Using recorded Modulating rate (MOD%), time of
operation at the Modulating rate (MODT), and
Maximum Heat (MAXT) calculate the Heat Load
(HLR) using:
HLR = (MOD% x MODT) + 65 + (100 x MAXT)
Is HLR<825
Is HLR>1965
MOD% = 40%
Unit will start the next cycle in
Intermediate Heat for 45 seconds
followed by 19 minutes of operation
at 40% rate before switching to
Maximum Heat if the call for heat still
exists.
The Modulating rate
MOD% for this cycle will
be as determined.
Thermostat is satisfied.
Yes
Yes
Unit will start the next cycle in
Maximum Heat and will remain
running in Maximum Heat until the
Thermostat is satisfied.
Calculated MOD% will be
calculated to the nearest
1%:
MOD% = (HLR – 65) / 19
MOD% = 100%
Unit will start the next cycle in
Intermediate Heat for 45 seconds
followed by 19 minutes of operation
at the calculated MOD% rate before
switching to Maximum Heat if the
call for heat still exists.