background image

Indoor unit

Outdoor unit

Multicore signal
wire

Wired
controller

Signal wire

Power cable

Control wire

Control

wire

indoor unit

 

outdoor unit

 

Multicore signal

 

 

Wired

 

controller

 

Signal wire

 

Power cable

 

Control wire

 

Control

 

wire

 

Содержание ICC(ICA)-**HR-SA6-NI

Страница 1: ......

Страница 2: ...2k Btu h 18k Btu h 24k Btu h 36k Btu h 48k Btu h 60k Btu h Ceiling Floor 12k Btu h 18k Btu h 24k Btu h 36k Btu h 48k Btu h 60k Btu h Low ESP Duct 12k Btu h Mid ESP Duct 18k Btu h 24k Btu h 36k Btu h 48k Btu h 60k Btu h High ESP Duct 24k Btu h 36k Btu h 48k Btu h 60k Btu h ...

Страница 3: ......

Страница 4: ...7 Four way cassette 1 Feature 8 2 Specfication 10 3 Capacity Amendment 16 4 Demension 18 5 Electrical wiring and connection 19 6 Installation 26 7 Explode view 31 ...

Страница 5: ... Built in drain pump drain head height is up to 1 2meters creating the ideal solution for perfect water drainage also construction and installation is much easier and convenient Long term air filter wash period is two times longer than normal filter and maintenance is free 3D helix air blade ensures the air flow sufficiently reduces the unit thickness and reduces the operation noise greatly Plasti...

Страница 6: ... Adjustable ESP Auto restart Optional Anti cold wind Afterheat wind blowing Timing ON OFF Operation Time display Operation mode display Fan speed display Defrost display Timing ON OFF display Wind angle display Sleeping mode display Running Auto start Dehumidifying Auto defrost Ventilation function Low ambient temperature cooling Health Washable air filter Fresh air interface Installation Left rig...

Страница 7: ...0 750 920 850 750 Indoor Coil Number Of Row 2 2 2 Tube Pitch a x Row Pitch b mm 20 5 12 7 20 5 12 7 20 5 12 7 Fin Pitch mm 1 5 1 5 1 4 Fin Material Hydrophilic aluminum fin Tube Outside Dia and Material mm φ7 Inner grooved φ7 Inner grooved φ7 Inner grooved Coil Length x Height x Width mm 1160 164 25 4 1160 164 25 4 1160 164 25 4 Heat Exchanging Area m2 4 34 4 34 5 76 Indoor Unit Indoor Air Flow Hi...

Страница 8: ...ity measured Inside the room DB temperature 20 Outside of the room DB temperature 7 WB temperature 6 2 Parameters above are all measured when the connecting pipe is 5 meters 3 Parameters above may be modified as product improvement We keep the right to change the product specifications without prior notice please take the parameters listed on the nameplate as criterion Model Indoor Panel Outdoor P...

Страница 9: ...Pipe Length m 20 30 30 Max Difference In Level m 15 15 15 Operation Temperature Range 16 32 16 32 16 32 Ambient Temperature Range Cooling Heating 5 49 15 24 5 49 5 49 15 24 Application Area m2 21 35 28 47 28 47 Connection Wiring Power Wiring Indoor mm 2 3 2 5mm 2 Power Wiring Outdoor mm 2 3 4mm 2 3 4mm 2 Signal Wiring mm 2 3 2 5mm 2 2 1mm 2 3 1mm 2 2 1mm 2 3 1mm 2 3 1mm 2 Wireless Remote Controlle...

Страница 10: ...h mm 1 4 1 4 1 4 Fin Material Hydrophilic aluminum fin Tube Outside Dia and Material mm φ7 Inner grooved φ7 Inner grooved φ7 Inner grooved Coil Length x Height x Width mm 2142 205 25 4 2142 205 25 4 2142 246 25 4 Heat Exchanging Area m 2 12 76 12 76 15 60 Indoor Unit Indoor Air Flow Hi Mi Lo m 3 h 1500 1200 1050 1500 1200 1050 1800 1440 1260 Noise Level Hi Mi Lo dB A 48 45 39 48 45 39 50 47 41 Net...

Страница 11: ... as product improvement We keep the right to change the product specifications without prior notice please take the parameters listed on the nameplate as criterion Model Indoor Panel Outdoor Factory Model Indoor Panel MB12 MB12 MB12 Outdoor Power Supply V Hz Ph 380 415 50 3 380 415 50 3 380 415 50 3 Capacity Cooling Btu h 48000 60000 60000 KW 14 0 17 6 17 6 Heating Btu h 53000 63500 W 15 5 18 5 El...

Страница 12: ...e 16 32 16 32 16 32 Ambient Temperature Range Cooling Heating 5 45 15 24 5 45 5 45 15 24 Application Area m 2 56 93 64 107 64 107 Connection Wiring Power Wiring Indoor mm 2 3 1mm 2 3 1mm 2 3 1mm 2 Power Wiring Outdoor mm 2 5 2 5mm 2 5 2 5mm 2 5 2 5mm 2 Signal Wiring mm 2 2 1mm 2 2 1mm 2 2 1mm 2 Wireless Remote Controller YKR H 009E YKR H 009E YKR H 009E Qty per 20 40 40HQ Only For Reference Set 20...

