ...ly displayed by the LED indicator light Use the table that is included in the appendix to eliminate the fault After each time you eliminate a fault check that the flue gas sensor is working without an...

Page 16: ...uct C A B D 5 Disconnect the plug connection in the cable for the gen erator 6 Unscrew the union nuts from the water valve Remove the clip from the cold water connection on the burner 7 Remove the pip...

Page 17: ...e dirty components using a soft brush leaving the installation room to do so and replace any dam aged components if required 3 Check whether the burner jets are blocked If a jet is blocked carefully r...

Page 18: ...ing cleaning agent to a container of hot water 4 Use a commercial descaler to remove any limescale while taking into consideration the corresponding docu mentation 5 Rinse the heat exchanger under run...

Page 19: ...s flow value at nominal heat input in the tables of gas settings in the appendix Note Deviations of 5 are permitted Conditions The deviation is greater than 5 Check whether the correct burner jets hav...

Page 20: ...w the sealing screw from the test nipple 1 for the burner pressure 4 Connect a U tube manometer resolution at least 0 1 bar Caution Risk of a gas leak The adjusting screw seals the gas valve as sembly...

Page 21: ...s 11 Customer service Applicability Austria Vaillant Group Austria GmbH Clemens Holzmeister Stra e 6 1100 Wien sterreich E Mail Kundendienst termin vaillant at Internet Kundendienst http www vaillant...

Page 22: ...ck on again 11 Setting the domestic hot water function 12 Handing over the operating instructions to the customer B Troubleshooting Symptom Possible cause Measure The product does not work The LED doe...

Page 23: ...el on the data plate DE 2E AT CH 2H G20 2 kPa 20 mbar DE 2LL G25 2 kPa 20 mbar DE AT CH 3P DE AT G31 5 kPa 50 mbar CH G31 3 7 kPa 37 mbar Factory setting G20 G25 G31 Burner jets label 11 4 1 14 4 1 11...

Page 24: ...14 4 1 Natural gas 2E G20 38 3 48 7 Natural gas 2E G25 41 7 52 8 Liquid gas 3P G31 14 8 18 8 Burner pressure Gas family Burner pressure for nominal heat input 11 4 1 14 4 1 Natural gas 2E G20 1 12 kPa...

Page 25: ...1 G LL DE OR MAG 144 1 G P BE OR MAG 144 1 G P CH 3 2 1 4 5 6 7 8 9 10 11 12 13 14 15 18 16 17 1 Gas valve assembly 2 Micro switch 3 Monitoring electrode 4 Ignition electrode 5 Burner 6 Transparent c...

Page 26: ...the product incl domestic hot water gener ation Annually 11 Checking leak tightness Annually 15 12 Checking the heat input Annually 19 13 Check the flame pattern Flames must not touch the heat exchang...

Page 27: ...est symbol registration no 1008CS3137 1008CS3137 1008CS3137 1008CS3137 MAG 144 1 G LL DE MAG 144 1 G P BE MAG 144 1 G P CH Designated country designation in accordance with ISO 3166 EN BE CH Approved...

Page 28: ...0 l min 6 5 14 0 l min 6 5 14 0 l min Max heat input in relation to the net calorific value Hi 21 7 kW 21 7 kW 27 7 kW 27 7 kW Min heat input Qmin 7 6 kW 7 6 kW 9 7 kW 9 7 kW Max heat output Pmax 18...

Page 29: ...n pressure 1 7 2 5 kPa 17 0 25 0 mbar 1 7 2 5 kPa 17 0 25 0 mbar 1 7 2 5 kPa 17 0 25 0 mbar 1 7 2 5 kPa 17 0 25 0 mbar Number of burner jets 24 24 24 24 Burner jet 0 85 mm 0 85 mm 0 85 mm 0 85 mm Burn...

Page 30: ...CH MAG 144 1 G LL DE Gas flow rate at max heat output 2 67 m h 2 67 m h 3 36 m h 3 36 m h Gas connection pressure 1 8 2 5 kPa 18 0 25 0 mbar 1 8 2 5 kPa 18 0 25 0 mbar 1 8 2 5 kPa 18 0 25 0 mbar 1 8 2...

Page 31: ...ent for combustion at max heat input 38 3 m h 38 3 m h 38 3 m h 49 84 m h Air requirement for combustion at min heat input 28 9 m h 28 9 m h 28 9 m h 38 04 m h CO content at max heat output 7 30 7 30...

Page 32: ...45 0 mbar 2 5 4 5 kPa 25 0 45 0 mbar Number of burner jets 24 24 28 28 Burner jet 0 5 mm 0 5 mm 0 51 mm 0 51 mm Burner pressure 31 7 mbar 31 7 mbar 34 5 mbar 34 5 mbar Air requirement for combustion a...

Page 33: ...ue gas monitoring device 4 Flue gas pipe installed 5 Flue gas route 4 Front casing closed 5 Frost 4 G Gas connection 12 Gas type 12 H Handing the product over to the operator 15 Heat exchanger 18 I If...