29
icos system condensing -
Installation and Servicing
SERVICING
2077
Front panel
40 SERVICING SCHEDULE
To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular
intervals and serviced as necessary. The frequency of
servicing will depend upon the installation condition and
usage but should be carried out at least annually.
It is the law that any service work must be carried out by a
registered CORGI installer.
Note.
Some aluminium oxide build-up on the heat engine
fins is usual with this type of condensing boiler.
Though removal is recommended annually, the heat
engine MUST be inspected and cleaned after a
MAXIMUM of 2 years operation
.
1.
Remove the boiler bottom panel - refer to Frame 43.
2.
Light the boiler and carry out a pre-service check, noting
any operational faults.
3.
Relight the boiler and operate for at least 10 minutes.
Check the gas consumption.
4.
Connect a suitable gas analyser to the sampling point on
the top of the boiler (refer to Frame 41) or into the flue
terminal if access is possible (optional test).
For correct boiler operation, the CO/CO
2
content of the flue
gas should not be greater than 0.004 ratio.
If this is the case, and the gas input is at least 90% of the
nominal, then no further action need be taken. If not,
proceed to Step 5 but see note above.
5.
Clean the main burner.
6.
Clean the heat engine.
Note.
This must be done with the heat engine and deposits
in a dry condition - refer to Frame 49.
7.
Check the main injector for blockage or damage.
8.
Wherever possible remove and clean the condensate trap
(refer to Frame 48) and check the drain for blockage.
9.
Check that the flue terminal is unobstructed and that the
flue system is sealed correctly.
The servicing procedures are covered more fully in Frames
41 to 50 and MUST be carried out in sequence.
Note.
In order to carry out either servicing or replacement of
components the boiler front panel and sealing panel
must be removed - refer to Frames 42 and 44.
WARNING.
Always turn OFF the gas supply at the gas
service cock, and switch OFF and disconnect the electricity
supply to the appliance before servicing.
IMPORTANT.
10.
After completing the servicing or exchange of components
always test for gas soundness and carry out functional
checks as in 3 and 4 above.
11.
When work is complete the sealing panel MUST be
correctly refitted, ensuring that a good seal is made.
Do NOT OPERATE the boiler if the sealing
panel is not fitted
12.
If, for any reason, the condensate trap has been removed.
Ensure that the trap is re-filled with water before
re-assembly.
13.
Complete the service section in the Benchmark log book.
41 SAMPLING POINT
42 BOILER FRONT PANEL REMOVAL
1.
Remove the 2 securing screws.
2.
Pull the panel forward at the bottom and lift to disengage
it from the top lugs.
2056
Sample point
SER
VICING
Содержание icos system m3080
Страница 1: ......
Страница 51: ...51 icos system condensing Installation and Servicing NOTES ...
Страница 53: ......