background image

- 13 -

MINIMUM AND/OR MAXIMUM HEAT TEMPERATURE RISE TOO LOW - Generally, this
indicates the furnace is extremely underfired.

STEP

ACTION

YES

NO

GO TO

1.

Remove the blower door. Disconnect the communication connector PL7 (if used) or the R

thermostat lead (if used) from the furnace control board. If setup switch SW4-2 is ON then

turn it OFF.

2

2.

Depress the door switch. Use piece of tape to hold it closed.

3

3.

Put setup switch SW1-2 into the ON position.

4

4.

Jumper R, W/W1, and W2 thermostat terminals.

5

5.

Once the blower motor turns ON and the furnace is running in maximum heat, clock the

maximum heat gas rate. On propane installations check the manifold pressure.

6

6.

Is the maximum heat rate within 2% of that specified on the rating plate?

9

7

7.

Ensure the gas inlet pressure and burner orifices are correct. Reference the Installation, Start-

Up, and Operating Instructions. Then adjust maximum heat on the gas valve to the proper

manifold pressure. If maximum heat cannot be adjusted to the proper manifold pressure,

replace the gas valve GV.

Note:

The modulating furnace manifold pressure is set at two points. The first point is

maximum heat. The second point is minimum heat. Both adjustments are independent and

are done with the same rotary adjustment switch on the modulating gas valve. When

adjusting do not apply excessive force as you may damage the rotary adjustment switch. To

adjust, slowly turn the rotary adjustment switch counterclockwise to decrease manifold

pressure or clockwise to increase manifold pressure. Turn the rotary adjustment switch one

click per second until you obtain the desired manifold pressure. If you turn the rotary

adjustment switch too quickly the manifold pressure will not change.

11

8.

Fix problem.

11

9.

Check maximum heat temperature rise and external static pressure with blower door in place.

Temperature rise should be mid range or higher than midpoint of range stated on furnace

rating plate. External static pressure in maximum heat should be less then .7 in.w.c. If

return temperature is below 60 deg. F condensation may form on heat exchangers. If left

uncorrected failure will result.

10

10.

Remove the jumper from the R and W2 thermostat terminals. When the furnace is running in

minimum heat, clock the minimum heat gas rate. On propane installations check the

manifold pressure.

12

11.

Go to the page number indicated in Index for the CLEANUP AND STARTUP

INSTRUCTIONS.

INDEX

12.

Is the minimum heat rate within 2% of that specified on the rating plate?

14

13

13.

Ensure the gas inlet pressure and burner orifices are correct. Reference the Installation, Start-

Up, and Operating Instructions. Then adjust minimum heat on the gas valve to the proper

manifold pressure. If minimum heat cannot be adjusted to the proper manifold pressure,

replace the gas valve GV.

Note:

The modulating furnace manifold pressure is set at two points. The first point is

maximum heat. The second point is minimum heat. Both adjustments are independent and

are done with the same rotary adjustment switch on the modulating gas valve. When

adjusting do not apply excessive force as you may damage the rotary adjustment switch. To

adjust, slowly turn the rotary adjustment switch counterclockwise to decrease manifold

pressure or clockwise to increase manifold pressure. Turn the rotary adjustment switch one

click per second until you obtain the desired manifold pressure. If you turn the rotary

adjustment switch too quickly the manifold pressure will not change.

11

14.

Is outdoor condensing unit operating during heating cycle?

8

15

15.

Check minimum heat temperature rise and external static pressure with blower door in place.

Temperature rise should be mid range or higher than midpoint of range stated on furnace

rating plate. External static pressure in minimum heat should be less then .25 in.w.c. If

return temperature is below 60 deg. F condensation may form on heat exchangers. If left

uncorrected failure will result.

16

16.

Check return air ducts in unheated spaces for leaks.

11

440 08 4001 00

Содержание 9MAC/E series

Страница 1: ...hm 46 SAFETY CONSIDERATIONS Installing and servicing heating equipment can be hazardous due to gas and electrical components Only trained and qualified personnel should install repair or service heati...

Страница 2: ...in wc Thermostat wire connections to the furnace at R and W W1 are the minimum required for gas heating operation W2 must be connected for 2 stage heating thermostats Y Y2 and G are required to be co...

Страница 3: ...ted by the furnace control CPU and a 25 second prepurge period begins The RPM is used to evaluate vent system resistance This evaluation is then used to determine the required RPM necessary to operate...

Страница 4: ...mode in response to closing the thermostat R to W1 circuit Closing the thermostat R to W1 and W2 circuits always causes maximum heat operation regardless of the setting of the minimum heat only switch...

Страница 5: ...is based on the A C selection shown in Table 1 The electronic air cleaner terminal EAC 1 is energized with 115 vac whenever the blower motor BLWM is operating When the thermostat is satisfied the R t...

