tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
◇
Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop
valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the
tighten torque as follows figure.
Equivalent pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate the pressure
loss.
Elbow and Oil loop conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
Actual
Pipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
ALCA-H42A5/C5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2
oil loops during the installation, then the equivalent pipe length should be:
L=25+0.35×5+2.4×2=31.5(m)
◇
Specification of connection pipe for indoor unit and outdoor unit
Cooling Capacity(Btu/h)
12000
18000
24000
36000
48000
60000
Connection
Pipe (mm)
Liquid Pipe
Φ6.35
Φ6.35
Φ9.52
Φ9.52
Gas Pipe
Φ12.7
Φ12.7
Φ15.88
Φ19.05
Max.
Length(m)
Liquid Pipe Dia.
Φ6.35
Φ6.35
Φ9.52
Φ9.52
Gas Pipe Dia.
Φ12.7
Φ12.7
Φ15.88
Φ19.05
Max. Length
15
20
30
50
Max. Height (m)
10
15
15
30
Max. Bend Qty
4
4
4
10
Extra R410a per meter when the
pipe length is more than 5 meter (kg)
0.05
0.05
0.07
0.09
Caution:
1.The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is
necessary. If the pipe length is more than this then you should charge more refrigerant into the system
according to the above Charging Data
2.The thickness of the pipe is 0.5-1.0, bearing pressure is 3.040MPa;
3.If the connection pipe is too long, the cooling capacity and stability would be decreased. And the more
bend quantity, the resistance in the piping system would be bigger, then the cooling and heating capacity
would be decreased even lead to compressor broken. We suggest you to use the shortest connection
Содержание ICC(ICA)-**HR-SA6-NI
Страница 1: ......
Страница 3: ......
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 18: ...21 ...
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ...50 ...
Страница 51: ...54 ...
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 67: ...540 760 111 539 257 287 322 130 300 326 590 800 540 4 10 19 370 ...
Страница 68: ...130 370 4 10 19 540 800 690 326 300 606 332 400 354 11 71 903 857 ...
Страница 69: ...148 1255 180 945 413 373 4 10 19 585 340 ...
Страница 72: ...152 ...
Страница 73: ......
Страница 74: ......
Страница 75: ...155 Introduction of Control Board QRD SW3F HCE1 outdoor unit board sockets Power supply 380V 415V ...
Страница 104: ...186 7 Failure analysis Wired controller communication failure ...
Страница 105: ...187 Communication failure between indoor and outdoor unit ...
Страница 106: ...188 Outdoor protection phase sequence ...
Страница 107: ...189 Cooling high pressure protection ...
Страница 108: ...190 Heating high pressure protection ...
Страница 109: ...191 Cooling low pressure protection ...
Страница 110: ...192 Heating low pressure protection ...
Страница 111: ...193 Cooling exhaust temperature protection ...
Страница 112: ...194 Heating exhaust temperature protection ...
Страница 113: ...195 Refrigerant shortage or four way valve failure protection ...
Страница 114: ...196 Sensor failure protection ...
Страница 115: ...197 No action after power on ...
Страница 116: ...198 Poor effect ...
Страница 117: ...199 ...
Страница 118: ...200 Abnormal sound or viberation ...
Страница 119: ...201 ...
Страница 120: ...202 Abnormal odor ...
Страница 121: ...203 Air switch action when air conditioner starting up ...
Страница 122: ...204 Air conditioner water leakage ...