26.
Is 115-vac across the transformer leads?
27
25
27.
Replace the transformer.
18
28.
Is 24-vac across W/W1 and on the modulating furnace control?
You will not be able to check for voltage across W/W1 and C
OM
-24V if the furnace is
connected to a Communicating Wall Control at communication connector PL7. Go to step
29.
30
29
29.
You have a defective thermostat, or a break in wiring between thermostat and furnace. Fix
problem.
18
30.
Disconnect all thermostat leads from the thermostat terminal block and jumper R to W/W1.
Does the furnace respond to the call for heat?
31
25
31.
You have an incompatible thermostat. Do any of the following:
- Wire the thermostat C terminal to C
OM
-24V.
- Isolate the W/W1 input with a relay.
- Install ballast resistor across W/W1 and C
OM
-24V.
- Replace the thermostat with a compatible model.
18
32.
Turn power off. Remove secondary voltage fuse from the modulating furnace control and
check the continuity of the fuse.
33
33.
Is the secondary voltage fuse open?
34
25
34.
Go to page number indicated in Index for the section covering SECONDARY VOLTAGE
FUSE IS OPEN.
INDEX
AMBER LED ON SOLID – Check to make sure the correct model plug PL4 is installed. The
rating plate shows the correct model plug for this furnace.
If the correct model plug is
installed then the control is locked out and will auto reset after 1 hour. Lockout could be due
to any of the following:
-
Flame sense circuit failure.
-
Gas valve relay stuck open.
-
Software check error.
Reset power to clear lockout. Replace control if status code repeats.