7
Viceroy GTS -
Installation & Servicing
GENERAL
Air inlet
B
Air outlet
550 mm
1.5 m
1 m
*
1 m
*
A
C
vic9106
Refer to notes above
Refer to notes above
2 BOILER CLEARANCES
The minimum dimensions as indicated must be respected to
ensure good access around the boiler.
Note.
To allow the inlet of the combustion air, the boiler room
must be adequately ventilated, the section and the location of
which must comply with local recommendations.
Refer also to Frame 3.
The boiler must be positioned so that there is enough space
available to allow the following:
•
Access around the boiler for servicing.
•
Space to open the boiler front door.
•
Space to access the burner.
Recommended minimum clearances are as follows:
Rear
1000mm or adequate space to make the flue connections
and access to the flue sample point, drain connection, flue
and smokehood cleanout doors and any safety or control
devices.
Sides
One side may be 100mm the other side must be 200mm
plus the burner projection or 500mm whichever is the
greater to allow the burner door to be swung open and
maintain access to the rear. In multiple boiler installations
both sides may be 100mm except at one end consideration
must also be given to the burner door hinge position and
consequent clearance for access to the rear.
Front
See Table below.
567
R = 41
5
R = 751,
5
15
240
burner door open
View from top
R = 751.5
vic7084
GTS 8
GTS 9
GTS 10
GTS 11
GTS 12
GTS 13
GTS 14
1505 1665 1825 1985 2145 2305 2465
105
105
105
105
105
105
105
1500
2000
2000
2000
2500
2500
2500
A
B
C
Dimension
Boiler
mm
mm
mm