Страница 6: ...us blower airflow When the thermostat calls for high cooling the blower motor BLWM will switch to high cooling airflow When the thermostat is satisfied the blower motor BLWM will operate an additional...

Страница 7: ...Failed or Out of Calibration pressure switches Water in vent piping possible sagging pipe Disconnected or obstructed pressure tubing 4 LIMIT CIRCUIT FAULT Indicates the limit or flame rollout is open...

Страница 8: ...BLOWER MOTOR FAULT Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed time limits Thirty seconds after being turned ON or ten seconds during steady...

Страница 9: ...status code other than the heartbeat Note Status codes are erased after 72 hours or can be manually erased by putting setup switch SW1 1 in the ON position and jumpering R W W1 and Y Y2 simultaneousl...

Страница 10: ...C terminal to COM 24V Isolate the W W1 input with a relay Install ballast resistor across W W1 and COM 24V Replace the thermostat with a compatible model 18 32 Turn power off Remove secondary voltage...

Страница 11: ...ce the modulating furnace control 7 13 Reconnect the G thermostat lead or jumper and observe operation of furnace in cooling mode for 10 minutes 14 14 Does the furnace operate properly in cooling mode...

Страница 12: ...116 1302 1488 18601 DEF 5T 60 4882 6512 651 814 976 814 6512 814 976 9761 1139 1139 1139 1302 1302 1139 16271 16271 1139 1627 1953 DEF DEF DEF 3 5T 60 80 5T 80 100 BASED ON 325 CFM TON SETUP SWITCH SW...

Страница 13: ...d on furnace rating plate External static pressure in maximum heat should be less then 7 in w c If return temperature is below 60 deg F condensation may form on heat exchangers If left uncorrected fai...

Страница 14: ...energized Note On the modulating furnace control the HUM terminal is energized when the blower turns ON 3 18 18 Disconnect jumper wire across R and W W1 thermostat terminals and wait until blower stop...

Страница 15: ...r stops 49 49 Jumper R G and Y Y2 thermostat terminals 50 50 Does the AMBER LED turn off when G and Y Y2 are energized 3 51 51 Reconnect communication connector PL7 if used or all thermostat leads if...

Страница 16: ...on modulating furnace control 11 12 11 The main harness is miswired 7 12 Is 24 vac across VIOLET wire on the medium pressure switch MPS and COM 24V on modulating furnace control 15 13 13 Is 24 vac acr...

Страница 17: ...Is 24 vac across YELLOW wire on the low pressure switch LPS and COM 24V on modulating furnace control 14 10 10 Is 24 vac across connector terminal PL1 2 and COM 24V on modulating furnace control 11 13...

Страница 18: ...blem still persists and wind conditions are not excessive turn setup switch SW1 3 ON to boost inducer speed On the Communicating Wall Control select MIN INT RISE ADJ 8 45 Check for partially clogged d...

Страница 19: ...power off 15 15 Do you have continuity across limit switch LS 19 16 16 Wait for unit to cool then recheck for continuity across limit switch LS 17 17 Do you have continuity across limit switch LS 19 1...

Страница 20: ...The setpoint is 170 deg F but the switch opens at a temperature below 160 deg F 18 56 56 The problem may be related to poor air distribution or excessive pressure drop across filter Check filter and r...

Страница 21: ...ex for the section covering the status code INDEX 8 Go to page number indicated in Index for CLEANUP AND START UP INSTRUCTIONS INDEX 9 Turn off the power and disconnect the jumper across the R and W W...

Страница 22: ...heat 37 8 40 Turn off the power and disconnect the jumper across the R and W W1 thermostat terminals 41 41 Turn power on and jumper R W W1 and W2 thermostat terminals 42 42 Do the main burners ignite...

Страница 23: ...10 17 Do you have continuity across each flame rollout switch FRS 25 18 18 Can flame rollout switch FRS be reset 20 19 19 Replace flame rollout switch FRS 10 20 Reset flame rollout switch FRS install...

Страница 24: ...PUT OPERATION 40 51 OF MAXIMUM HEAT 40 45 OF MAXIMUM HEAT ON 5T 060 1 STEADY STATE If the medium pressure switch input turns ON the modulating furnace control begins flashing status code 9 and continu...

Страница 25: ...ating furnace control ramps inducer RPM up until the high pressure switch HPS remakes When the high pressure switch HPS remakes the modulating furnace control continues the heating cycle If high press...

Страница 26: ...and disconnect jumper wire across R and W W1 thermostat terminals 38 38 Connect 1 side of slope manometer with a tee to collector box pressure tap Refer to pressure check diagram in Appendix C 39 39 T...