Страница 13: ...g capacity amendment coefficient of cooling capacity nominal cooling capacity nominal cooling capacity could be found from the performance parameters list amendment coefficient of cooling capacity could be found from table above Amendment coefficient of heating capacity under different indoor outdoor DB WB temperature Actual heating capacity calculation Actual heating capacity amendment coefficien...

Страница 14: ... coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit Different Heating Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit Height Difference H m Cooling Equivalent pipe length EL m Height Difference H m Equivalent pipe length EL m Heating ...

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ...21 ...

Страница 19: ...t outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire Multicore signal Wired controller indoor unit outdoor unit Signal wire Power cable Control wire Control wire ...

Страница 20: ...t Outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire indoor unit outdoor unit Multicore signal Wired controller Signal wire Power cable Control wire Control wire ...

Страница 21: ...utdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire Indoor unit Outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire ...

Страница 22: ...output High Mid Low Neutra l Indoor fan output input Float switch input Buzzer 4 DIP switch Return air temp Indoor coil temp input Wired control receiver Transformer output 3 DIP switch Remote control receiver Neutral Low Mid High Compressor output Drainage pump output Electric heating output Outdoor fan output Indoor fan output 4 way valve Neutra l insert Wired control receiver Remote control rec...

Страница 23: ...er electrode Heat insulation material used to connect copper pipe PE foam material its thickness is more than 8mm Wrench 2 pcs one of them is with adjustable torque wrench 42N m 65N m 100N mm Power cable electrical wire between indoor and outdoor unit Must be in accordance with the wire diameter in the wiring diagram Nitrogen cylinder in order to prevent oxidation when welding using Nitrogen to re...

Страница 24: ...s the proportion of refrigerant is bigger than air so if it leaks the gas will be filled on the ground Therefore if the units mounted on a closed room there must be good ventilation to prevent suffocation In case of leakage of refrigerant units should immediately stop running and contact with maintenance personnel in time There must be no fire at the site because the refrigerant will turn to harmf...

Страница 25: ...al otherwise it will cause water leakage air leakage etc Tighten the bolt and ensure that four hooks are in close contact with the nuts and washers and the unit is suspended firmly and reliably onto the hooks After the unit is installed ensure it is secure and does not shake or sway Ensure that the centre of the indoor unit is in alignment with the centre of the opening in the ceiling 6 6 Drainage...

Страница 26: ...bserve the junction to ensure that there is no water leakage If the unit is installed in the newly built house strongly recommend that this test taken before the ceiling installation Even it is the heating only unit this test is unavoidable 6 7 Panel installation As to the MB12 panel please refer to the following picture the panel has four hooks which attach to corresponding hangers on the unit an...

Страница 27: ...acement hole is connected to the return air inlet of the indoor unit when in the process of operation due to the negative pressure the fresh air can be introduced from outside Connect to duct There are four rectangular connection holes on the four sides of the unit If users what to connect it to the duct please close the outlet to the side which needs connecting to the duct as well as cut down the...

Страница 28: ...embly 1 1 2 空气过滤网 Air filter net 1 1 3 导风叶片 guide wind vane 4 1 4 步进电机 Step motor 4 24BYJ48 2 1 5 显示灯板 Display board 1 SX DISP 01 1 6 面板围框组件 Panel frame assembly 1 2 电控盒盖 Cover for electric components 1 3 电控盒总成 Electric assembly 1 3 1 电容 capacitance 1 2 5μF 450V a c ...

Страница 29: ...ssembly 1 6 3 蒸发器进液管组件 Evaporator inlet tube assembly 1 7 蒸发器挂钩 Evaporator Pothook 2 8 蒸发器连接板 Evaporator connect board 1 9 排水泵 Drain pump 1 PLD 700 9 1 浮子开关 Bodder switch 1 9 2 排水泵支架 Drain pump support 1 10 风轮 Wind wheel 1 Ф283 166 11 电机 Fan motor 1 YSK30 6E1 12 电机支架 motor holder 1 13 风道 Air passage 1 14 接水盘固定板 Water pan holder 4 15 挂钩 Pothook 4 16 围板 A Boarding A 1 16 1 围板 B Boarding B 1 17 阀板 A ...

Страница 30: ...机 Step motor 1 24BYJ48 2 1 6 显示灯板 Display board 1 SX DISP 01 2 导风圈总成 Guide wind loop assembly 1 2 1 导风圈 Guide wind loop 1 2 2 导风圈配板 Guide wind board 1 2 3 端子板 7 位 TerminAL board 1 3 接水盘组件 Defrosting pan 1 4 蒸发器总成 Evaporator assembly 1 4 1 蒸发器组件 Evaporator part 1 4 2 蒸发器出气管组件 Evaporator outlet tube assembly 1 4 3 蒸发器进液管组件 Evaporator inlet tube assembly 1 5 电控盒总成 Electric box assembly 1 5 1 控制板 PCB ...

