Status Code 5
ABNORMAL FLAME-PROVING SIGNAL - This status code indicates the flame signal was sensed while gas valve GV was de-
energized. The inducer will run until the fault is cleared.
STEP
ACTION
YES
NO
GO TO
1.
Turn off gas to the furnace by shutting off the external manual shut-off valve.
2
2.
Does status code 5 stop flashing?
3
4
3.
Replace the gas valve.
8
4.
Disconnect wire from the flame-proving sensor electrode FSE.
8
5.
Does status code 5 stop flashing?
6
7
6.
Clean flame sensor with fine steel wool. Remove burner gang and inspect. Remove any
spider webs or unusual carbon deposits near where the flame sensor is located.
8
7.
Replace the modulating furnace control.
8
8.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
INDEX
Status Code 6
IGNITION-PROVING FAULT - This status code indicates flame was not sensed during trial for ignition period. The control
will repeat ignition sequence 3 more times before going to status code 6 + 1 - IGNITION LOCKOUT. This status code can
also indicate flame signal was lost during steady-state operation.
STEP
ACTION
YES
NO
GO TO
1.
Shut the power off, remove the blower door, and disconnect communication connector PL7
(if used) or the R thermostat lead (if used) from the furnace control board.
2
2.
Turn the power on and depress the door switch. Use a piece of tape to hold it closed.
3
3.
Jumper the R and W/W1 thermostat terminals.
4
4.
Observe the operation of the furnace through a heating cycle.
5
5.
Does status code 6 flash?
9
6
6.
Does a different status code flash?
7
8
7.
Go to page number indicated in the Index for the section covering the status code.
INDEX
8.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
INDEX
9.
Turn off the power and disconnect the jumper across the R and W/W1 thermostat terminals.
10
10.
Turn the power on.
11
11.
Check the hot surface igniter. To do this run a COMPONENT TEST by putting setup switch
SW1-6 in the ON position. Does the igniter glow orange/white hot by the end of the 15
second warm-up period?
16
12
12.
Hook an AC voltmeter across PL2-3 and L2 on the modulating furnace control. Repeat the
COMPONENT TEST by turning setup switch SW1-6 OFF and then back ON. Is 115-vac
across PL2-3 and L2 during the 15 second warm-up period?
14
13
13.
Replace the modulating furnace control.
8
14.
Check continuity in harness and igniter. Replace failed component.
15
15.
Fix problem.
8
16.
Put setup switch SW1-6 in the OFF position, jumper the R and W/W1 thermostat terminals,
and monitor voltage across BLUE and GREEN/YELLOW wires to gas valve GV.
17
17.
Just before status code 6 begins flashing was 24-vac across BLUE and GREEN/YELLOW
wire to gas valve GV?
21
18
18.
Turn off the power.
19
19.
Do you have continuity across the following connections?
- PL1-10 and PL17-5, BLUE wire from the modulating furnace control to gas valve GV.
13
20
20.
The BLUE wire from the modulating furnace control to the gas valve GV is not making a
good connection. Repair the wire or replace the harness.
8
21.
Does the gas valve open and allow gas to flow?
24
22
22.
Are all the manual gas cocks and the gas valve switch in the ON position?
23
15
23.
Replace gas valve.
8
24.
Do the main burners ignite?
26
40
25.
Check for the following:
- Inadequate flame carryover or rough ignition.
- Low inlet gas pressure.
- Flue gas leak into vestibule.
- Proper firing rate.
15