34
Innovative Circuit Technology Ltd.
Start Time:
Set the time of day for automatically recurring discharge test to
start. The time must be entered using 24-hour time format.
[note]
Day of Week takes precedence over Discharge Test Interval.
NTP Time Synchronization must be enabled on the
Communications Basic
Setup
page to enable automatic discharge tests.
[Note] that a discharge test can only be initiated when the battery is fully
charged. If the system is unable to start a Discharge Test at the selected
Start Time, it will attempt again at the same time next day, or next week if a
specific Day of Week is selected.
You may alternatively manually initiate a Battery Discharge Test of a fully
charged battery by pressing the
Manual Discharge Test
button. (System will
state that the discharge test is
Not Ready
if the battery SOC is less than
100%)
The most recent discharge test results are shown here, with fields for days
since the
Last Battery Discharge Test
,
Status
(Pass or Fail),
Discharge Time
,
End Voltage
at the completion of the test, and the
Amp-Hours Discharged
during the test. The scheduled date of the next automatically repeating test
will also be shown if this feature has been enabled.