Страница 31: ...frame assembly 1 1 4 1 面板围框 Panel frame 1 1 4 2 导风叶片 Wind guiding blade 4 1 5 步进电机 Step motor 1 24BYJ48 2 1 6 显示灯板 Display board 1 SX DISP 01 2 导风圈总成 Guide wind loop assembly 1 2 1 导风圈 Guide wind loop 1 2 2 导风圈配板 Guide wind board 1 2 3 端子板 7 位 TerminAL board 1 3 接水盘组件 Defrosting pan 1 4 蒸发器总成 Evaporator assembly 1 4 1 蒸发器组件 Evaporator part 1 4 2 蒸发器出气管组件 Evaporator outlet tube assembly 1 4 3 蒸发器进液...

Страница 32: ...1 3 接水盘组件 Defrosting pan 1 4 蒸发器总成 Evaporator assembly 1 4 1 蒸发器组件 Evaporator part 1 4 2 蒸发器出气管组件 Evaporator outlet tube assembly 1 4 3 蒸发器进液管组件 Evaporator inlet tube assembly 1 5 电控盒总成 Electric box assembly 1 5 1 控制板 PCB board 1 QRD SN3F 2S SYE1 5 2 变压器 Transformer 1 TDB 8 B PTC 5 3 电容 capacitance 1 6μF 450V a c 5 4 传感器 5K3470 XH2 0 5m 塑封 Sensor 1 1 5 5 传感器 5K3470 XH2 1 5m 铜壳 Sensor 2 1 6 底盘泡沫组件 ...

Страница 33: ...36 Ceiling floor type 1 Feature 37 2 Specfication 39 3 Capacity amendment 45 4 Demension 47 5 Electrical wiring 48 6 Installation 56 7 Explode view 58 ...

Страница 34: ...insulation efficiency and no condensation on shell Long term air filter the wash period is two times longer than normal filter maintenance is free Adopting low noise centrifugal fan strong wind but quiet operation the silence design achieves harmony residential living All the installation and maintenance can be done in the bottom of unit saving the maintenance space 3 phase power supply type units...

Страница 35: ...eating 3 Speed Adjustable ESP Auto restart Optional Anti cold wind Afterheat wind blowing Timing ON OFF Operation Time display Operation mode display Fan speed display Defrost display Timing ON OFF display Wind angle display Sleeping mode display Running Auto start Dehumidifying Auto defrost Ventilation function Low ambient temperature cooling Health Washable air filter Fresh air interface Install...

Страница 36: ...010 900 1300 1010 900 Indoor Coil Number Of Row 2 2 3 Tube Pitch a x Row Pitch b mm 20 5 12 7 20 5 12 7 20 5 12 7 Fin Spacing mm 1 6 1 6 1 6 Fin Material Hydrophilic aluminum fin Tube Outside Dia and Material mm φ7 Inner grooved φ7 Inner grooved φ7 Inner grooved Coil Length x Height x Width mm 570 246 25 4 570 246 25 4 570 246 38 1 Heat Exchanging Area m2 4 00 4 00 6 00 Indoor Unit Indoor Air Flow...

Страница 37: ...ture 6 2 Parameters above are all measured when the connecting pipe is 5 meters 3 Parameters above may be modified as product improvement We keep the right to change the product specifications without prior notice please take the parameters listed on the nameplate as criterion Model Indoor Outdoor Outdoor Power Supply V Hz P h 220 240 50 1 220 240 50 1 220 240 50 1 Capacity Cooling Btu h 18000 240...

Страница 38: ...tion Area m 2 21 35 28 47 28 47 Connection Wiring Power Wiring Indoor mm 2 3 2 5mm 2 Power Wiring Outdoor mm2 3 4mm2 3 4mm2 Signal Wiring mm2 3 2 5mm2 2 1m m 2 3 1mm2 2 1mm 2 3 1mm 2 3 1mm2 Wireless Remote Controller YKR H 009E YKR H 009E YKR H 009E Qty per 20 40 40HQ Only For Reference Set 54 114 142 40 80 114 40 80 114 Note 1 Working condition of the cooling capacity measured Inside the room DB ...

Страница 39: ...r grooved Φ7 Inner grooved Coil Length x Height x Width mm 950 264 57 15 950 264 57 15 1300 246 38 1 Heat Exchanging Area m2 14 56 14 56 13 69 Indoor Unit Indoor Air Flow Hi Mi Lo m 3 h 1500 1200 1050 1500 1200 1050 1800 1440 1260 Noise Level Hi Mi Lo dB A 50 47 41 50 47 41 51 48 42 Net Dimension W H D mm 1280 660 205 1280 660 205 1631 660 205 Packing Dimension W H D mm 1360 720 280 1360 720 280 1...

Страница 40: ...del Indoor Outdoor Factory Model Indoor Outdoor Power Supply V Hz P h 380 415 50 3 380 415 50 3 380 415 50 3 Capacity Cooling Btu h 48000 60000 60000 kW 14 0 17 6 17 6 Heating Btu h 51000 63500 kW 15 0 18 5 Electric Data Rated Cooling Power Input kW 4 87 5 71 5 71 Rated Heating Power Input kW 5 13 5 97 Rated Cooling Current A 9 32 10 93 10 93 Rated Heating Current A 9 82 11 48 Performance EER W W ...

Страница 41: ...4 107 Connection Wiring Power Wiring Indoor mm 2 3 1mm 2 3 1mm 2 3 1mm 2 Power Wiring Outdoor mm 2 5 2 5mm 2 5 2 5mm 2 5 2 5mm 2 Signal Wiring mm2 2 1mm2 2 1mm2 2 1mm2 Wireless Remote Controller YKR H 009E YKR H 009E YKR H 009E Qty per 20 40 40HQ Only For Reference Set 20 41 43 20 41 43 20 41 43 Note 1 Working condition of the cooling capacity measured Inside the room DB temperature 27 WB temperat...

Страница 42: ...g capacity amendment coefficient of cooling capacity nominal cooling capacity nominal cooling capacity could be found from the performance parameters list amendment coefficient of cooling capacity could be found from table above 3 3 Amendment coefficient of heating capacity under different indoor outdoor DB WB temperature Actual heating capacity calculation Actual heating capacity amendment coeffi...

Страница 43: ... coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit 3 5 Different Heating Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit Height Difference H m Cooling Equivalent pipe length EL m Height Difference H m Equivalent pipe length EL m Heating ...

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ...50 ...

Страница 48: ...nal wire Wired controller Control wire Signal wire Power cable Control wire Indoor unit Outdoor unit Indoor unit Outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire ...

Страница 49: ...utdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire Indoor unit Outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire ...

Страница 50: ...utdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire Indoor unit Outdoor unit Multicore signal wire Wired controller Signal wire Power cable Control wire Control wire ...

Страница 51: ...54 ...

Страница 52: ...inage pump High Mid Low Neutra Indoor fan output Float switch Buzzer 4 DIP switch Return air temp Indoor coil temp input Wired control receiver Transformer output 3 DIP switch Remote control receiver Neutral Low Mid High Compressor output Drainage pump output Electric heating output Outdoor fan output Indoor fan output 4 way valve Neutra l insert Wired control receiver Remote control receiver Step...

Страница 53: ... than 8mm Wrench 2 pcs one of them is with adjustable torque wrench 42N m 65N m 100N mm Power cable electrical wire between indoor and outdoor unit Must be in accordance with the wire diameter in the wiring diagram Nitrogen cylinder in order to prevent oxidation when welding using Nitrogen to replace the air 6 2 The distance between indoor unit and obstacle 6 3 Indoor unit suspension Select the su...

Страница 54: ...er insulation pipe with the thickness of more than 8mm Drainage pipe must have a downward gradient 1 50 1 100 If the drain pipe is installed ups and downs it will cause water backflow or leakage etc The pipe should not rise at any point When finish installation please carry out the drainage test to ensure that the water flow through the pipeline fluently and carefully observe the junction to ensur...

Страница 55: ......

Страница 56: ......

Страница 57: ......

Страница 58: ......

Страница 59: ...5 35 50 Refrigerant Oil ml 480 480 750 OutdoorFan Motor Model YDK30 6A YDK30 6A YDK65 6B code R60020113800 R60020113800 R60020207200 Brand AUX AUX AUX Output Power x Fan quantity W 30 1 30 1 65 1 Capacitor uF 2 5 2 5 4 Speed r min 770 770 870 Coil Number Of Row 2 2 2 Tube Pitch a x Row Pitch b mm 20 5 12 7 20 5 12 7 22 19 05 Fin Pitch mm 1 6 1 6 1 6 Fin Material Hydrophilic aluminum fin Tube Outsi...

Страница 60: ... Stuffing Quantity 20 40 40H Unit 61 132 167 61 132 167 54 112 135 Power Supply V Hz P h 220 240 50 1 220 240 50 1 220 240 50 1 Max Input Consumption W 2650 3200 3200 Max Current A 12 0 14 5 14 5 Capacity Cooling Btu h 18000 24000 24000 kW 5 3 7 2 7 2 Heating Btu h 20000 27500 kW 5 8 8 1 Compressor Model PA215X2CS 4KU 1 PA290X3CS 4MU I PA290X3CS 4MU I Type ROTARY ROTARY ROTARY Brand TOSHIBA TOSHIB...