Страница 27: ...akers or manual disconnects to the problem unit correctly set 11 10 10 Fix problem 5 11 Are the Auxiliary Limit switches properly set 12 10 12 Do you have 115 vac across L1 and L2 in the problem unit...

Страница 28: ...iter HSI come on during the cycle 15 24 15 Disconnect the humidifier lead from HUM terminal on modulating furnace control 16 16 Does the furnace still alternately cycle induced draft motor IDM and blo...

Страница 29: ...p switch SW1 6 in the ON position 9 10 9 Put setup switch SW1 6 in the OFF position 5 10 Is this a new service replacement control 19 13 11 You need to remove the model plug PL4 from the old control a...

Страница 30: ...from the furnace control board 2 2 Turn the power on and depress the door switch Use a piece of tape to hold it closed 3 3 Jumper the R and W W1 thermostat terminals 4 4 Observe the operation of the f...

Страница 31: ...30 Does the voltage drop as described in step 29 31 17 31 Put setup switch SW1 6 in the OFF position 32 32 Connect a DC voltmeter across terminals PL8 3 ORANGE and COM 24V then run COMPONENT TEST by t...

Страница 32: ...door switch Use a piece of tape to hold it closed 19 19 Do you have 115 vac across the BLACK blower motor wire connected to L1 and the WHITE blower motor wire connected to L2 21 20 20 Replace the mod...

Страница 33: ...rminals PL13 3 BLUE and PL13 4 GREEN Does the voltage fluctuate as described in step 28 15 32 32 You have an open wire or bad terminal on the BLUE wire between connectors PL3 and PL13 Repair it or rep...

Страница 34: ...ex for the section covering the status code INDEX 8 Go to page number Indicated in Index for CLEANUP AND START UP INSTRUCTIONS INDEX 9 Does the inducer motor turn on 27 10 10 Hook an AC voltmeter acro...

Страница 35: ...ng in direction shown on inducer housing 41 25 41 Turn power off and disconnect jumper from the R and W W1 thermostat terminals 49 42 Connect 1 side of slope manometer with a tee to collector box pres...

Страница 36: ...the furnace until ignition 5 5 Does status code 4 3 flash 9 6 6 Does a different status code flash 7 8 7 Go to page number indicated in the Index for the section covering the status code INDEX 8 Go to...

Страница 37: ...or is not running during lockout refer to status code 6 If the inducer motor is running at full speed during lockout this indicates that flame sense was lost 3 times within 60 minutes of cumulative ga...

Страница 38: ...ECTOR PL3 ECM BLOWER HARNESS CONNECTOR TRANSFORMER 24 VAC CONNECTIONS 3 AMP FUSE STATUS AND COMM LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR AIR CONDITIONING A C AIRFLOW SE...

Страница 39: ...39 Fig 2 Wiring Schematic 440 08 4001 00...

Страница 40: ...ines motor speed Setting up the desired airflow CFM for an ECM blower motor is done by setting the A C or CF selections on the modulating furnace control shown in figure 1 The ECM blower motor then de...

Страница 41: ...41 Figure 3 ECM Blower Motor 440 08 4001 00...

Страница 42: ...c max 0 70 in wc 0 05 0 62 in wc max 0 47 in wc 0 05 60 000 21 casing 1 46 in wc max 1 29 in wc 0 07 1 00 in wc max 0 85 in wc 0 05 0 64 in wc max 0 49 in wc 0 05 80 000 1 58 in wc max 1 40 in wc 0 08...

Страница 43: ...43 APPENDIX D STATIC PRESSURE READING LOCATION DIAGRAMS Figure 5 Upflow Total Static Pressure Reading Locations Figure 6 Downflow Total Static Pressure Reading Locations 440 08 4001 00...

Страница 44: ...20 in w c Coil Static Pressure Drop Wet 0 20 in w c Total ESP 0 60 in w c Both Examples 1 and 2 are correct Example 1 ESP readings were taken as laid out in static pressure reading location diagrams F...

Страница 45: ...amps Hot Surface Igniter Reading The Silicon Nitride igniter in this furnace is not voltage sensitive and will work within the voltage range of 102 to 132 VAC Hence there is no voltage regulation circ...

Страница 46: ...um heat operation EXAMPLE 1 Furnace ran for 45 seconds in intermediate heat 19 minutes in minimum heat MOD 40 and 5 minutes at maximum heat during previous call for heat MOD 40 MODT 19 MAXT 5 Calculat...

Страница 47: ...m Heat if the call for heat still exists The Modulating rate MOD for this cycle will be as determined Thermostat is satisfied Yes Yes Unit will start the next cycle in Maximum Heat and will remain run...

Страница 48: ...48 Replaces New Form ICP Eng 3 12 440 08 4001 00...

Отзывы: