Innovative Circuit Technology Ltd.
45
Minimum E-mail Interval
: Specify a minimum interval required between e-
mail notifications. (Default 1 minute, range 0 to 60 minutes) This time
interval is used to prevent an un-intended flood of e-mail alarm
notifications that could occur when an alarm limit is incorrectly configured,
for example.
General E-mail Notifications
:
Select these options to receive an e-mail when one or more of these events
occurs:
AC Input Power is lost
: Check this box to receive an e-mail notification
when the ac input drops below a functional level.
Power Module failure occurs
: Check this box to receive an e-mail
notification when any of the installed power modules stop functioning.
A Module is offline
: Check this box to be notified when a module loses
communication with the ICM.
System Current Limit is triggered:
Check this box to get a notification each
time the system output current hits the maximum current limit value
Intelligent Controller Module reset:
Check this box for notification of an
ICM reset for any reason.
The Network Watchdog triggers
: Check this box to receive an e-mail
notification after the Network Watchdog triggers due to a loss of the
network connection and the network has then come back online.
USER SETUP:
Select the
USER SETUP
tab to set up and configure the password for up to 10
users, with the ability to limit who has access to the power system settings. Click
on the
Save User Settings
button at the bottom of the page to save any
password changes.
The unit has no password assigned by default, so an Administrator password
should be assigned to your power system for improved security.
NOTE:
Record your new password(s) for future access! If the Administrator password is
lost the unit must be reset to return the password to the blank default setting,
causing loss of all other user settings. See the
Password Reset
section for more
details.