Страница 61: ...3 71 23 71 Air Flow Volume CFM 1529 1641 1641 m 3 h 2600 2790 2790 Noise Level dB A 55 60 60 Dimension W D H Net mm 800 300 590 800 300 690 800 300 690 Packing mm 930 410 660 930 410 760 930 410 760 Weight Net kg 36 48 49 Gross kg 40 52 53 Refrigerant Type Quantity Type R410A R410A R410A Charged Volume g 1360 2360 2360 Design Pressure MPa 4 15 4 15 4 15 Refrigerant Piping Liquid Side mm 6 35 9 52 ...

Страница 62: ...Input W 3270 3270 4270 Rated Current RLA A 5 8 5 8 7 3 Locked Rotor Amp LRA A 49 49 58 Thermal Protection temp 155 5 155 5 160 5 Capacitor uF Refrigerant Oil ml 1200 1200 1300 OutdoorFan Motor Model YDK150 6C 420 YDK150 6C 420 YDK68 6 359 code R60020114400 R60020114400 R60020200600 Brand WEITELI WEITELI WEITELI Output Power x Fan quantity W 150 1 150 1 68 2 Capacitor uF 6 6 3 2 Speed r min 820 820...

Страница 63: ...fing Quantity 20 40 40H Unit 30 64 77 30 64 77 20 42 44 Notes 1 Nominal cooling capacities are based on the following conditions Return air temp 27 DB 19 WB and outdoor temp 35 DB 24 WB 2 Nominal heating capacities are based on the following conditions Return air temp 20 DB and outdoor temp 7 DB 6 WB 3 Parameters above are all measured when the connecting pipe is 5 meters Model Factory Model Power...

Страница 64: ...1090 430 1370 1090 430 1370 1090 430 1370 Weight Net kg 88 101 89 Gross kg 102 115 103 Refrigerant Type Quantity Type R410A R410A R410A Charged Volume g 2850 2850 2850 Design Pressure MPa 4 15 4 15 4 15 Refrigerant Piping Liquid Side mm 9 52 9 52 9 52 Gas Side mm 19 05 19 05 19 05 Max Length m 50 50 50 Max Height m 30 30 30 Operation Temperature Range 16 32 16 32 16 32 Ambient Temperature Range Co...

Страница 65: ... 1 12 1 07 1 02 0 96 0 93 30 22 1 19 1 13 1 08 1 02 0 99 32 24 1 26 1 20 1 15 1 08 1 05 Actual cooling capacity calculation Actual cooling capacity amendment coefficient of cooling capacity nominal cooling capacity nominal cooling capacity could be found from the performance parameters list amendment coefficient of cooling capacity could be found from table above 2 3 Amendment coefficient of heati...

Страница 66: ... from table above 2 4 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit 2 5 Different Heating Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit Height Difference H m Cooling Equivalent pipe len...

Страница 67: ...540 760 111 539 257 287 322 130 300 326 590 800 540 4 10 19 370 ...

Страница 68: ...130 370 4 10 19 540 800 690 326 300 606 332 400 354 11 71 903 857 ...

Страница 69: ...148 1255 180 945 413 373 4 10 19 585 340 ...

Страница 70: ...s continuous supplied to the air conditioned area though Duct by fan motor Heating cycle It is the contrary cycle of cooling cycle at this moment the 4 way valve changes direction and make refrigerant flow to direction changer that is the vapor discharged from the compressor enters into the indoor heat exchanger to condense the condensation of refrigerant after the capillary expenditure evaporates...

Страница 71: ...Valve Condenser Fan Evaporator Stopping Valve liquid Stopping Valve gas One Way Valve Capillary Cooling Capillary Heating Refrigerant flow direction in Cooling Refrigerant flow direction in Heating T Ambient T Evaporator T Discharge T Condenser T Mild Condenser indoor unit Fan ...

Страница 72: ...152 ...

Страница 73: ......

Страница 74: ......

Страница 75: ...155 Introduction of Control Board QRD SW3F HCE1 outdoor unit board sockets Power supply 380V 415V ...

Страница 76: ... valve board 1 12 截止阀组件 1 4in Stop valve 1 4in 1 13 截止阀组件 1 2in Stop valve 1 2in 1 14 电器盖板 Cover for electric components 1 15 四通阀管路组件 Four way valve assembly 1 15 1 四通阀 Four way valve loop 1 Not including Cooling 15 2 四通阀线圈 Four way valve loop 1 16 顶盖板 Top cover board 1 17 电器架总成 Electric assembly 1 17 1 电容 35μF Capacitor for Compressor 1 35μF 17 2 电容 2 5μF Capacitor for fan motor 1 2 5μF 17 3 端子板 ...

Страница 77: ...157 17 6 传感器 1m Sensor 1m 1 5K3470 EL2A 18 冷凝器总成 condenser assembly 1 18 1 冷凝器组件 condenser part 1 18 2 制冷毛细管 Cooling capillary 1 18 3 制热毛细管 Heating capillary 1 ...

