24
Innovative Circuit Technology Ltd.
Password Reset (Front panel)
Always record the display password when set, as it must be entered to change
any power shelf settings. To clear the display password in cases where it is lost,
switch off the AC power to the unit, then simultaneously press the ENTER and
BACK
X
buttons for more than 15s while restoring the AC power. A new
password will then have to be re-entered as shown above if password
protection is required.
Reset the web-GUI password back to the factory default (user: admin, no pw) by
selecting
RESET COMM SETTINGS
in the Network Status, Advanced Options
front panel display menu shown above.
OPERATION (No ICM)
Power Modules installed in a basic shelf without an Intelligent Control Module
(ICM) will behave as a fixed output power supply, with the output voltage and
current limit set to the factory default levels. Modules may still be hot-swapped
with identical replacement units, and the output load will share across all active
power modules.
Check that each module’s green “POWER” LED is lit, indicating normal
operation. A lit red “
ALARM
” LED indicates a faulted module. Momentarily
withdraw the faulted module then re-insert once the LED is off to check if the
fault can be re-set. If the fault persists while other modules are operating
normally the faulted module must be replaced.
DC-DC Converter modules installed in a basic shelf without an Intelligent Control
Module (ICM) will behave as a fixed output converter, with the output voltage
and current limit set to the factory default levels. During normal operation the
DC-DC Converter mod
ule’s green “POWER” LED will be lit. A lit red “ALARM” LED
indicates a module fault.
Alarm indications can be monitored remotely using the Form-C alarm relay
contacts accessible via the back panel ALARM connector. (See the Installation
section for connection information)
OPERATION (web-GUI)
Connect to your Intelligent Hybrid Power Series via the Ethernet for full access
to all system settings, status, and alarm conditions. Units with the ICM installed
are equipped with a built-in web server that can be accessed via any standard
web browser on a network connected computer or phone. No additional
software is required on your device.