Страница 78: ...otor bracket assembly 1 9 隔风立板 Wind defending vertical board 1 10 底盘组件 Chassis assembly 1 11 压缩机 Compressor 1 PA215X2CS 4KU1 12 右侧板 Right hand board 1 13 阀板 Stop valve board 1 14 截止阀组件 1 4in Stop valve 1 4in 1 15 截止阀组件 1 2in Stop valve 1 2in 1 16 电器盖板 Cover for electric components 1 17 四通阀管路组件 Four way valve assembly 1 17 1 四通阀 Four way valve loop 1 Not including Cooling mode 17 2 四通阀线圈 Four way v...

Страница 79: ...bracket assembly 1 9 隔风立板 Wind defending vertical board 1 10 底盘组件 Chassis assembly 1 11 压缩机 Compressor 1 PA290X3CS 4MUI 12 右侧板 Right hand board 1 13 阀板 Stop valve board 1 14 截止阀组件 3 8in Stop valve 3 8in 1 15 截止阀组件 5 8in Stop valve 5 8in 1 16 电器盖板 Cover for electric components 1 17 四通阀管路组件 Four way valve assembly 1 17 1 四通阀 Four way valve loop 1 Not including Cooling 17 2 四通阀线圈 Four way valve loop ...

Страница 80: ...tor bracket assembly 1 9 底盘组件 Chassis assembly 1 10 气液分离器组件 Flash chamber assembly 1 11 回气管组件 Return air pipe assembly 1 11 1 低压开关 Low Pressure Switch 1 12 压缩机 Compressor 1 E404DH 38D2G 13 油温加热带 Oil heat strap 1 14 阀板 Stop valve board 1 15 截止阀组件 3 8in Stop valve 3 8in 1 16 截止阀组件 5 8in Stop valve 5 8in 1 17 电器盖板 Cover for electric components 1 18 右侧板 Right hand board 1 19 四通阀管路组件 Four way valve ass...

Страница 81: ...or 1 20 5 控制板 PCB board 1 QRD SW1C HCE1 20 6 变压器 Transformer 1 20 7 传感器 1 3m Sensor 1 3m 1 5K3470 XH2 20 8 传感器 0 9m Sensor0 9m 1 6 3K3954 XH2 20 9 传感器 0 9m Sensor 0 9m 1 5K3470 XH2 21 电器架固定板 Electric components bracket 1 1 顶盖板 Top cover board 1 2 电机架组件 Motor bracket assembly 1 3 大面板 Big panel 1 4 面板网罩 Net for big panel 2 5 轴流风叶 Axial flow wind leaves 2 6 小面板 Small panel 1 7 室外风扇电机 Outdoor Motor 2 ...

Страница 82: ...our way valve loop 1 14 4 消音器 Muffler 1 15 右侧板 Right hand board 1 16 阀板组件 Stop valve assembly 1 16 1 截止阀3 8in Stop valve 3 8in 1 16 2 截止阀3 4in Stop valve 3 4in 1 17 电器盖板 Cover for electric components 1 18 气液分离器 Flash chamber 1 19 电器总成 Electric assembly 1 19 1 控制板 PCB board 1 19 2 交流接触器 AC contactor 1 19 3 电容3μF Capacitor for fan motor 1 3μF 19 4 端子板 Terminal board 1 19 5 变压器 transformer 1 19 6 传感器...

Страница 83: ...阀 Four way valve 1 Not including Cooling only units 14 3 四通阀线圈 Four way valve loop 1 14 4 消音器 Muffler 1 15 右侧板 Right hand board 1 16 阀板组件 Stop valve assembly 1 16 1 截止阀3 8in Stop valve 3 8in 1 16 2 截止阀3 4in Stop valve 3 4in 1 17 电器盖板 Cover for electric components 1 18 气液分离器 Flash chamber 1 19 电器总成 Electric assembly 1 19 1 控制板 PCB board 1 19 2 交流接触器 AC contactor 1 19 3 电容3μF Capacitor for fan motor...

Страница 84: ...on of outdoor unit The site shall be strong enough to bear its weight prevent noise and vibration The site shall be ensured to avoid direct sunshine if necessary set a Havelock above the outdoor unit The site shall be easy to drainage the rain water and the frost water The site shall be ensured that the outdoor unit will not be covered by snow LDring the winter season The site shall be ensured tha...

Страница 85: ...or air to remove the dust and water in the pipe Please lay out the piping according to the tend towards of the piping but it is not allowed more than 3 times curved at the same point of the pipe if do like this the pipe will become rigid Pipe bending machine is used during the process of bending the pipe the curvature shall not be too small or it will affect the refrigerant flow Piping specificati...

Страница 86: ...e length should be L 25 0 35 5 2 4 2 31 5 m Specification of connection pipe for indoor unit and outdoor unit Cooling Capacity Btu h 12000 18000 24000 36000 48000 60000 Connection Pipe mm Liquid Pipe Φ6 35 Φ6 35 Φ9 52 Φ9 52 Gas Pipe Φ12 7 Φ12 7 Φ15 88 Φ19 05 Max Length m Liquid Pipe Dia Φ6 35 Φ6 35 Φ9 52 Φ9 52 Gas Pipe Dia Φ12 7 Φ12 7 Φ15 88 Φ19 05 Max Length 15 20 30 50 Max Height m 10 15 15 30 M...

Страница 87: ... with liquid valve 1 Connect the gas valve of the stop valve to the thimble side of the rubber hoses the other side of rubber hoses should be connected to the refrigerant tank 2 Open the refrigerant tank valve using the refrigerant inside the tank with high speed to empty the air in the indoor unit and the connection piping When the outlet air becomes mist it feels cold by touching it then the air...

Страница 88: ...art of indoor unit which get in touch with the back side of ceiling should pasted with insulation material Besides the previously more than 8mm thick insulation material connection piping both gas pipe and liquid pipe drainage pipe should be wrapped by additional 10 30 mm thick insulation material To seal the hole on the wall To prevent rainwater or other foreign bodies from entering the room and ...

Страница 89: ... 1mm φ9 52 0 75mm 0 05 φ19 05 1mm φ9 52 0 75mm 0 07 φ19 05 1mm φ12 7 1mm 0 09 Others Users to install the air conditioner at site shall ensure that the oil can return to the unit smoothly Horizontal pipes should incline toward the outdoor unit using a 20 1 slop e If there is a height difference between the indoor and outdoor unit oil loops should be installed in the inter connecting gas large pipe...

Страница 90: ...ical connection precaution Warning Installation of electric items must be carried out by qualified professional technicians An isolated circuitry should be fixed with whole pole disconnection devices which is with at least 3mm gap of touch point Power supply and indoor to outdoor connection should use special cable Providing the necessity of installation or replacement the professional technician ...

Страница 91: ...or outdoor refer to the section of part 1 Recommendation of power supply cord Power supply 220V 50Hz Cooling capacity Btu h Model Power supply spec Power supply side Power supply cord Connection wires Indoor side 3 1 5mm2 3 1 5mm2 Indoor side 3 2 5mm 2 3 2 5mm 2 Outdoor side 3 4mm2 4 1mm2 Power supply 380V 415V 3N 50Hz Cooling capacity Btu h Model No Power supply spec Power supply cord of indoor u...

Страница 92: ... or more frequently if required When the filter is very dirty it can be washed in detergent and hot water below 45 Ensure the filter is fully dry before reinstallation to avoid risk of electric shock or short circuiting Do not dry the filter using direct sunlight Check at the beginning of each season Check whether there are no physical obstructions at the air inlet or outlet of either indoor or ou...

Страница 93: ...in components of air conditioner 179 2 Electrical system main components 182 3 Poor efficiency explanation 184 4 Failure phenomenon 185 5 Electric components malfunction inspection 186 6 Failure code display 187 7 Failure analysis 189 ...

Страница 94: ...nd high pressure gas and then send the gas to condenser make the refrigerant cycle in this series products all the compressors are complete hermetic compressor in which motor and compressor are together Scroll compressor condenser heat exchanger The function of condenser Make the high temp and high pressure refrigerant gas discharged by compressor become liquid make the gas heat exchange with air ...

Страница 95: ...igerant flow quantity and pressure One way valve One way valve is used for heat pump unit it make the refrigerant liquid only flow as the arrow direction Four way valve Function of 4 way valve When change cooling mode into heating mode it will change the flow direction of refrigerant When heating the valve get electricity cooling without electricity the slip assembly move to the right connect pipe...

Страница 96: ...Function To stop or release refrigerant only on off can t adjust or throttle Muffler Function Eliminate the system noise Gas and liquid separator Function Separate liquid and gas refrigerant to protect the compressor ...

Страница 97: ...r Pressure switch Function To avoid the air conditioner work in a abnormal pressure making the air conditioner work safety Capacitor Induce the single phase motor produce gyre magnetic field connect with the accessory winding and participate in the operation AC Contactor When AC contactor s inner magnetic loop without power the counter force of spring and the weight of armature core will make the ...

Страница 98: ...ain circuit is still disconnect need to press start button to restart unit Condensate pump Only for Cassette the pump head is 1 2 meter the condensate pipe must have over 1 100 descend angle after unit cooling or dehumidify stops running the pump will still work 3 minutes to clean the condensate Sensor Physical properties will change along with the temperature pressure change used for check temper...

Страница 99: ...r starting or fuse be burned out etc It is not malfunction need to find out the causing if the causing is the electricity net voltage is too low user should load a power manostat to keep voltage between 220V 380V for AC normally running Select high wind speed but indoor temperature still at high side air flow from the air outlet is too weak It is because air filter is too dirty or blocked making c...

Страница 100: ...erature causing harsh sounds 3 Liquid sound is from refrigerant flowing Sometimes the room is smelly 1 The AC itself will not be smelly if it is smelly it is because environment smell accumulated 2 Solution clean the filter when heating there is no wind at the beginning of starting unit 1 It is to prevent cold air blowing please be patient 2 The unit has auto restart function when it is repowered ...

Страница 101: ...urn and melt phenomenon 6 The winding has resistance value below 1000 but cannot be nil or infinite 4 4 ways valve winding The winding has resistance value below 1000 but cannot be nil or infinite 5 Capacitor 7 No expansion phenomenon apparently 8 Measure capacitor by using capacitor phase of multi meter if the multi meter has no capacitor phase use ohm phase contact the two terminal of meter to t...

Страница 102: ...2 times 1s E2 6 non stop Indoor heating over load protection None 7 shutdown Defrosting not failure Operation lamp flash None 8 non stop 6 2 Unit failure code for unit power supply is 380 415V Failure causing Display mode1 indication lamp on display lamp board Display mode1 failure lamp on control board Display mode3 wired controller Display priority Phenomenon Communication failure Flash 5 times ...

Страница 103: ...nsor abnormal TA Flash 1 times and go out 2S E1 4 shutdown Indoor coil sensor abnormal TE Flash 3 times and go out 2S E3 5 shutdown Outdoor coil sensor abnormal TW Flash 2 times and go out 2S Flash 2 times and go out 2S E2 8 non stop Outdoor condensate temp Sensor abnormal TL Flash 7 times and go out 2S Flash 7 times and go out 2S E7 9 non stop Discharging temp sensor abnormal TP Flash 8 times and...

Страница 104: ...186 7 Failure analysis Wired controller communication failure ...

Страница 105: ...187 Communication failure between indoor and outdoor unit ...

Страница 106: ...188 Outdoor protection phase sequence ...

Страница 107: ...189 Cooling high pressure protection ...

Страница 108: ...190 Heating high pressure protection ...

Страница 109: ...191 Cooling low pressure protection ...

Страница 110: ...192 Heating low pressure protection ...

Страница 111: ...193 Cooling exhaust temperature protection ...

Страница 112: ...194 Heating exhaust temperature protection ...

Страница 113: ...195 Refrigerant shortage or four way valve failure protection ...

Страница 114: ...196 Sensor failure protection ...

Страница 115: ...197 No action after power on ...

Страница 116: ...198 Poor effect ...

Страница 117: ...199 ...

Страница 118: ...200 Abnormal sound or viberation ...

Страница 119: ...201 ...

Страница 120: ...202 Abnormal odor ...

Страница 121: ...203 Air switch action when air conditioner starting up ...

Страница 122: ...204 Air conditioner water leakage ...

Страница 123: ...ess the button can adjust temperature Temperature adjustment range 16 32 Fan button Change the fan speed will change in turn as Auto Low Medium High Auto Swing button Press this button for the first time when operation it will start the swing function Push the button for the second time cancel the swing function The function is available matched with the concerned unit Health button Press this but...

Страница 124: ...utton of Timer can cancel timing setting Notes 1 Time sequence of timing ON and OFF determines the order of Timing ON Timer OFF and Timer OFF Timing ON If the both are the same or either one is the same as time of current clock it is invalid to press Timer button to confirm presetting time after it reaches the presetting time it will implement corresponding timing operation 2 After setting time of...

Страница 125: ...44 9 21 55 32 3 835 72 1 013 8 20 56 33 3 695 73 0 9837 7 19 61 34 3 562 74 0 9550 6 18 72 35 3 434 75 0 9273 5 17 87 72 3 311 76 0 9005 4 17 06 37 3 193 77 0 8746 3 16 30 38 3 081 78 0 8496 2 15 57 39 2 972 79 0 8254 1 14 88 40 2 869 80 0 8021 0 14 23 41 2 769 81 0 779 1 13 60 42 2 673 82 0 758 2 13 01 43 2 581 83 0 737 3 12 45 44 2 493 84 0 716 4 11 91 45 2 409 85 0 696 5 11 40 46 2 307 86 0 677...

Страница 126: ...30 9 244 0 31 37 59 71 8 428 111 2 460 8 231 7 32 36 06 72 8 152 112 2 392 7 220 0 33 34 59 73 7 885 113 2 326 6 209 0 34 33 21 74 7 628 114 2 262 5 198 6 35 31 88 75 7 381 115 2 201 4 188 7 36 30 60 76 7 143 116 2 141 3 179 4 37 29 39 77 6 914 117 2 083 2 170 7 38 28 23 78 6 693 118 2 026 1 162 4 39 27 13 79 6 480 119 1 972 0 154 5 40 26 07 80 6 276 120 1 920 1 147 1 41 25 06 81 6 075 121 1 868 2...

Страница 127: ... 54 15 30 94 4 040 134 1 331 15 75 71 55 14 74 95 3 920 135 1 297 16 72 33 56 14 22 96 3 803 136 1 266 17 69 13 57 13 71 97 3 691 137 1 234 18 66 08 58 13 23 98 3 583 138 1 204 19 63 18 59 12 77 99 3 478 139 1 174 ...

Отзывы: